0. Space TypeBOS-School
1. Establishment NameCurley K 8 JM Curley
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH4.8
13. Max ACH9.5
14. Avg ACH6.6
15. eACH0
16. Filter MERV
17. Percent Outside Air63.3
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft777.2
22. cuft7772
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 117. % Outside air 65. Calculated air volume (cfm) outside 411. Calculated air volume (cfm) return 224. Combined air volume (cfm) 635. ACH outside 3.1. ACH merv filter return air 1.7. ACH total 4.8. ACH Copy paste check (uses total or outside) 3.1.

Room 111. % Outside air 64. Calculated air volume (cfm) outside 473. Calculated air volume (cfm) return 262. Combined air volume (cfm) 735. ACH outside 3.7. ACH merv filter return air 2.1. ACH total 5.8. ACH Copy paste check (uses total or outside) 3.7.

Room 212. % Outside air 84. Calculated air volume (cfm) outside 589. Calculated air volume (cfm) return 108. Combined air volume (cfm) 697. ACH outside 4.7. ACH merv filter return air 0.9. ACH total 5.5. ACH Copy paste check (uses total or outside) 4.7.

Room 201. % Outside air 65. Calculated air volume (cfm) outside 608. Calculated air volume (cfm) return 330. Combined air volume (cfm) 938. ACH outside 6.1. ACH merv filter return air 3.3. ACH total 9.5. ACH Copy paste check (uses total or outside) 6.1.

Room 209. % Outside air 81. Calculated air volume (cfm) outside 709. Calculated air volume (cfm) return 166. Combined air volume (cfm) 875. ACH outside 5.5. ACH merv filter return air 1.3. ACH total 6.7. ACH Copy paste check (uses total or outside) 5.5.

Room 110. % Outside air 88. Calculated air volume (cfm) outside 567. Calculated air volume (cfm) return 81. Combined air volume (cfm) 648. ACH outside 4.4. ACH merv filter return air 0.6. ACH total 5.0. ACH Copy paste check (uses total or outside) 4.4.