About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Beethoven Ludwig van Elem |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 3.5 |
13. Max ACH | 6.1 |
14. Avg ACH | 4.8 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 1248 |
22. cuft | 12480 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 114. % Outside air 100. Calculated air volume (cfm) outside 690. Calculated air volume (cfm) return 0. Combined air volume (cfm) 690. ACH outside 5.2. ACH merv filter return air 0.0. ACH total 5.2. ACH Copy paste check (uses total or outside) 5.2. Room 113. % Outside air 100. Calculated air volume (cfm) outside 617. Calculated air volume (cfm) return 0. Combined air volume (cfm) 617. ACH outside 5.0. ACH merv filter return air 0.0. ACH total 5.0. ACH Copy paste check (uses total or outside) 5. Room 208. % Outside air 100. Calculated air volume (cfm) outside 539. Calculated air volume (cfm) return 0. Combined air volume (cfm) 539. ACH outside 4.4. ACH merv filter return air 0.0. ACH total 4.4. ACH Copy paste check (uses total or outside) 4.3. Room 206. % Outside air 100. Calculated air volume (cfm) outside 600. Calculated air volume (cfm) return 0. Combined air volume (cfm) 600. ACH outside 4.6. ACH merv filter return air 0.0. ACH total 4.6. ACH Copy paste check (uses total or outside) 4.6. Room 201. % Outside air 100. Calculated air volume (cfm) outside 575. Calculated air volume (cfm) return 0. Combined air volume (cfm) 575. ACH outside 3.5. ACH merv filter return air 0.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 3.5. Room 110. % Outside air 74. Calculated air volume (cfm) outside 303. Calculated air volume (cfm) return 107. Combined air volume (cfm) 410. ACH outside 1.5. ACH merv filter return air 0.5. ACH total 2.0. ACH Copy paste check (uses total or outside) 1.5. |