About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameKing ML Jr K 8
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH1.8
13. Max ACH7.1
14. Avg ACH4.8
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft769.4
22. cuft7694
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 301. ACH Copy paste check (uses total or outside) 1.8. Window opening length (inches) 36. Window opening height (inches) 4. Co2 ambient (ppm) 415. Co2 test start (ppm) 2270. Co2 test end (ppm) 1600. Run time (min:sec) 15:00. Window air velocity max 493. Window air velocity min 20. Window air velocity avg 133. Window outside air volume (cfm) avg 133. Window cu-ft 1.00. Window cfm max 493. Window cfm min 20. Window cfm avg 133. wACH max 3.7. wACH min 0.1. wACH avg 1.0. wACH Copy paste check (does not match calcultated) 1.8.

Room 309. ACH Copy paste check (uses total or outside) 7.1. Window opening length (inches) 36. Window opening height (inches) 4. Co2 ambient (ppm) 422. Co2 test start (ppm) 2030. Co2 test end (ppm) 1213. Run time (min:sec) 6:00. Window air velocity max 640. Window air velocity min 46. Window air velocity avg 349. Window outside air volume (cfm) avg 349. Window cu-ft 1.00. Window cfm max 640. Window cfm min 46. Window cfm avg 349. wACH max 5.0. wACH min 0.4. wACH avg 2.7. wACH Copy paste check (does not match calcultated) 7.1.

Room 306. ACH Copy paste check (uses total or outside) 6.7. Window opening length (inches) 36. Window opening height (inches) 4. Co2 ambient (ppm) 422. Co2 test start (ppm) 2502. Co2 test end (ppm) 1612. Run time (min:sec) 5:00. Window air velocity max 555. Window air velocity min 218. Window air velocity avg 382. Window outside air volume (cfm) avg 382. Window cu-ft 1.00. Window cfm max 555. Window cfm min 218. Window cfm avg 382. wACH max 4.0. wACH min 1.6. wACH avg 2.8. wACH Copy paste check (does not match calcultated) 6.7.

Room 325. ACH Copy paste check (uses total or outside) 4.1. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 420. Co2 test start (ppm) 1873. Co2 test end (ppm) 1055. Run time (min:sec) 12:00. Window air velocity max 353. Window air velocity min 57. Window air velocity avg 184. Window outside air volume (cfm) avg 189. Window cu-ft 1.03. Window cfm max 363. Window cfm min 59. Window cfm avg 189. wACH max 3.0. wACH min 0.5. wACH avg 1.6. wACH Copy paste check (does not match calcultated) 4.1.

Room 321. ACH Copy paste check (uses total or outside) 3.4. Window opening length (inches) 37. Window opening height (inches) 4. Co2 ambient (ppm) 420. Co2 test start (ppm) 2094. Co2 test end (ppm) 1322. Run time (min:sec) 11:00. Window air velocity max 364. Window air velocity min 40. Window air velocity avg 187. Window outside air volume (cfm) avg 192. Window cu-ft 1.03. Window cfm max 374. Window cfm min 41. Window cfm avg 192. wACH max 3.0. wACH min 0.3. wACH avg 1.6. wACH Copy paste check (does not match calcultated) 3.4.

Room 105. ACH Copy paste check (uses total or outside) 7. Window opening length (inches) 60. Window opening height (inches) 4. Co2 ambient (ppm) 409. Co2 test start (ppm) 2097. Co2 test end (ppm) 1152. Run time (min:sec) 7:00. Window air velocity max 580. Window air velocity min 159. Window air velocity avg 333. Window outside air volume (cfm) avg 555. Window cu-ft 1.67. Window cfm max 967. Window cfm min 265. Window cfm avg 555. wACH max 7.5. wACH min 2.1. wACH avg 4.3. wACH Copy paste check (does not match calcultated) 7.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/King ML Jr K 8.txt. Feel free to add Survey data. King ML Jr K 8

CAB v 0.11 R -1

05:20:12 Start Time
05:20:12 End Time
0 Seconds