0. Space Type | BOS-School |
1. Establishment Name | Tobin Maurice J K 8 |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 2.9 |
13. Max ACH | 4.6 |
14. Avg ACH | 4.1 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 61.1 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 900 |
22. cuft | 9000 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 103. % Outside air 64. Calculated air volume (cfm) outside 390. Calculated air volume (cfm) return 220. Combined air volume (cfm) 610. ACH outside 2.7. ACH merv filter return air 1.5. ACH total 4.2. ACH Copy paste check (uses total or outside) 2.7. Room 106. % Outside air 64. Calculated air volume (cfm) outside 375. Calculated air volume (cfm) return 215. Combined air volume (cfm) 590. ACH outside 2.6. ACH merv filter return air 1.5. ACH total 4.1. ACH Copy paste check (uses total or outside) 2.6. Room 201A. % Outside air 61. Calculated air volume (cfm) outside 385. Calculated air volume (cfm) return 250. Combined air volume (cfm) 635. ACH outside 2.7. ACH merv filter return air 1.7. ACH total 4.4. ACH Copy paste check (uses total or outside) 2.7. Room 3. % Outside air 62. Calculated air volume (cfm) outside 415. Calculated air volume (cfm) return 250. Combined air volume (cfm) 665. ACH outside 2.9. ACH merv filter return air 1.7. ACH total 4.6. ACH Copy paste check (uses total or outside) 2.9. Room 4. % Outside air 68. Calculated air volume (cfm) outside 440. Calculated air volume (cfm) return 210. Combined air volume (cfm) 650. ACH outside 3.0. ACH merv filter return air 1.4. ACH total 4.5. ACH Copy paste check (uses total or outside) 3. Room C147. % Outside air 63. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 170. Combined air volume (cfm) 470. ACH outside 2.0. ACH merv filter return air 1.1. ACH total 3.1. ACH Copy paste check (uses total or outside) 2. |