About Us Contact Us

Building Data Report

0. Space TypeHotel
1. Establishment NameDisney Old Key West Florida
2. Address
3. CityLake Buena Vista
4. State / ProvinceFlorida
5. CountryUSA
6. Date4/16/2023
7. Data SourceCustomer
8. Performed byCustomer
9. Company Name Address Contact
10. Requirement SourceLocal Building Code
11. TechnologyHVAC Manual On Demand Ventilation - fan option
12. Min ACH4.5
13. Max ACH17.7
14. Avg ACH8.5
15. eACH
16. Filter MERV
17. Percent Outside Air
18. ON and Ventilates Entire Indoor AreaFail
19. Vent Clearance min 6 ftNo
20. No of Rooms761
21. sqft1851
22. cuft18383
23. No of Buildings49
24. Comments Grand Villa 2202 sq-ft. 49 building 761 rooms. On demand system. Fan goes into auto mode when temp adjusted. Need to select fan after temp adjust to have fan stay on only 1 fan speed. Floor 1 Lvrm 461 4x8+8 4x16 in 182 182 assumed too high above 182 vent 3 poles + 36in x 3 poles + 48in = 18x19ft. Dining Kitchen 259 4x16in 269 3 poles x 4 poles + 5in - 35in = 15x17ft. Doorway 969 4x10in Intake 211 17x28in Pole 35+25in 3 poles + 40 in = 120 in 10 ft. Grand Villa 2202 sq-ft. Bdrm 1 main vent had no ventilation marked as fail. Floor 2. Bdrm 2 Main someone closed off vents. Opened for measurements. Bdrm 3 Bath 240 3x7in vent 4x6ft Bath sink area 259 16x3in 8x6ft Total 12x6ft. Bdrm 3 Main 317 576 4x16in 12x14.7 there is a cut in make it 14ft. Hall 413 4x10in Intake 317 23x23 All values measured except as noted.