Sheet Last Modified: 05-24-2021    
School:  Franklin S. Edmonds Elementary School
Vendor: Devine Test 1 Devine Test 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B1 Classroom 0 0 Yes 400 9 9 Unit Ventilator
B2 Kitchen 75 5 572 13 5 Unit Ventilator
B3 Kitchen 165 11 480 10 10 Unit Ventilator
H2 Office 0 Yes 178 4 4 Convector
101 Classroom 165 11 Yes 1128 25 25 Unit Ventilator
102 Classroom 441 29 1056 24 24 Unit Ventilator
103 Classroom 397 26 864 19 19 Unit Ventilator
104 Classroom 455 30 1056 24 24 Unit Ventilator
105 Classroom 412 27 1128 25 25 Unit Ventilator
106 Classroom 460 30 1056 24 24 Unit Ventilator
107 Classroom 256 17 720 16 16 Unit Ventilator
108 Classroom 567 37 1056 24 24 Unit Ventilator
109 Classroom 527 35 1056 24 24 Unit Ventilator
110 Classroom 431 28 1056 24 24 Unit Ventilator
111 Classroom 634 42 1008 22 22 Unit Ventilator
112A Office 0 Yes 364 8 8 Convector
112B Office 0 Yes 210 4 4 Convector
113 Classroom 662 44 1008 22 22 Unit Ventilator
114 Office 0 Yes 364 8 8 Unit Ventilator
115 Classroom 551 36 1008 22 22 Unit Ventilator
115A Office 0 Yes 252 5 5 Convector
116 Classroom 169 11 Yes 736 16 16 Unit Ventilator
117 Classroom 299 19 912 20 19 Unit Ventilator
118 Classroom 281 18 912 20 18 Unit Ventilator
118A Office 0 175 3 0 Convector
119 Classroom 282 18 912 20 18 Unit Ventilator
120 Classroom 0 0 Yes 912 20 20 Unit Ventilator
121 Classroom 0 0 Yes 912 20 20 Unit Ventilator
122 Classroom 340 22 912 20 20 Unit Ventilator
201 Classroom 503 33 1056 24 24 Unit Ventilator
202 Classroom 418 27 1056 24 24 Unit Ventilator
203 Classroom 415 27 1056 24 24 Unit Ventilator
204 Classroom 395 26 1056 24 24 Unit Ventilator
205 Classroom 491 32 1056 24 24 Unit Ventilator
206 Classroom 414 27 1056 24 24 Unit Ventilator
207 Classroom 485 32 1056 24 24 Unit Ventilator
208 Classroom 348 23 1056 24 23 Unit Ventilator
209 Classroom 431 28 1056 24 24 Unit Ventilator
210 Classroom 304 20 1056 24 20 Unit Ventilator
211 Classroom 322 21 1056 24 21 Unit Ventilator
212 Classroom 31 2 Yes 1056 24 24 Unit Ventilator
213 Classroom 186 12 1008 22 12 Unit Ventilator
215 Classroom 509 33 1008 22 22 Unit Ventilator
216 Library 969 64 1008 22 22 Unit Ventilator
217 Classroom 503 33 1008 22 22 Unit Ventilator
217-A VP office 0 Yes 252 5 5 Convector
218 Classroom 0 0 Yes 864 19 19 Unit Ventilator
219 Classroom 44 2 1008 22 2 Unit Ventilator
- Auditorium 1860 124 1849 42 42 Air Handling Unit
- Gym 1195 79 2795 63 63 Air Handling Unit
- Lunch 0 0 780 17 0 Unit Ventilator
- Cafeteria 411 27 Yes 1560 35 35 Unit Ventilator
- Kitchen 0 0 Yes 400 9 9 Unit Ventilator
- Women Helper 0 Yes 262 5 5 Convector
- Nurse 0 0 Yes 280 6 6 Convector
- Prin. Office 0 0 Yes 322 7 7 Convector
- Main Office 0 0 Yes 650 14 14 Convector