About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Kilmer Joyce Russeell Rd 4 8 |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 2.8 |
13. Max ACH | 3.4 |
14. Avg ACH | 3.1 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 55.5 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 790.4 |
22. cuft | 7904 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 104. % Outside air 69. Calculated air volume (cfm) outside 335. Calculated air volume (cfm) return 148. Combined air volume (cfm) 483. ACH outside 2.2. ACH merv filter return air 1.0. ACH total 3.2. ACH Copy paste check (uses total or outside) 2.2. Room 101. % Outside air 71. Calculated air volume (cfm) outside 292. Calculated air volume (cfm) return 119. Combined air volume (cfm) 411. ACH outside 2.0. ACH merv filter return air 0.8. ACH total 2.8. ACH Copy paste check (uses total or outside) 2. Room 203. % Outside air 52. Calculated air volume (cfm) outside 246. Calculated air volume (cfm) return 226. Combined air volume (cfm) 472. ACH outside 1.8. ACH merv filter return air 1.6. ACH total 3.4. ACH Copy paste check (uses total or outside) 1.8. Room 204. % Outside air 51. Calculated air volume (cfm) outside 232. Calculated air volume (cfm) return 226. Combined air volume (cfm) 458. ACH outside 1.7. ACH merv filter return air 1.6. ACH total 3.3. ACH Copy paste check (uses total or outside) 1.7. Room 205. % Outside air 36. Calculated air volume (cfm) outside 142. Calculated air volume (cfm) return 250. Combined air volume (cfm) 392. ACH outside 1.0. ACH merv filter return air 1.8. ACH total 2.8. ACH Copy paste check (uses total or outside) 1. Room 120. % Outside air 65. Calculated air volume (cfm) outside 130. Calculated air volume (cfm) return 70. Combined air volume (cfm) 200. ACH outside 1.0. ACH merv filter return air 0.5. ACH total 1.5. ACH Copy paste check (uses total or outside) 1. |