About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameHigginson Lewis
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH5.8
13. Max ACH10.3
14. Avg ACH7
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1134.5
22. cuft11345
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 111. ACH Copy paste check (uses total or outside) 6.2. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 439. Co2 test start (ppm) 2192. Co2 test end (ppm) 1378. Run time (min:sec) 6:00. Window air velocity max 725. Window air velocity min 516. Window air velocity avg 579. Window outside air volume (cfm) avg 595. Window cu-ft 1.03. Window cfm max 745. Window cfm min 530. Window cfm avg 595. wACH max 5.4. wACH min 3.8. wACH avg 4.3. wACH Copy paste check (does not match calcultated) 6.2.

Room 108. ACH Copy paste check (uses total or outside) 5.8. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 439. Co2 test start (ppm) 2083. Co2 test end (ppm) 1260. Run time (min:sec) 7:00. Window air velocity max 782. Window air velocity min 166. Window air velocity avg 639. Window outside air volume (cfm) avg 657. Window cu-ft 1.03. Window cfm max 804. Window cfm min 171. Window cfm avg 657. wACH max 19.7. wACH min 4.2. wACH avg 16.1. wACH Copy paste check (does not match calcultated) 5.8.

Room 107. ACH Copy paste check (uses total or outside) 6.1. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 439. Co2 test start (ppm) 2193. Co2 test end (ppm) 1367. Run time (min:sec) 6:00. Window air velocity max 733. Window air velocity min 560. Window air velocity avg 625. Window outside air volume (cfm) avg 642. Window cu-ft 1.03. Window cfm max 753. Window cfm min 576. Window cfm avg 642. wACH max 5.4. wACH min 4.1. wACH avg 4.6. wACH Copy paste check (does not match calcultated) 6.1.

Room 207. ACH Copy paste check (uses total or outside) 5.8. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 439. Co2 test start (ppm) 2500. Co2 test end (ppm) 1463. Run time (min:sec) 7:00. Window air velocity max 767. Window air velocity min 71. Window air velocity avg 437. Window outside air volume (cfm) avg 449. Window cu-ft 1.03. Window cfm max 788. Window cfm min 73. Window cfm avg 449. wACH max 5.7. wACH min 0.5. wACH avg 3.2. wACH Copy paste check (does not match calcultated) 5.8.

Room 210B. ACH Copy paste check (uses total or outside) 10.3. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 439. Co2 test start (ppm) 2170. Co2 test end (ppm) 1285. Run time (min:sec) 4:00. Window air velocity max 499. Window air velocity min 191. Window air velocity avg 325. Window outside air volume (cfm) avg 334. Window cu-ft 1.03. Window cfm max 513. Window cfm min 196. Window cfm avg 334. wACH max 7.4. wACH min 2.8. wACH avg 4.8. wACH Copy paste check (does not match calcultated) 10.3.

Room 201. ACH Copy paste check (uses total or outside) 6. Window opening length (inches) 45. Window opening height (inches) 4. Co2 ambient (ppm) 401. Co2 test start (ppm) 2010. Co2 test end (ppm) 1197. Run time (min:sec) 7:00. Window air velocity max 758. Window air velocity min 469. Window air velocity avg 511. Window outside air volume (cfm) avg 639. Window cu-ft 1.25. Window cfm max 948. Window cfm min 586. Window cfm avg 639. wACH max 5.0. wACH min 3.1. wACH avg 3.4. wACH Copy paste check (does not match calcultated) 6.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Higginson Lewis.txt. Feel free to add Survey data. Higginson Lewis

CAB v 0.11 R -1

17:06:00 Start Time
17:06:00 End Time
0 Seconds

5.026003 cab pid: 1928364 httpd pid: error pid: