Sheet Last Modified: 03-22-2021      
School:  Alexander Adaire Elementary School House Fan Abated/Final Report    
Vendor: Chadwick Test 1 Devine Test 1 Devine Test 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Auditorium 2,417 161 3,234 73 73 Air Handling Unit
- Gym/Cafeteria 322 21 3,432 78 21 Air Handling Unit
- Main Ofiice 161 10 468 10 10 Unit Ventilator
100 Classroom 452 30 960 21 21 Unit Ventilator
101 Classroom 480 32 960 21 21 Unit Ventilator
102 Classroom 509 33 960 21 21 Unit Ventilator
103 Classroom 409 27 960 21 21 Unit Ventilator
104 Classroom 514 34 960 21 21 Unit Ventilator
105 Classroom 523 34 960 21 21 Unit Ventilator
106 Classroom 125 8 Yes 782 17 17 Unit Ventilator
107 Classroom 272 18 380 8 8 Unit Ventilator
108 Faculty Room 0 0 104 2 0 Unit Ventilator
109 Classroom 485 32 1,470 33 32 Unit Ventilator
200 Classroom 546 36 912 20 20 Unit Ventilator
201 Classroom 607 40 912 20 20 Unit Ventilator
202 Classroom 613 40 936 21 21 Unit Ventilator
203 Library 593 39 1,080 24 24 Unit Ventilator
204 Classroom 480 32 912 20 20 Unit Ventilator
205 Classroom 182 12 Yes 960 21 21 Unit Ventilator
206 Classroom 317 21 984 22 21 Unit Ventilator
207 Classroom 798 53 456 10 10 Unit Ventilator
208 Classroom 577 38 960 21 21 Unit Ventilator
209 Classroom 458 30 960 21 21 Unit Ventilator
210 Classroom 519 34 960 21 21 Unit Ventilator
211 Classroom 534 35 1,008 22 22 Unit Ventilator
212 Classroom 1,568 104 960 21 21 Unit Ventilator
214 Classroom 340 22 960 21 21 Unit Ventilator
216 Classroom 617 41 456 10 10 Unit Ventilator
218 Classroom 424 28 782 17 17 Unit Ventilator