About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameHernandez Rafael K 8
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH3.5
13. Max ACH9.7
14. Avg ACH6.1
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1006
22. cuft10060
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 109. ACH Copy paste check (uses total or outside) 3.5. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 532. Co2 test start (ppm) 2087. Co2 test end (ppm) 1307. Run time (min:sec) 12:00. Window air velocity max 403. Window air velocity min 111. Window air velocity avg 277. Window outside air volume (cfm) avg 362. Window cu-ft 1.31. Window cfm max 526. Window cfm min 145. Window cfm avg 362. wACH max 3.6. wACH min 1.0. wACH avg 2.5. wACH Copy paste check (does not match calcultated) 3.5.

Room 111. ACH Copy paste check (uses total or outside) 7.1. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 420. Co2 test start (ppm) 2025. Co2 test end (ppm) 1125. Run time (min:sec) 7:00. Window air velocity max 444. Window air velocity min 197. Window air velocity avg 363. Window outside air volume (cfm) avg 474. Window cu-ft 1.31. Window cfm max 580. Window cfm min 257. Window cfm avg 474. wACH max 4.0. wACH min 1.8. wACH avg 3.2. wACH Copy paste check (does not match calcultated) 7.1.

Room 103. ACH Copy paste check (uses total or outside) 6.7. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 420. Co2 test start (ppm) 2086. Co2 test end (ppm) 1184. Run time (min:sec) 7:00. Window air velocity max 487. Window air velocity min 281. Window air velocity avg 325. Window outside air volume (cfm) avg 424. Window cu-ft 1.31. Window cfm max 636. Window cfm min 367. Window cfm avg 424. wACH max 4.3. wACH min 2.5. wACH avg 2.9. wACH Copy paste check (does not match calcultated) 6.7.

Room 211. ACH Copy paste check (uses total or outside) 4.4. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 390. Co2 test start (ppm) 2270. Co2 test end (ppm) 1440. Run time (min:sec) 8:00. Window air velocity max 474. Window air velocity min 1. Window air velocity avg 113. Window outside air volume (cfm) avg 148. Window cu-ft 1.31. Window cfm max 619. Window cfm min 1. Window cfm avg 148. wACH max 4.3. wACH min 0.0. wACH avg 1.0. wACH Copy paste check (does not match calcultated) 4.4.

Room 205. ACH Copy paste check (uses total or outside) 9.7. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 390. Co2 test start (ppm) 2200. Co2 test end (ppm) 1336. Run time (min:sec) 4:00. Window air velocity max 374. Window air velocity min 257. Window air velocity avg 338. Window outside air volume (cfm) avg 441. Window cu-ft 1.31. Window cfm max 488. Window cfm min 336. Window cfm avg 441. wACH max 3.4. wACH min 2.3. wACH avg 3.0. wACH Copy paste check (does not match calcultated) 9.7.

Room 112. ACH Copy paste check (uses total or outside) 8.1. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 439. Co2 test start (ppm) 2210. Co2 test end (ppm) 1340. Run time (min:sec) 5:00. Window air velocity max 731. Window air velocity min 92. Window air velocity avg 400. Window outside air volume (cfm) avg 411. Window cu-ft 1.03. Window cfm max 751. Window cfm min 95. Window cfm avg 411. wACH max 4.5. wACH min 0.6. wACH avg 2.5. wACH Copy paste check (does not match calcultated) 8.1.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Hernandez Rafael K 8.txt. Feel free to add Survey data. Hernandez Rafael K 8

CAB v 0.11 R -1

21:39:53 Start Time
21:39:53 End Time
0 Seconds

5.026003 cab pid: 414231 httpd pid: error pid: