Building Data Report

0. Space TypeBOS-School
1. Establishment NameBeethoven Ludwig van Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH3.5
13. Max ACH6.1
14. Avg ACH4.8
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1248
22. cuft12480
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 114. % Outside air 100. Calculated air volume (cfm) outside 690. Calculated air volume (cfm) return 0. Combined air volume (cfm) 690. ACH outside 5.2. ACH merv filter return air 0.0. ACH total 5.2. ACH Copy paste check (uses total or outside) 5.2.

Room 113. % Outside air 100. Calculated air volume (cfm) outside 617. Calculated air volume (cfm) return 0. Combined air volume (cfm) 617. ACH outside 5.0. ACH merv filter return air 0.0. ACH total 5.0. ACH Copy paste check (uses total or outside) 5.

Room 208. % Outside air 100. Calculated air volume (cfm) outside 539. Calculated air volume (cfm) return 0. Combined air volume (cfm) 539. ACH outside 4.4. ACH merv filter return air 0.0. ACH total 4.4. ACH Copy paste check (uses total or outside) 4.3.

Room 206. % Outside air 100. Calculated air volume (cfm) outside 600. Calculated air volume (cfm) return 0. Combined air volume (cfm) 600. ACH outside 4.6. ACH merv filter return air 0.0. ACH total 4.6. ACH Copy paste check (uses total or outside) 4.6.

Room 201. % Outside air 100. Calculated air volume (cfm) outside 575. Calculated air volume (cfm) return 0. Combined air volume (cfm) 575. ACH outside 3.5. ACH merv filter return air 0.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 3.5.

Room 110. % Outside air 74. Calculated air volume (cfm) outside 303. Calculated air volume (cfm) return 107. Combined air volume (cfm) 410. ACH outside 1.5. ACH merv filter return air 0.5. ACH total 2.0. ACH Copy paste check (uses total or outside) 1.5.