About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameSumner Charles Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH2.8
13. Max ACH8.8
14. Avg ACH4.7
15. eACH0
16. Filter MERV
17. Percent Outside Air83
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft768
22. cuft7680
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 109. % Outside air 83. Calculated air volume (cfm) outside 532. Calculated air volume (cfm) return 105. Combined air volume (cfm) 637. ACH outside 3.9. ACH merv filter return air 0.8. ACH total 4.7. ACH Copy paste check (uses total or outside) 3.9.

Room 102. % Outside air 88. Calculated air volume (cfm) outside 455. Calculated air volume (cfm) return 63. Combined air volume (cfm) 518. ACH outside 3.3. ACH merv filter return air 0.5. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.3.

Room 201. % Outside air 100. Calculated air volume (cfm) outside 387. Calculated air volume (cfm) return 0. Combined air volume (cfm) 387. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.8.

Room 202. % Outside air 100. Calculated air volume (cfm) outside 694. Calculated air volume (cfm) return 0. Combined air volume (cfm) 694. ACH outside 4.9. ACH merv filter return air 0.0. ACH total 4.9. ACH Copy paste check (uses total or outside) 4.9.

Room 209. % Outside air 42. Calculated air volume (cfm) outside 183. Calculated air volume (cfm) return 254. Combined air volume (cfm) 437. ACH outside 1.4. ACH merv filter return air 1.9. ACH total 3.3. ACH Copy paste check (uses total or outside) 1.2.

Room 103. % Outside air 69. Calculated air volume (cfm) outside 400. Calculated air volume (cfm) return 180. Combined air volume (cfm) 580. ACH outside 3.1. ACH merv filter return air 1.4. ACH total 4.5. ACH Copy paste check (uses total or outside) 3.1.