About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameO Donnell Hugh Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH3.1
13. Max ACH6.1
14. Avg ACH4.4
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1318.1
22. cuft13181
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 107*. ACH Copy paste check (uses total or outside) 4.3. Window opening length (inches) 22. Window opening height (inches) 4. Co2 ambient (ppm) 425. Co2 test start (ppm) 1800. Co2 test end (ppm) 1094. Run time (min:sec) 10:00. Window air velocity max 792. Window air velocity min 340. Window air velocity avg 520. Window outside air volume (cfm) avg 318. Window cu-ft 0.61. Window cfm max 484. Window cfm min 208. Window cfm avg 318. wACH max 3.7. wACH min 1.6. wACH avg 2.4. wACH Copy paste check (does not match calcultated) 4.3.

Room 111*. ACH Copy paste check (uses total or outside) 4. Window opening length (inches) 22. Window opening height (inches) 4. Co2 ambient (ppm) 425. Co2 test start (ppm) 1770. Co2 test end (ppm) 1071. Run time (min:sec) 11:00. Window air velocity max 943. Window air velocity min 149. Window air velocity avg 379. Window outside air volume (cfm) avg 232. Window cu-ft 0.61. Window cfm max 576. Window cfm min 91. Window cfm avg 232. wACH max 4.6. wACH min 0.7. wACH avg 1.8. wACH Copy paste check (does not match calcultated) 4.

Room 202**. ACH Copy paste check (uses total or outside) 3.5. Window opening length (inches) 44. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2192. Co2 test end (ppm) 1336. Run time (min:sec) 11:00. Window air velocity max 398. Window air velocity min 51. Window air velocity avg 158. Window outside air volume (cfm) avg 193. Window cu-ft 1.22. Window cfm max 486. Window cfm min 62. Window cfm avg 193. wACH max 3.7. wACH min 0.5. wACH avg 1.5. wACH Copy paste check (does not match calcultated) 3.5.

Room 212**. ACH Copy paste check (uses total or outside) 6.1. Window opening length (inches) 44. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2631. Co2 test end (ppm) 1746. Run time (min:sec) 5:00. Window air velocity max 433. Window air velocity min 118. Window air velocity avg 248. Window outside air volume (cfm) avg 303. Window cu-ft 1.22. Window cfm max 529. Window cfm min 144. Window cfm avg 303. wACH max 3.9. wACH min 1.1. wACH avg 2.2. wACH Copy paste check (does not match calcultated) 6.1.

Room 205**. ACH Copy paste check (uses total or outside) 5.5. Window opening length (inches) 44. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2142. Co2 test end (ppm) 1158. Run time (min:sec) 9:00. Window air velocity max 394. Window air velocity min 70. Window air velocity avg 196. Window outside air volume (cfm) avg 240. Window cu-ft 1.22. Window cfm max 482. Window cfm min 86. Window cfm avg 240. wACH max 3.6. wACH min 0.6. wACH avg 1.8. wACH Copy paste check (does not match calcultated) 5.5.

Room 103. ACH Copy paste check (uses total or outside) 6.9. Window opening length (inches) 60. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2117. Co2 test end (ppm) 1254. Run time (min:sec) 6:00. Window air velocity max 876. Window air velocity min 266. Window air velocity avg 582. Window outside air volume (cfm) avg 970. Window cu-ft 1.67. Window cfm max 1460. Window cfm min 443. Window cfm avg 970. wACH max 6.6. wACH min 2.0. wACH avg 4.4. wACH Copy paste check (does not match calcultated) 6.9.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/O Donnell Hugh Elem.txt. Feel free to add Survey data. O Donnell Hugh Elem

CAB v 0.11 R -1

04:38:26 Start Time
04:38:26 End Time
0 Seconds