About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameMcKinley South End Acad
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH5.1
13. Max ACH6.7
14. Avg ACH5.9
15. eACH0
16. Filter MERV
17. Percent Outside Air77.2
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms8
21. sqft1142
22. cuft11420
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 211. % Outside air 61. Calculated air volume (cfm) outside 416. Calculated air volume (cfm) return 261. Combined air volume (cfm) 677. ACH outside 3.3. ACH merv filter return air 2.0. ACH total 5.3. ACH Copy paste check (uses total or outside) 3.3.

Room 201. % Outside air 93. Calculated air volume (cfm) outside 609. Calculated air volume (cfm) return 43. Combined air volume (cfm) 652. ACH outside 4.8. ACH merv filter return air 0.3. ACH total 5.1. ACH Copy paste check (uses total or outside) 4.8.

Room 103. % Outside air 77. Calculated air volume (cfm) outside 605. Calculated air volume (cfm) return 164. Combined air volume (cfm) 789. ACH outside 4.7. ACH merv filter return air 1.3. ACH total 6.2. ACH Copy paste check (uses total or outside) 4.7.

Room 108. % Outside air 77. Calculated air volume (cfm) outside 540. Calculated air volume (cfm) return 163. Combined air volume (cfm) 703. ACH outside 4.2. ACH merv filter return air 1.3. ACH total 5.5. ACH Copy paste check (uses total or outside) 4.2.

Room 113. % Outside air 80. Calculated air volume (cfm) outside 561. Calculated air volume (cfm) return 137. Combined air volume (cfm) 698. ACH outside 4.4. ACH merv filter return air 1.1. ACH total 5.5. ACH Copy paste check (uses total or outside) 4.4.

Room 114. % Outside air 94. Calculated air volume (cfm) outside 611. Calculated air volume (cfm) return 36. Combined air volume (cfm) 847. ACH outside 4.8. ACH merv filter return air 0.3. ACH total 6.6. ACH Copy paste check (uses total or outside) 4.8.

Room 109. % Outside air 82. Calculated air volume (cfm) outside 687. Calculated air volume (cfm) return 155. Combined air volume (cfm) 842. ACH outside 5.4. ACH merv filter return air 1.2. ACH total 6.6. ACH Copy paste check (uses total or outside) 5.4.

Room 107A. % Outside air 32. Calculated air volume (cfm) outside 210. Calculated air volume (cfm) return 447. Combined air volume (cfm) 657. ACH outside 1.1. ACH merv filter return air 2.3. ACH total 3.5. ACH Copy paste check (uses total or outside) 1.1.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/McKinley South End Acad.txt. Feel free to add Survey data. McKinley South End Acad

CAB v 0.11 R -1