0. Space Type | BOS-School |
1. Establishment Name | Irving Washington Middle |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 2 |
13. Max ACH | 3.7 |
14. Avg ACH | 2.8 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 27.2 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 5 |
21. sqft | 725.4 |
22. cuft | 7254 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 208. % Outside air 27. Calculated air volume (cfm) outside 136. Calculated air volume (cfm) return 373. Combined air volume (cfm) 509. ACH outside 1.0. ACH merv filter return air 2.7. ACH total 3.7. ACH Copy paste check (uses total or outside) 0.9. Room 204. % Outside air 30. Calculated air volume (cfm) outside 85. Calculated air volume (cfm) return 197. Combined air volume (cfm) 282. ACH outside 0.6. ACH merv filter return air 1.4. ACH total 2.0. ACH Copy paste check (uses total or outside) 0.6. Room 303. % Outside air 30. Calculated air volume (cfm) outside 83. Calculated air volume (cfm) return 197. Combined air volume (cfm) 280. ACH outside 0.6. ACH merv filter return air 1.4. ACH total 2.0. ACH Copy paste check (uses total or outside) 0.6. Room 310. % Outside air 33. Calculated air volume (cfm) outside 113. Calculated air volume (cfm) return 230. Combined air volume (cfm) 343. ACH outside 1.1. ACH merv filter return air 2.2. ACH total 3.3. ACH Copy paste check (uses total or outside) 1. Room 101. % Outside air 0. Calculated air volume (cfm) outside 0. Calculated air volume (cfm) return 450. Combined air volume (cfm) 450. ACH outside 0.0. ACH merv filter return air 3.7. ACH total 3.7. ACH Copy paste check (uses total or outside) 0. |