Sheet Last Modified: 03-12-2021    
School:  Ellwood Elementary School
Vendor: EMCOR Exhaust Retest
  Devine 2nd Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 100 13.0 0 Yes 1465 33 33 Unit Ventilator
100 A Counselor Office 0 Yes 297 6 6
100 B-C Nurse 0 Yes 342 7 7
100 E Main Office 0 Yes 416 9 9
102 102 414.0 27 574 13 13 Unit Ventilator
102 C Principal 0 Yes 400 9 9
103 103 328.0 21 582 13 13 Unit Ventilator
104 104 392.0 26 701 15 15 Unit Ventilator
105 105 457.0 30 1158 26 26 Unit Ventilator
107 107 420.0 28 905 20 20 Unit Ventilator
108 108 443.0 29 906 20 20 Unit Ventilator
109 109 468.0 31 904 20 20 Unit Ventilator
110 110 372.0 24 916 20 20 Unit Ventilator
111 111 260.0 17 448 10 10 Unit Ventilator
201 201 520.0 34 940 21 21 Unit Ventilator
202 202 195.0 13 912 20 13 Unit Ventilator
203 203 640.0 42 903 20 20 Unit Ventilator
204 204 430.0 28 914 20 20 Unit Ventilator
206 206 409.0 27 860 19 19 Unit Ventilator
207 207 423.0 28 912 20 20 Unit Ventilator
208 208 417.0 27 904 20 20 Unit Ventilator
210 210 154.0 10 903 20 10 Unit Ventilator
211 211 511.0 34 912 20 20 Unit Ventilator
212 212 534.0 35 975 22 22 Unit Ventilator
- Auditorium 0.0 0 2900 65 0 AHU
- Gym 2,115.0 141 3922 89 89 AHU
- Library 0.0 0 Yes 2809 63 63 AHU
- Floor 1 East Corridor 0.0 0 0 0 Unit Ventilator
- Floor 1 East Corridor 0.0 0 0 0 Unit Ventilator