Sheet Last Modified: 05-18-2021    
School:  Kenneth C. Crossan Elementary School
Vendor: Devine Test 1
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Kindergarten Classroom 580 38 1088 24 24 Air Handling Unit
2 Classroom 555 37 900 20 20 Air Handling Unit
3 Classroom 522 34 930 21 21 Air Handling Unit
4 Classroom 299 19 840 19 19 Air Handling Unit
5 Kindergarten Classroom 0 Yes 900 20 20 Air Handling Unit
5 Classroom 505 33 600 13 13 Air Handling Unit
6 Classroom 820 54 805 18 18 Air Handling Unit
7 Computer Classrm. 437 29 900 20 20 Air Handling Unit
8 Classroom 580 38 1094 24 24 Air Handling Unit
9 Classrom 444 29 840 19 19 Air Handling Unit
9A Teachers Rm. 0 0 Yes 450 10 10 Air Handling Unit
10 Classroom 822 54 600 13 13 Air Handling Unit
11 Classroom 466 31 720 16 16 Air Handling Unit
12 Classroom 606 40 720 16 16 Air Handling Unit
13 Classroom 626 41 720 16 16 Air Handling Unit
- Auditorium 1,107.00 73 2760 62 62 Air Handling Unit
- Cafeteria/Gym 0 0 2300 52 0 Air Handling Unit
- Counselors Rm. 0 0 Yes 450 10 10 Air Handling Unit
- Grnd. Fl. Boys Bathrm. 568 37 736 16 16 Air Handling Unit
- Grnd. Fl. Girls Bathrm. 620 41 775 17 17 Air Handling Unit
- Ind. Arts Classroom 0 0 600 13 0 N/A
- Library 525 35 1152 26 26 Air Handling Unit
- Main Office 0 0 Yes 460 10 10 N/A
- Nurse Office 0 Yes 450 10 10 N/A
- Art Room 0 Yes 600 13 13 N/A
- Principal's Ofice 0 0 450 10 0 N/A
Portable Classroom 0 0 Yes 0 0 Unit Ventilator