About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameOtis James Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation
12. Min ACH3.4
13. Max ACH7.5
14. Avg ACH5.8
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1103.7
22. cuft11037
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 100. ACH Copy paste check (uses total or outside) 7.5. Window opening length (inches) 60. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2041. Co2 test end (ppm) 999. Run time (min:sec) 8:00. Window air velocity max 819. Window air velocity min 475. Window air velocity avg 600. Window outside air volume (cfm) avg 1000. Window cu-ft 1.67. Window cfm max 1365. Window cfm min 792. Window cfm avg 1000. wACH max 9.0. wACH min 5.2. wACH avg 6.6. wACH Copy paste check (does not match calcultated) 7.5.

Room 205. ACH Copy paste check (uses total or outside) 5.8. Window opening length (inches) 69. Window opening height (inches) 4. Co2 ambient (ppm) 412. Co2 test start (ppm) 1867. Co2 test end (ppm) 1087. Run time (min:sec) 8:00. Window air velocity max 1004. Window air velocity min 254. Window air velocity avg 581. Window outside air volume (cfm) avg 1114. Window cu-ft 1.92. Window cfm max 1924. Window cfm min 487. Window cfm avg 1114. wACH max 11.4. wACH min 2.9. wACH avg 6.6. wACH Copy paste check (does not match calcultated) 5.8.

Room 201. ACH Copy paste check (uses total or outside) 4.8. Window opening length (inches) 69. Window opening height (inches) 4. Co2 ambient (ppm) 412. Co2 test start (ppm) 2024. Co2 test end (ppm) 1122. Run time (min:sec) 9:00. Window air velocity max 576. Window air velocity min 174. Window air velocity avg 424. Window outside air volume (cfm) avg 813. Window cu-ft 1.92. Window cfm max 1104. Window cfm min 334. Window cfm avg 813. wACH max 6.8. wACH min 2.1. wACH avg 5.0. wACH Copy paste check (does not match calcultated) 4.8.

Room 306. ACH Copy paste check (uses total or outside) 3.4. Window opening length (inches) 60. Window opening height (inches) 4. Co2 ambient (ppm) 400. Co2 test start (ppm) 2150. Co2 test end (ppm) 1330. Run time (min:sec) 11:00. Window air velocity max 286. Window air velocity min 30. Window air velocity avg 103. Window outside air volume (cfm) avg 172. Window cu-ft 1.67. Window cfm max 477. Window cfm min 50. Window cfm avg 172. wACH max 2.9. wACH min 0.3. wACH avg 1.0. wACH Copy paste check (does not match calcultated) 3.4.

Room 307A. ACH Copy paste check (uses total or outside) 6.4. Window opening length (inches) 60. Window opening height (inches) 4. Co2 ambient (ppm) 400. Co2 test start (ppm) 2108. Co2 test end (ppm) 1300. Run time (min:sec) 6:00. Window air velocity max 98. Window air velocity min 17. Window air velocity avg 48. Window outside air volume (cfm) avg 80. Window cu-ft 1.67. Window cfm max 163. Window cfm min 28. Window cfm avg 80. wACH max 2.3. wACH min 0.4. wACH avg 1.1. wACH Copy paste check (does not match calcultated) 6.4.

Room 1. ACH Copy paste check (uses total or outside) 5.6. Window opening length (inches) 42. Window opening height (inches) 4. Co2 ambient (ppm) 415. Co2 test start (ppm) 1900. Co2 test end (ppm) 1900. Run time (min:sec) 8:00. Window air velocity max 698. Window air velocity min 359. Window air velocity avg 544. Window outside air volume (cfm) avg 635. Window cu-ft 1.17. Window cfm max 814. Window cfm min 419. Window cfm avg 635. wACH max 4.4. wACH min 2.3. wACH avg 3.5. wACH Copy paste check (does not match calcultated) 5.6.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Otis James Elem.txt. Feel free to add Survey data. Otis James Elem

CAB v 0.11 R -1

16:39:37 Start Time
16:39:37 End Time
0 Seconds

5.026003 cab pid: 1136510 httpd pid: error pid: