About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameAlighieri Dante Mont
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH2.8
13. Max ACH6.5
14. Avg ACH5.1
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft861.6
22. cuft8616
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 102. ACH Copy paste check (uses total or outside) 6.5. Window opening length (inches) 38. Window opening height (inches) 4. Co2 ambient (ppm) 400. Co2 test start (ppm) 2170. Co2 test end (ppm) 1328. Run time (min:sec) 6:00. Window air velocity max 837. Window air velocity min 253. Window air velocity avg 549. Window outside air volume (cfm) avg 580. Window cu-ft 1.06. Window cfm max 884. Window cfm min 267. Window cfm avg 580. wACH max 5.6. wACH min 1.7. wACH avg 3.7. wACH Copy paste check (does not match calcultated) 6.5.

Room 101. ACH Copy paste check (uses total or outside) 2.8. Window opening length (inches) 45. Window opening height (inches) 4. Co2 ambient (ppm) 419. Co2 test start (ppm) 2340. Co2 test end (ppm) 1561. Run time (min:sec) 11:00. Window air velocity max 430. Window air velocity min 62. Window air velocity avg 252. Window outside air volume (cfm) avg 315. Window cu-ft 1.25. Window cfm max 538. Window cfm min 78. Window cfm avg 315. wACH max 3.7. wACH min 0.5. wACH avg 2.1. wACH Copy paste check (does not match calcultated) 2.8.

Room 202. ACH Copy paste check (uses total or outside) 3.6. Window opening length (inches) 45. Window opening height (inches) 4. Co2 ambient (ppm) 419. Co2 test start (ppm) 2239. Co2 test end (ppm) 1479. Run time (min:sec) 9:00. Window air velocity max 869. Window air velocity min 113. Window air velocity avg 364. Window outside air volume (cfm) avg 455. Window cu-ft 1.25. Window cfm max 1086. Window cfm min 141. Window cfm avg 455. wACH max 8.2. wACH min 1.1. wACH avg 3.4. wACH Copy paste check (does not match calcultated) 3.6.

Room 203. ACH Copy paste check (uses total or outside) 5.4. Window opening length (inches) 45. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2498. Co2 test end (ppm) 1520. Run time (min:sec) 7:00. Window air velocity max 662. Window air velocity min 99. Window air velocity avg 244. Window outside air volume (cfm) avg 305. Window cu-ft 1.25. Window cfm max 828. Window cfm min 124. Window cfm avg 305. wACH max 6.6. wACH min 1.0. wACH avg 2.5. wACH Copy paste check (does not match calcultated) 5.4.

Room 204. ACH Copy paste check (uses total or outside) 6.3. Window opening length (inches) 45. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2073. Co2 test end (ppm) 1118. Run time (min:sec) 8:00. Window air velocity max 957. Window air velocity min 147. Window air velocity avg 441. Window outside air volume (cfm) avg 551. Window cu-ft 1.25. Window cfm max 1196. Window cfm min 184. Window cfm avg 551. wACH max 9.0. wACH min 1.4. wACH avg 4.1. wACH Copy paste check (does not match calcultated) 6.3.

Room 101. ACH Copy paste check (uses total or outside) 4.2. Window opening length (inches) 56. Window opening height (inches) 4. Co2 ambient (ppm) 405. Co2 test start (ppm) 2210. Co2 test end (ppm) 1370. Run time (min:sec) 9:00. Window air velocity max 44. Window air velocity min 5. Window air velocity avg 20. Window outside air volume (cfm) avg 31. Window cu-ft 1.56. Window cfm max 68. Window cfm min 8. Window cfm avg 31. wACH max 0.5. wACH min 0.1. wACH avg 0.2. wACH Copy paste check (does not match calcultated) 4.2.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Alighieri Dante Mont.txt. Feel free to add Survey data. Alighieri Dante Mont

CAB v 0.11 R -1

18:29:21 Start Time
18:29:21 End Time
0 Seconds