About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameMcCormack John W Middle
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH3.2
13. Max ACH4.4
14. Avg ACH3.9
15. eACH0
16. Filter MERV
17. Percent Outside Air81
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft825
22. cuft8250
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 134. % Outside air 81. Calculated air volume (cfm) outside 310. Calculated air volume (cfm) return 75. Combined air volume (cfm) 385. ACH outside 2.6. ACH merv filter return air 0.6. ACH total 3.2. ACH Copy paste check (uses total or outside) 2.6.

Room 135. % Outside air 87. Calculated air volume (cfm) outside 501. Calculated air volume (cfm) return 74. Combined air volume (cfm) 575. ACH outside 3.3. ACH merv filter return air 0.5. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.3.

Room 243. % Outside air 79. Calculated air volume (cfm) outside 453. Calculated air volume (cfm) return 122. Combined air volume (cfm) 575. ACH outside 3.5. ACH merv filter return air 0.9. ACH total 4.4. ACH Copy paste check (uses total or outside) 3.5.

Room 238. % Outside air 74. Calculated air volume (cfm) outside 453. Calculated air volume (cfm) return 162. Combined air volume (cfm) 615. ACH outside 2.7. ACH merv filter return air 1.0. ACH total 3.7. ACH Copy paste check (uses total or outside) 2.7.

Room 229. % Outside air 85. Calculated air volume (cfm) outside 564. Calculated air volume (cfm) return 102. Combined air volume (cfm) 666. ACH outside 3.4. ACH merv filter return air 0.6. ACH total 4.0. ACH Copy paste check (uses total or outside) 3.4.

Room 103. % Outside air 74. Calculated air volume (cfm) outside 549. Calculated air volume (cfm) return 191. Combined air volume (cfm) 740. ACH outside 4.0. ACH merv filter return air 1.4. ACH total 5.4. ACH Copy paste check (uses total or outside) 4.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/McCormack John W Middle.txt. Feel free to add Survey data. McCormack John W Middle

CAB v 0.11 R -1

16:43:22 Start Time
16:43:23 End Time
1 Seconds

5.026003 cab pid: 2596667 httpd pid: error pid: