School:  Lewis Elkin Elementary School  
Vendor: Devine Test 1 Devine Test 2 Devine Test 3  
School:  Elkin Little School House  
Vendor: Devine Test 1      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
101 Classroom 391 26 420 9 9 Unit Ventilator
102 Classroom 0 0 Yes 1136 25 25 Unit Ventilator Bad Motor
103 Classroom 299 19 Yes 1303 29 29 Unit Ventilator
104 Classroom 293 19 1201 27 19 Unit Ventilator
105 Classroom 301 20 Yes 1269 28 28 Unit Ventilator
106 Classroom 300 20 418 9 9 Unit Ventilator
107 Classroom 411 27 897 20 20 Unit Ventilator
108 Classroom 386 25 897 20 20 Unit Ventilator
109 Classroom 389 25 897 20 20 Unit Ventilator
110 Classroom 376 25 821 18 18 Unit Ventilator
111 Classroom 313 20 938 21 20 Unit Ventilator
112 Classroom 363 24 898 20 20 Unit Ventilator
113 Classroom 318 21 898 20 20 Unit Ventilator
114 Classroom 349 23 898 20 20 Unit Ventilator
115 Classroom 345 23 1024 23 23 Unit Ventilator
116 Lounge 133 8 309 7 7 Unit Ventilator
117 Classroom 129 8 215 4 4 Unit Ventilator
117 Office 96 6 317 7 6 Unit Ventilator
117A Classroom Vestibule 171 11 102 2 2 Unit Ventilator
118 Office 109 7 122 2 2 Unit Ventilator
119 Office 105 7 117 2 2 Unit Ventilator
120 Security Office 214 14 259 5 5 Unit Ventilator
121 Office 0 Yes 400 9 9 N/A
201 Classroom 496 33 772 17 17 Unit Ventilator
202 Classroom 325 21 933 21 21 Unit Ventilator
203 Classroom 385 25 838 19 19 Unit Ventilator
204 Classroom 360 24 756 17 17 Unit Ventilator
204A Office 178 11 201 4 4 Unit Ventilator
205 Classroom 334 22 815 18 18 Unit Ventilator
206 Classroom 402 26 815 18 18 Unit Ventilator
207 Classroom 357 23 815 18 18 Unit Ventilator
207A Office 74 4 201 4 4 Unit Ventilator
208 Classroom 388 25 762 17 17 Unit Ventilator
209 Classroom 365 24 811 18 18 Unit Ventilator
210 Classroom 285 19 814 18 18 Unit Ventilator
211 Classroom 430 28 746 16 16 Unit Ventilator
211A Office 161 10 201 4 4 Unit Ventilator
212 Classroom 312 20 810 18 18 Unit Ventilator
213 Classroom 358 23 815 18 18 Unit Ventilator
214 Classroom 376 25 786 17 17 Unit Ventilator
215 Classroom 0 0 Yes 863 19 19 Unit Ventilator Not operating. Facility manager is aware
215A Classroom 131 8 201 4 4 Unit Ventilator
216 Classroom 395 26 855 19 19 Unit Ventilator
217 Classroom 493 32 1259 28 28 Unit Ventilator 2 Units.
218 Classroom 437 29 788 17 17 Unit Ventilator
219 Classroom 76 5 117 2 2 Unit Ventilator
220 Library 1,770 118 2982 67 67 Unit Ventilator 4 Units. 1 unit is a wall unit.  1 unit is a window unit.  1 unit serves 220, but, is in 220B.  1 unit serves 220, but, is in 220C.  This unit needs repair and has 0 CFM of OA.
220A Office 214 14 373 8 8 Unit Ventilator
220B Office 0 0 421 9 0 N/A No ouside air to room.
220C Office 0 0 398 9 0 N/A No ouside air to room.
221 Room 0 0 141 3 0 Unit Ventilator Unit not operating
B01 Classroom 360 24 1859 42 24 Unit Ventilator No return air cover/grille
B02 Classroom 364 24 928 21 21 Unit Ventilator
B03 Classroom 183 12 525 11 11 Unit Ventilator
B04 Classroom 300 20 613 13 13 Unit Ventilator 2 Units.  UV-2 is a window unit.  UV-3 is a wall unit.
- Assistant Principal's Office 40 2 98 2 2 Unit Ventilator
- Auditorium 0 0 7138 162 0 Unit Ventilator 4 units.  UV-1, UV-2, UV-3, and UV-4 are not operating. One fell down.  Facility manager is aware. Might be control issue
- Main Office Conference Room 0 0 181 4 0 Unit Ventilator Measured 0 CFM at all diffusers. No access to unit since Building Engineer does not have key to Server Room.
- Copy room 34 2 179 4 2 Unit Ventilator Measured 0 CFM at all diffusers. No access to unit since Building Engineer does not have key to Server Room.
- Parent Resources Office 0 0 84 1 0 Unit Ventilator Measured 0 CFM at all diffusers. No access to unit since Building Engineer does not have key to Server Room.
- Education Office 57 3 207 4 3 Unit Ventilator
- Gymnasium 3,457 230 4778 108 108 Unit Ventilator 2 Units.
- Ms. Potts' Office 46 3 133 3 3 Unit Ventilator
- Health Office/Nurses Area/Nurse's Suite 480 32 637 14 14 Unit Ventilator
- Cafeteria/Lunchroom  1,731 115 2558 58 58 Unit Ventilator 6 Units.  Univent 6 has a bad motor and 0 CFM of OA.
- Principal's Office 34 2 167 3 2 Unit Ventilator
- Main Office  235 15 Yes 674 15 15 Unit Ventilator
- Teacher's Lounge 0 0 623 14 0 Unit Ventilator Not operating. Facility manager is aware. Might be control issue
- Library (Wall mount unit, south area) 33 2 2775 63 2 Unit Ventilator data is for Wall mount unit, south area.  Unit against window not operating
LSH Building
1 Classroom 829 55 1018 23 23 Air Handling Unit
2 Classroom 619 41 1018 23 23 Air Handling Unit
3 Classroom 651 43 1018 23 23 Air Handling Unit
4 Classroom 486 32 1018 23 23 Air Handling Unit
5 Classroom 410 27 1018 23 23 Air Handling Unit
6 Classroom 586 39 1018 23 23 Air Handling Unit
7 Classroom 379 25 1,018 23 23 Air Handling Unit
8 Classroom 519 34 1018 23 23 Air Handling Unit
- Main Office 0 0 295 6 0 Air Handling Unit Need to confirm with Jason that this reading is for the main office.  Previous note for this line: Broken belt none onsite
- Multi Purpose Room 1,105 73 1995 45 45 Air Handling Unit
- Teacher's Lounge 0 0 220 5 0 Air Handling Unit Motor Issue