About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Dever Paul A Elem |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 3.7 |
13. Max ACH | 5 |
14. Avg ACH | 4.2 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 97.8 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 792 |
22. cuft | 7920 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 102. % Outside air 100. Calculated air volume (cfm) outside 696. Calculated air volume (cfm) return 0. Combined air volume (cfm) 696. ACH outside 4.3. ACH merv filter return air 0.0. ACH total 4.3. ACH Copy paste check (uses total or outside) 4.3. Room 113. % Outside air 100. Calculated air volume (cfm) outside 759. Calculated air volume (cfm) return 0. Combined air volume (cfm) 759. ACH outside 4.9. ACH merv filter return air 0.0. ACH total 4.9. ACH Copy paste check (uses total or outside) 3.9. Room 217. % Outside air 100. Calculated air volume (cfm) outside 627. Calculated air volume (cfm) return 0. Combined air volume (cfm) 627. ACH outside 3.8. ACH merv filter return air 0.0. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.8. Room 208. % Outside air 100. Calculated air volume (cfm) outside 600. Calculated air volume (cfm) return 0. Combined air volume (cfm) 600. ACH outside 3.7. ACH merv filter return air 0.0. ACH total 3.7. ACH Copy paste check (uses total or outside) 3.7. Room 202. % Outside air 100. Calculated air volume (cfm) outside 642. Calculated air volume (cfm) return 0. Combined air volume (cfm) 642. ACH outside 3.9. ACH merv filter return air 0.0. ACH total 3.9. ACH Copy paste check (uses total or outside) 3.9. Room 108. % Outside air 60. Calculated air volume (cfm) outside 455. Calculated air volume (cfm) return 300. Combined air volume (cfm) 755. ACH outside 3.4. ACH merv filter return air 2.3. ACH total 5.7. ACH Copy paste check (uses total or outside) 3.4. |