0. Space Type | BOS-School |
1. Establishment Name | Curley K 8 JM Curley |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 4.8 |
13. Max ACH | 9.5 |
14. Avg ACH | 6.6 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 63.3 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 777.2 |
22. cuft | 7772 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 117. % Outside air 65. Calculated air volume (cfm) outside 411. Calculated air volume (cfm) return 224. Combined air volume (cfm) 635. ACH outside 3.1. ACH merv filter return air 1.7. ACH total 4.8. ACH Copy paste check (uses total or outside) 3.1. Room 111. % Outside air 64. Calculated air volume (cfm) outside 473. Calculated air volume (cfm) return 262. Combined air volume (cfm) 735. ACH outside 3.7. ACH merv filter return air 2.1. ACH total 5.8. ACH Copy paste check (uses total or outside) 3.7. Room 212. % Outside air 84. Calculated air volume (cfm) outside 589. Calculated air volume (cfm) return 108. Combined air volume (cfm) 697. ACH outside 4.7. ACH merv filter return air 0.9. ACH total 5.5. ACH Copy paste check (uses total or outside) 4.7. Room 201. % Outside air 65. Calculated air volume (cfm) outside 608. Calculated air volume (cfm) return 330. Combined air volume (cfm) 938. ACH outside 6.1. ACH merv filter return air 3.3. ACH total 9.5. ACH Copy paste check (uses total or outside) 6.1. Room 209. % Outside air 81. Calculated air volume (cfm) outside 709. Calculated air volume (cfm) return 166. Combined air volume (cfm) 875. ACH outside 5.5. ACH merv filter return air 1.3. ACH total 6.7. ACH Copy paste check (uses total or outside) 5.5. Room 110. % Outside air 88. Calculated air volume (cfm) outside 567. Calculated air volume (cfm) return 81. Combined air volume (cfm) 648. ACH outside 4.4. ACH merv filter return air 0.6. ACH total 5.0. ACH Copy paste check (uses total or outside) 4.4. |