Sheet Last Modified: | 04-28-2021 | |||||||||||||||||||||||
School: | Cayuga Elementary School (former St. Henry’s) | |||||||||||||||||||||||
Vendor: | Chadwick Test 1 | Devine Test 1 | ||||||||||||||||||||||
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. | ||||||||||||||||||||||||
Classroom ID / Area ID Number | Classroom / Area Type supplied | Actual Mechanical System Outside Air CFM (OA) | Mechanical System Occupancy (OA CFM / 15) | Active Pure Unit Installed | Classroom / Area Square Footage | Square Footage Occupancy (SqFt / 44) | Maximum Occupancy per Room | Type of Unit | ||||||||||||||||
101 | classroom | 355.0 | 23 | 830 | 18 | 18 | Unit Ventilator | |||||||||||||||||
102 | classroom | 375.0 | 25 | 740 | 16 | 16 | Unit Ventilator | |||||||||||||||||
103 | classroom | 315.0 | 21 | 795 | 18 | 18 | Unit Ventilator | |||||||||||||||||
104 | classroom | 280.0 | 18 | 796 | 18 | 18 | Unit Ventilator | |||||||||||||||||
105 | Nurse's Office | 0 | Yes | 330 | 7 | 7 | N/A | |||||||||||||||||
106 | classroom | 275.0 | 18 | 403 | 9 | 9 | Unit Ventilator | |||||||||||||||||
117 | classroom | 736.0 | 49 | 806 | 18 | 18 | Unit Ventilator | |||||||||||||||||
118 | classroom | 625.0 | 41 | 688 | 15 | 15 | Unit Ventilator | |||||||||||||||||
119 | classroom | 586.0 | 39 | 845 | 19 | 19 | Unit Ventilator | |||||||||||||||||
120 | classroom | 335.0 | 22 | 670 | 15 | 15 | Unit Ventilator | |||||||||||||||||
201 | classroom | 325.0 | 21 | 830 | 18 | 18 | Unit Ventilator | |||||||||||||||||
202 | classroom | 305.0 | 20 | 740 | 16 | 16 | Unit Ventilator | |||||||||||||||||
203 | classroom | 380.0 | 25 | 795 | 18 | 18 | Unit Ventilator | |||||||||||||||||
204 | classroom | 360.0 | 24 | 796 | 18 | 18 | Unit Ventilator | |||||||||||||||||
205 | classroom | 355.0 | 23 | 765 | 17 | 17 | Unit Ventilator | |||||||||||||||||
206 | classroom | 310.0 | 20 | 780 | 17 | 17 | Unit Ventilator | |||||||||||||||||
214 | classroom | 375.0 | 25 | 728 | 16 | 16 | Unit Ventilator | |||||||||||||||||
215 | classroom | 365.0 | 24 | 693 | 15 | 15 | Unit Ventilator | |||||||||||||||||
216 | classroom | 330.0 | 22 | 737 | 16 | 16 | Unit Ventilator | |||||||||||||||||
217 | classroom | 1,606.0 | 107 | 822 | 18 | 18 | Unit Ventilator | |||||||||||||||||
301 | classroom | 345.0 | 23 | 830 | 18 | 18 | Unit Ventilator | |||||||||||||||||
302 | classroom | 275.0 | 18 | 740 | 16 | 16 | Unit Ventilator | |||||||||||||||||
303 | classroom | 380.0 | 25 | 795 | 18 | 18 | Unit Ventilator | |||||||||||||||||
304 | classroom | 380.0 | 25 | 796 | 18 | 18 | Unit Ventilator | |||||||||||||||||
305 | classroom | 553.0 | 36 | 765 | 17 | 17 | Unit Ventilator | |||||||||||||||||
306 | classroom | 315.0 | 21 | 790 | 17 | 17 | Unit Ventilator | |||||||||||||||||
- | Gym | 1,213.0 | 80 | 2754 | 62 | 62 | Air Handling Unit | |||||||||||||||||
- | Basement Corridor | 90.0 | 6 | 0 | 0 | Air Handling Unit | ||||||||||||||||||
- | Main Entrance Corridor | 46.0 | 3 | 0 | 0 | Air Handling Unit | ||||||||||||||||||
- | 1st Floor Corridor | 31.0 | 2 | 0 | 0 | Air Handling Unit | ||||||||||||||||||
- | Cafeteria | 936.0 | 62 | 3432 | 78 | 62 | Air Handling Unit | |||||||||||||||||