0. Space TypeBOS-School
1. Establishment NameBates Phineas Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH1.2
13. Max ACH3.3
14. Avg ACH2.4
15. eACH0
16. Filter MERV
17. Percent Outside Air84.5
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft839.8
22. cuft8398
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 102. % Outside air 100. Calculated air volume (cfm) outside 406. Calculated air volume (cfm) return 0. Combined air volume (cfm) 406. ACH outside 3.0. ACH merv filter return air 0.0. ACH total 3.0. ACH Copy paste check (uses total or outside) 3.

Room 101. % Outside air 70. Calculated air volume (cfm) outside 238. Calculated air volume (cfm) return 100. Combined air volume (cfm) 338. ACH outside 1.8. ACH merv filter return air 0.7. ACH total 2.5. ACH Copy paste check (uses total or outside) 1.8.

Room 202. % Outside air 100. Calculated air volume (cfm) outside 160. Calculated air volume (cfm) return 0. Combined air volume (cfm) 160. ACH outside 1.2. ACH merv filter return air 0.0. ACH total 1.2. ACH Copy paste check (uses total or outside) 1.2.

Room 204. % Outside air 100. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 0. Combined air volume (cfm) 300. ACH outside 2.2. ACH merv filter return air 0.0. ACH total 2.2. ACH Copy paste check (uses total or outside) 2.2.

Room 206B. % Outside air 88. Calculated air volume (cfm) outside 301. Calculated air volume (cfm) return 43. Combined air volume (cfm) 344. ACH outside 2.3. ACH merv filter return air 0.3. ACH total 2.6. ACH Copy paste check (uses total or outside) 2.3.

Room 114. % Outside air 100. Calculated air volume (cfm) outside 850. Calculated air volume (cfm) return 0. Combined air volume (cfm) 850. ACH outside 6.1. ACH merv filter return air 0.0. ACH total 6.1. ACH Copy paste check (uses total or outside) 6.1.