About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameBoston Green Academy
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH1.3
13. Max ACH4.4
14. Avg ACH2.6
15. eACH0
16. Filter MERV
17. Percent Outside Air73
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms4
21. sqft856.3
22. cuft8563
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 115. % Outside air 100. Calculated air volume (cfm) outside 195. Calculated air volume (cfm) return 0. Combined air volume (cfm) 195. ACH outside 1.3. ACH merv filter return air 0.0. ACH total 1.3. ACH Copy paste check (uses total or outside) 1.3.

Room 215. % Outside air 60. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 265. Combined air volume (cfm) 660. ACH outside 2.6. ACH merv filter return air 1.8. ACH total 4.4. ACH Copy paste check (uses total or outside) 2.6.

Room 213. % Outside air 60. Calculated air volume (cfm) outside 240. Calculated air volume (cfm) return 160. Combined air volume (cfm) 400. ACH outside 1.6. ACH merv filter return air 1.1. ACH total 2.7. ACH Copy paste check (uses total or outside) 1.6.

Room 204. % Outside air 51. Calculated air volume (cfm) outside 205. Calculated air volume (cfm) return 155. Combined air volume (cfm) 360. ACH outside 1.4. ACH merv filter return air 1.1. ACH total 2.5. ACH Copy paste check (uses total or outside) 1.4.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Boston Green Academy.txt. Feel free to add Survey data. Boston Green Academy

CAB v 0.11 R -1

01:48:44 Start Time
01:48:44 End Time
0 Seconds

5.026003 cab pid: 480104 httpd pid: error pid: