About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Henderson K 12 Upper |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation |
12. Min ACH | 3.4 |
13. Max ACH | 6 |
14. Avg ACH | 4.8 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 4 |
21. sqft | 877.2 |
22. cuft | 8772 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 117. ACH Copy paste check (uses total or outside) 4.1. Window opening height (inches) 4. Co2 ambient (ppm) 465. Co2 test start (ppm) 2238. Co2 test end (ppm) 1306. Run time (min:sec) 11:00. Window cu-ft #VALUE!. Window cfm max #VALUE!. Window cfm min #VALUE!. Window cfm avg #VALUE!. wACH max #VALUE!. wACH min #VALUE!. wACH avg #VALUE!. wACH Copy paste check (does not match calcultated) 4.1. Room 219. ACH Copy paste check (uses total or outside) 6. Window opening height (inches) 4. Co2 ambient (ppm) 465. Co2 test start (ppm) 1889. Co2 test end (ppm) 990. Run time (min:sec) 10:00. Window cu-ft #VALUE!. Window cfm max #VALUE!. Window cfm min #VALUE!. Window cfm avg #VALUE!. wACH max #VALUE!. wACH min #VALUE!. wACH avg #VALUE!. wACH Copy paste check (does not match calcultated) 6. Room 226. ACH Copy paste check (uses total or outside) 5.7. Window opening height (inches) 4. Co2 ambient (ppm) 465. Co2 test start (ppm) 2224. Co2 test end (ppm) 975. Run time (min:sec) 13:00. Window cu-ft #VALUE!. Window cfm max #VALUE!. Window cfm min #VALUE!. Window cfm avg #VALUE!. wACH max #VALUE!. wACH min #VALUE!. wACH avg #VALUE!. wACH Copy paste check (does not match calcultated) 5.7. Room 110. ACH Copy paste check (uses total or outside) 5.3. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 532. Co2 test start (ppm) 2161. Co2 test end (ppm) 1341. Run time (min:sec) 8:00. Window air velocity max 681. Window air velocity min 355. Window air velocity avg 542. Window outside air volume (cfm) avg 708. Window cu-ft 1.31. Window cfm max 889. Window cfm min 463. Window cfm avg 708. wACH max 6.1. wACH min 3.2. wACH avg 4.8. wACH Copy paste check (does not match calcultated) 5.3. |