About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | McCormack John W Middle |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 3.2 |
13. Max ACH | 4.4 |
14. Avg ACH | 3.9 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 81 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 825 |
22. cuft | 8250 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 134. % Outside air 81. Calculated air volume (cfm) outside 310. Calculated air volume (cfm) return 75. Combined air volume (cfm) 385. ACH outside 2.6. ACH merv filter return air 0.6. ACH total 3.2. ACH Copy paste check (uses total or outside) 2.6. Room 135. % Outside air 87. Calculated air volume (cfm) outside 501. Calculated air volume (cfm) return 74. Combined air volume (cfm) 575. ACH outside 3.3. ACH merv filter return air 0.5. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.3. Room 243. % Outside air 79. Calculated air volume (cfm) outside 453. Calculated air volume (cfm) return 122. Combined air volume (cfm) 575. ACH outside 3.5. ACH merv filter return air 0.9. ACH total 4.4. ACH Copy paste check (uses total or outside) 3.5. Room 238. % Outside air 74. Calculated air volume (cfm) outside 453. Calculated air volume (cfm) return 162. Combined air volume (cfm) 615. ACH outside 2.7. ACH merv filter return air 1.0. ACH total 3.7. ACH Copy paste check (uses total or outside) 2.7. Room 229. % Outside air 85. Calculated air volume (cfm) outside 564. Calculated air volume (cfm) return 102. Combined air volume (cfm) 666. ACH outside 3.4. ACH merv filter return air 0.6. ACH total 4.0. ACH Copy paste check (uses total or outside) 3.4. Room 103. % Outside air 74. Calculated air volume (cfm) outside 549. Calculated air volume (cfm) return 191. Combined air volume (cfm) 740. ACH outside 4.0. ACH merv filter return air 1.4. ACH total 5.4. ACH Copy paste check (uses total or outside) 4. |