About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Taylor Charles H Elem |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation |
12. Min ACH | 8.2 |
13. Max ACH | 16.7 |
14. Avg ACH | 11.2 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 5 |
21. sqft | 491.5 |
22. cuft | 4915 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 107. ACH Copy paste check (uses total or outside) 16.7. Window opening length (inches) 52. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2097. Co2 test end (ppm) 962. Run time (min:sec) 4:00. Window air velocity max 735. Window air velocity min 330. Window air velocity avg 429. Window outside air volume (cfm) avg 620. Window cu-ft 1.44. Window cfm max 1062. Window cfm min 477. Window cfm avg 620. wACH max 9.9. wACH min 4.4. wACH avg 5.8. wACH Copy paste check (does not match calcultated) 16.7. Room 104. ACH Copy paste check (uses total or outside) 11. Window opening length (inches) 52. Window opening height (inches) 4. Co2 ambient (ppm) 396. Co2 test start (ppm) 2034. Co2 test end (ppm) 1049. Run time (min:sec) 5:00. Window air velocity max 707. Window air velocity min 119. Window air velocity avg 390. Window outside air volume (cfm) avg 563. Window cu-ft 1.44. Window cfm max 1021. Window cfm min 172. Window cfm avg 563. wACH max 7.6. wACH min 1.3. wACH avg 4.2. wACH Copy paste check (does not match calcultated) 11. Room 210. ACH Copy paste check (uses total or outside) 9.9. Window opening length (inches) 51. Window opening height (inches) 4. Co2 ambient (ppm) 428. Co2 test start (ppm) 1789. Co2 test end (ppm) 933. Run time (min:sec) 6:00. Window air velocity max 478. Window air velocity min 98. Window air velocity avg 202. Window outside air volume (cfm) avg 286. Window cu-ft 1.42. Window cfm max 677. Window cfm min 139. Window cfm avg 286. wACH max 5.0. wACH min 1.0. wACH avg 2.1. wACH Copy paste check (does not match calcultated) 9.9. Room 201. ACH Copy paste check (uses total or outside) 8.2. Window opening length (inches) 51. Window opening height (inches) 4. Co2 ambient (ppm) 428. Co2 test start (ppm) 2095. Co2 test end (ppm) 1273. Run time (min:sec) 5:00. Window air velocity max 478. Window air velocity min 206. Window air velocity avg 289. Window outside air volume (cfm) avg 409. Window cu-ft 1.42. Window cfm max 677. Window cfm min 292. Window cfm avg 409. wACH max 4.9. wACH min 2.1. wACH avg 3.0. wACH Copy paste check (does not match calcultated) 8.2. Room 100B. ACH Copy paste check (uses total or outside) 18. Window opening length (inches) 72. Window opening height (inches) 4. Co2 ambient (ppm) 417. Co2 test start (ppm) 2405. Co2 test end (ppm) 1516. Run time (min:sec) 2:00. Window air velocity max 833. Window air velocity min 218. Window air velocity avg 703. Window outside air volume (cfm) avg 1406. Window cu-ft 2.00. Window cfm max 1666. Window cfm min 436. Window cfm avg 1406. wACH max 20.3. wACH min 5.3. wACH avg 17.2. wACH Copy paste check (does not match calcultated) 18. |