0. Space Type | BOS-School |
1. Establishment Name | Channing William E Elem |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 0.7 |
13. Max ACH | 3.5 |
14. Avg ACH | 2.3 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 44.5 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 940.8 |
22. cuft | 9408 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 101. % Outside air 100. Calculated air volume (cfm) outside 91. Calculated air volume (cfm) return 0. Combined air volume (cfm) 91. ACH outside 0.7. ACH merv filter return air 0.0. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7. Room 110. % Outside air 100. Calculated air volume (cfm) outside 600. Calculated air volume (cfm) return 0. Combined air volume (cfm) 600. ACH outside 2.6. ACH merv filter return air 0.0. ACH total 2.6. ACH Copy paste check (uses total or outside) 2.6. Room 215. % Outside air 0. Calculated air volume (cfm) outside -26. Calculated air volume (cfm) return 534. Combined air volume (cfm) 508. ACH outside -0.2. ACH merv filter return air 3.5. ACH total 3.3. ACH Copy paste check (uses total or outside) 0. Room 204. % Outside air 0. Calculated air volume (cfm) outside -56. Calculated air volume (cfm) return 475. Combined air volume (cfm) 419. ACH outside -0.4. ACH merv filter return air 3.3. ACH total 2.9. ACH Copy paste check (uses total or outside) 0. Room 201. % Outside air 0. Calculated air volume (cfm) outside -77. Calculated air volume (cfm) return 590. Combined air volume (cfm) 513. ACH outside -0.5. ACH merv filter return air 4.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 0. Room 103. % Outside air 89. Calculated air volume (cfm) outside 468. Calculated air volume (cfm) return 59. Combined air volume (cfm) 527. ACH outside 3.0. ACH merv filter return air 0.4. ACH total 3.4. ACH Copy paste check (uses total or outside) 3. |