0. Space TypeBOS-School
1. Establishment NameTrotter William Monroe K 8
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH1.6
13. Max ACH3.1
14. Avg ACH2.2
15. eACH0
16. Filter MERV
17. Percent Outside Air62.1
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1134
22. cuft11340
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room C131. % Outside air 69. Calculated air volume (cfm) outside 165. Calculated air volume (cfm) return 75. Combined air volume (cfm) 240. ACH outside 1.1. ACH merv filter return air 0.5. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.1.

Room A202. % Outside air 53. Calculated air volume (cfm) outside 152. Calculated air volume (cfm) return 134. Combined air volume (cfm) 286. ACH outside 1.0. ACH merv filter return air 0.9. ACH total 1.9. ACH Copy paste check (uses total or outside) 1.

Room B233. % Outside air 58. Calculated air volume (cfm) outside 125. Calculated air volume (cfm) return 90. Combined air volume (cfm) 215. ACH outside 1.2. ACH merv filter return air 0.9. ACH total 2.0. ACH Copy paste check (uses total or outside) 1.2.

Room C242. % Outside air 54. Calculated air volume (cfm) outside 127. Calculated air volume (cfm) return 110. Combined air volume (cfm) 237. ACH outside 1.2. ACH merv filter return air 1.0. ACH total 2.3. ACH Copy paste check (uses total or outside) 1.2.

Room C247. % Outside air 51. Calculated air volume (cfm) outside 147. Calculated air volume (cfm) return 40. Combined air volume (cfm) 287. ACH outside 1.4. ACH merv filter return air 0.4. ACH total 2.7. ACH Copy paste check (uses total or outside) 1.4.

Room 113. % Outside air 72. Calculated air volume (cfm) outside 217. Calculated air volume (cfm) return 83. Combined air volume (cfm) 300. ACH outside 1.1. ACH merv filter return air 0.4. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.1.