0. Space Type | BOS-School |
1. Establishment Name | Bates Phineas Elem |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 1.2 |
13. Max ACH | 3.3 |
14. Avg ACH | 2.4 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 84.5 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 839.8 |
22. cuft | 8398 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 102. % Outside air 100. Calculated air volume (cfm) outside 406. Calculated air volume (cfm) return 0. Combined air volume (cfm) 406. ACH outside 3.0. ACH merv filter return air 0.0. ACH total 3.0. ACH Copy paste check (uses total or outside) 3. Room 101. % Outside air 70. Calculated air volume (cfm) outside 238. Calculated air volume (cfm) return 100. Combined air volume (cfm) 338. ACH outside 1.8. ACH merv filter return air 0.7. ACH total 2.5. ACH Copy paste check (uses total or outside) 1.8. Room 202. % Outside air 100. Calculated air volume (cfm) outside 160. Calculated air volume (cfm) return 0. Combined air volume (cfm) 160. ACH outside 1.2. ACH merv filter return air 0.0. ACH total 1.2. ACH Copy paste check (uses total or outside) 1.2. Room 204. % Outside air 100. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 0. Combined air volume (cfm) 300. ACH outside 2.2. ACH merv filter return air 0.0. ACH total 2.2. ACH Copy paste check (uses total or outside) 2.2. Room 206B. % Outside air 88. Calculated air volume (cfm) outside 301. Calculated air volume (cfm) return 43. Combined air volume (cfm) 344. ACH outside 2.3. ACH merv filter return air 0.3. ACH total 2.6. ACH Copy paste check (uses total or outside) 2.3. Room 114. % Outside air 100. Calculated air volume (cfm) outside 850. Calculated air volume (cfm) return 0. Combined air volume (cfm) 850. ACH outside 6.1. ACH merv filter return air 0.0. ACH total 6.1. ACH Copy paste check (uses total or outside) 6.1. |