Building Data Report

0. Space TypeBOS-School
1. Establishment NameChanning William E Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH0.7
13. Max ACH3.5
14. Avg ACH2.3
15. eACH0
16. Filter MERV
17. Percent Outside Air44.5
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft940.8
22. cuft9408
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 101. % Outside air 100. Calculated air volume (cfm) outside 91. Calculated air volume (cfm) return 0. Combined air volume (cfm) 91. ACH outside 0.7. ACH merv filter return air 0.0. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7.

Room 110. % Outside air 100. Calculated air volume (cfm) outside 600. Calculated air volume (cfm) return 0. Combined air volume (cfm) 600. ACH outside 2.6. ACH merv filter return air 0.0. ACH total 2.6. ACH Copy paste check (uses total or outside) 2.6.

Room 215. % Outside air 0. Calculated air volume (cfm) outside -26. Calculated air volume (cfm) return 534. Combined air volume (cfm) 508. ACH outside -0.2. ACH merv filter return air 3.5. ACH total 3.3. ACH Copy paste check (uses total or outside) 0.

Room 204. % Outside air 0. Calculated air volume (cfm) outside -56. Calculated air volume (cfm) return 475. Combined air volume (cfm) 419. ACH outside -0.4. ACH merv filter return air 3.3. ACH total 2.9. ACH Copy paste check (uses total or outside) 0.

Room 201. % Outside air 0. Calculated air volume (cfm) outside -77. Calculated air volume (cfm) return 590. Combined air volume (cfm) 513. ACH outside -0.5. ACH merv filter return air 4.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 0.

Room 103. % Outside air 89. Calculated air volume (cfm) outside 468. Calculated air volume (cfm) return 59. Combined air volume (cfm) 527. ACH outside 3.0. ACH merv filter return air 0.4. ACH total 3.4. ACH Copy paste check (uses total or outside) 3.