About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameMozart Wolfgang Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH5.9
13. Max ACH9.3
14. Avg ACH7
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft790.3
22. cuft7903
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 100. ACH Copy paste check (uses total or outside) 6.9. Window opening length (inches) 39. Window opening height (inches) 4. Co2 ambient (ppm) 420. Co2 test start (ppm) 2066. Co2 test end (ppm) 1248. Run time (min:sec) 6:00. Window air velocity max 378. Window air velocity min 19. Window air velocity avg 181. Window outside air volume (cfm) avg 196. Window cu-ft 1.08. Window cfm max 410. Window cfm min 21. Window cfm avg 196. wACH max 3.2. wACH min 0.2. wACH avg 1.5. wACH Copy paste check (does not match calcultated) 6.9.

Room 104. ACH Copy paste check (uses total or outside) 5.9. Window opening length (inches) 51. Window opening height (inches) 4. Co2 ambient (ppm) 420. Co2 test start (ppm) 234. Co2 test end (ppm) 1421. Run time (min:sec) 6:00. Window air velocity max 336. Window air velocity min 74. Window air velocity avg 129. Window outside air volume (cfm) avg 183. Window cu-ft 1.42. Window cfm max 476. Window cfm min 105. Window cfm avg 183. wACH max 3.6. wACH min 0.8. wACH avg 1.4. wACH Copy paste check (does not match calcultated) 5.9.

Room 103. ACH Copy paste check (uses total or outside) 6.7. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 426. Co2 test start (ppm) 2009. Co2 test end (ppm) 1070. Run time (min:sec) 8:00. Window air velocity max 161. Window air velocity min 37. Window air velocity avg 85. Window outside air volume (cfm) avg 111. Window cu-ft 1.31. Window cfm max 210. Window cfm min 48. Window cfm avg 111. wACH max 1.6. wACH min 0.4. wACH avg 0.8. wACH Copy paste check (does not match calcultated) 6.7.

Room 202. ACH Copy paste check (uses total or outside) 6.9. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 426. Co2 test start (ppm) 2976. Co2 test end (ppm) 1557. Run time (min:sec) 7:00. Window air velocity max 700. Window air velocity min 96. Window air velocity avg 414. Window outside air volume (cfm) avg 541. Window cu-ft 1.31. Window cfm max 914. Window cfm min 125. Window cfm avg 541. wACH max 6.9. wACH min 1.0. wACH avg 4.1. wACH Copy paste check (does not match calcultated) 6.9.

Room 201. ACH Copy paste check (uses total or outside) 6.5. Window opening length (inches) 47. Window opening height (inches) 4. Co2 ambient (ppm) 426. Co2 test start (ppm) 2435. Co2 test end (ppm) 1470. Run time (min:sec) 6:00. Window air velocity max 438. Window air velocity min 65. Window air velocity avg 183. Window outside air volume (cfm) avg 239. Window cu-ft 1.31. Window cfm max 572. Window cfm min 85. Window cfm avg 239. wACH max 4.3. wACH min 0.6. wACH avg 1.8. wACH Copy paste check (does not match calcultated) 6.5.

Room 108*. ACH Copy paste check (uses total or outside) 3.1. Window opening length (inches) 22. Window opening height (inches) 4. Co2 ambient (ppm) 425. Co2 test start (ppm) 2263. Co2 test end (ppm) 1467. Run time (min:sec) 11:00. Window air velocity max 492. Window air velocity min 87. Window air velocity avg 288. Window outside air volume (cfm) avg 176. Window cu-ft 0.61. Window cfm max 301. Window cfm min 53. Window cfm avg 176. wACH max 2.3. wACH min 0.4. wACH avg 1.3. wACH Copy paste check (does not match calcultated) 3.1.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Mozart Wolfgang Elem.txt. Feel free to add Survey data. Mozart Wolfgang Elem

CAB v 0.11 R -1

04:38:01 Start Time
04:38:01 End Time
0 Seconds