0. Space TypeBOS-School
1. Establishment NameIrving Washington Middle
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH2
13. Max ACH3.7
14. Avg ACH2.8
15. eACH0
16. Filter MERV
17. Percent Outside Air27.2
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms5
21. sqft725.4
22. cuft7254
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 208. % Outside air 27. Calculated air volume (cfm) outside 136. Calculated air volume (cfm) return 373. Combined air volume (cfm) 509. ACH outside 1.0. ACH merv filter return air 2.7. ACH total 3.7. ACH Copy paste check (uses total or outside) 0.9.

Room 204. % Outside air 30. Calculated air volume (cfm) outside 85. Calculated air volume (cfm) return 197. Combined air volume (cfm) 282. ACH outside 0.6. ACH merv filter return air 1.4. ACH total 2.0. ACH Copy paste check (uses total or outside) 0.6.

Room 303. % Outside air 30. Calculated air volume (cfm) outside 83. Calculated air volume (cfm) return 197. Combined air volume (cfm) 280. ACH outside 0.6. ACH merv filter return air 1.4. ACH total 2.0. ACH Copy paste check (uses total or outside) 0.6.

Room 310. % Outside air 33. Calculated air volume (cfm) outside 113. Calculated air volume (cfm) return 230. Combined air volume (cfm) 343. ACH outside 1.1. ACH merv filter return air 2.2. ACH total 3.3. ACH Copy paste check (uses total or outside) 1.