Sheet Last Modified: 05-20-2021    
School:  Lingelbach Elementary School
Vendor: Devine Test 1 Devine Test 2 Devine Test 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 227 15 968 22 15 Unit Ventilator
102 Classroom 477 31 968 22 22 Unit Ventilator
103 Classroom 219 14 Yes 889 20 20 Unit Ventilator
104 Classroom 0 0 Yes 963 21 21 Unit Ventilator
105 Classroom 268 17 941 21 17 Unit Ventilator
106 Classroom 293 19 971 22 19 Unit Ventilator
200 Classroom 444 29 1394 31 29 Unit Ventilator
200A Classroom 675 45 1235 28 28 Unit Ventilator
201 Classroom 514 34 969 22 22 Unit Ventilator
202 Classroom 280 18 969 22 18 Unit Ventilator
203 Classroom 278 18 971 22 18 Unit Ventilator
204 Classroom 290 19 971 22 19 Unit Ventilator
205 Classroom 336 22 955 21 21 Unit Ventilator
206 Classroom 278 18 969 22 18 Unit Ventilator
301 Classroom 285 19 940 21 19 Unit Ventilator
302 Classroom 795 53 937 21 21 Unit Ventilator
303 Classroom 837 55 933 21 21 Unit Ventilator
303A Classroom 357 23 463 10 10 Unit Ventilator
304 Classroom 406 27 464 10 10 Unit Ventilator
305 Classroom 395 26 967 21 21 Unit Ventilator
306 Classroom 906 60 944 21 21 Unit Ventilator
- Auditorium 841 56 2847 64 56 Air Handling Unit
- Counselor's Office 0 Yes 137 3 3 Convector
- Gym/Cafeteria 1,451 96 2340 53 53 Air Handling Unit
- Library 855 57 2312 52 52 Unit Ventilator
- Main Office 0 Yes 332 7 7 Convector
- North Stairwell 0 0 168 3 0 Unit Ventilator
- Nurse's Office 0 Yes 269 6 6 Convector
- Principal's Office 0 Yes 262 5 5 Convector
- Reading Room 0 Yes 137 3 3 Convector
- South Stairwell 0 0 168 3 0 Unit Ventilator