0. Space Type | BOS-School |
1. Establishment Name | Sumner Charles Elem |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 2.8 |
13. Max ACH | 8.8 |
14. Avg ACH | 4.7 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 83 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 768 |
22. cuft | 7680 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 109. % Outside air 83. Calculated air volume (cfm) outside 532. Calculated air volume (cfm) return 105. Combined air volume (cfm) 637. ACH outside 3.9. ACH merv filter return air 0.8. ACH total 4.7. ACH Copy paste check (uses total or outside) 3.9. Room 102. % Outside air 88. Calculated air volume (cfm) outside 455. Calculated air volume (cfm) return 63. Combined air volume (cfm) 518. ACH outside 3.3. ACH merv filter return air 0.5. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.3. Room 201. % Outside air 100. Calculated air volume (cfm) outside 387. Calculated air volume (cfm) return 0. Combined air volume (cfm) 387. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.8. Room 202. % Outside air 100. Calculated air volume (cfm) outside 694. Calculated air volume (cfm) return 0. Combined air volume (cfm) 694. ACH outside 4.9. ACH merv filter return air 0.0. ACH total 4.9. ACH Copy paste check (uses total or outside) 4.9. Room 209. % Outside air 42. Calculated air volume (cfm) outside 183. Calculated air volume (cfm) return 254. Combined air volume (cfm) 437. ACH outside 1.4. ACH merv filter return air 1.9. ACH total 3.3. ACH Copy paste check (uses total or outside) 1.2. Room 103. % Outside air 69. Calculated air volume (cfm) outside 400. Calculated air volume (cfm) return 180. Combined air volume (cfm) 580. ACH outside 3.1. ACH merv filter return air 1.4. ACH total 4.5. ACH Copy paste check (uses total or outside) 3.1. |