0. Space TypeBOS-School
1. Establishment NameHolmes Oliver Wendell
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH3.8
13. Max ACH23
14. Avg ACH10.7
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft926.8
22. cuft9268
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 1. ACH Copy paste check (uses total or outside) 23. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 401. Co2 test start (ppm) 2000. Co2 test end (ppm) 1139. Run time (min:sec) 2:00. Window air velocity max 732. Window air velocity min 696. Window air velocity avg 714. Window outside air volume (cfm) avg 932. Window cu-ft 1.31. Window cfm max 956. Window cfm min 909. Window cfm avg 932. wACH max 18.7. wACH min 17.8. wACH avg 18.2. wACH Copy paste check (does not match calcultated) 23.

Room 304. ACH Copy paste check (uses total or outside) 3.8. Window opening length (inches) 48. Window opening height (inches) 4. Co2 ambient (ppm) 443. Co2 test start (ppm) 1969. Co2 test end (ppm) 1207. Run time (min:sec) 11:00. Window air velocity max 485. Window air velocity min 63. Window air velocity avg 288. Window outside air volume (cfm) avg 384. Window cu-ft 1.33. Window cfm max 647. Window cfm min 84. Window cfm avg 384. wACH max 4.0. wACH min 0.5. wACH avg 2.4. wACH Copy paste check (does not match calcultated) 3.8.

Room 301. ACH Copy paste check (uses total or outside) 4.5. Window opening length (inches) 48. Window opening height (inches) 4. Co2 ambient (ppm) 443. Co2 test start (ppm) 2010. Co2 test end (ppm) 1247. Run time (min:sec) 9:00. Window air velocity max 464. Window air velocity min 46. Window air velocity avg 237. Window outside air volume (cfm) avg 316. Window cu-ft 1.33. Window cfm max 619. Window cfm min 61. Window cfm avg 316. wACH max 3.3. wACH min 0.3. wACH avg 1.7. wACH Copy paste check (does not match calcultated) 4.5.

Room 2. ACH Copy paste check (uses total or outside) 7.9. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 380. Co2 test start (ppm) 2135. Co2 test end (ppm) 1290. Run time (min:sec) 5:00. Window air velocity max 549. Window air velocity min 532. Window air velocity avg 540. Window outside air volume (cfm) avg 705. Window cu-ft 1.31. Window cfm max 717. Window cfm min 695. Window cfm avg 705. wACH max 3.8. wACH min 3.6. wACH avg 3.7. wACH Copy paste check (does not match calcultated) 7.9.

Room 4. ACH Copy paste check (uses total or outside) 19.5. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 380. Co2 test start (ppm) 2200. Co2 test end (ppm) 1330. Run time (min:sec) 2:00. Window air velocity max 732. Window air velocity min 696. Window air velocity avg 714. Window outside air volume (cfm) avg 932. Window cu-ft 1.31. Window cfm max 956. Window cfm min 909. Window cfm avg 932. wACH max 16.1. wACH min 15.3. wACH avg 15.7. wACH Copy paste check (does not match calcultated) 19.5.

Room 2. ACH Copy paste check (uses total or outside) 6.5. Window opening length (inches) 43. Window opening height (inches) 4. Co2 ambient (ppm) 400. Co2 test start (ppm) 2130. Co2 test end (ppm) 1306. Run time (min:sec) 6:00. Window air velocity max 770. Window air velocity min 307. Window air velocity avg 570. Window outside air volume (cfm) avg 681. Window cu-ft 1.19. Window cfm max 920. Window cfm min 367. Window cfm avg 681. wACH max 6.0. wACH min 2.4. wACH avg 4.4. wACH Copy paste check (does not match calcultated) 6.5.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Holmes Oliver Wendell.txt. Feel free to add Survey data. Holmes Oliver Wendell

CAB v 0.11 R -1

12:41:01 Start Time
12:41:01 End Time
0 Seconds

5.026003 cab pid: 949129 httpd pid: error pid: