Sheet Last Modified: 04-08-2021    
School:  William H. Loesche Elementary School
Vendor: Devine Test 1 Devine Test 2
  Devine Test 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 286 19 840 19 19 Unit Ventilator
101 Classroom 282 18 840 19 18 Unit Ventilator
102 Classroom 82.0 5 Yes 784 17 17 Unit Ventilator
103 Classroom 288 19 840 19 19 Unit Ventilator
104 Classroom 0.0 0 840 19 0 Unit Ventilator
105 Classroom 300 20 840 19 19 Unit Ventilator
107 Classroom 288 19 840 19 19 Unit Ventilator
108 Classroom 213.0 14 Yes 1122 25 25 Unit Ventilator
109 Classroom 185.0 12 840 19 12 Unit Ventilator
110 Classroom 156.0 10 Yes 840 19 19 Unit Ventilator
111 Classroom 190.0 12 Yes 882 20 20 Unit Ventilator
112 Classroom 285 19 729 16 16 Unit Ventilator
200 Classroom 258 17 840 19 17 Unit Ventilator
201 Classroom 292 19 840 19 19 Unit Ventilator
202 Classroom 283 18 840 19 18 Unit Ventilator
203 Classroom 158.0 10 Yes 840 19 19 Unit Ventilator
204 Classroom 262 17 840 19 17 Unit Ventilator
205 Classroom 205.0 13 Yes 840 19 19 Unit Ventilator
206 Classroom 153.0 10 476 10 10 Unit Ventilator
207 Classroom 297 19 840 19 19 Unit Ventilator
208 Classroom 210.0 14 840 19 14 Unit Ventilator
208A Classroom 150.0 10 252 5 5 Unit Ventilator
209 Classroom 184.0 12 Yes 840 19 19 Unit Ventilator
210 Classroom 193.0 12 780 17 12 Unit Ventilator
211 Classroom 142.0 9 Yes 783 17 17 Unit Ventilator
212 Classroom 267 17 840 19 17 Unit Ventilator
214 Classroom 280 18 1212 27 18 Unit Ventilator
215 Classroom 268 17 1232 28 17 Unit Ventilator
216 Classroom 415.0 27 756 17 17 Unit Ventilator
217 Classroom 276 18 841 19 18 Unit Ventilator
218 Classroom 144.0 9 Yes 840 19 19 Unit Ventilator
219 Classroom 106.0 7 Yes 840 19 19 Unit Ventilator
220 Classroom 246.0 16 870 19 16 Unit Ventilator
221 Classroom 140.0 9 870 19 9 Unit Ventilator
222 Classroom 106.0 7 840 19 7 Unit Ventilator
223 Classroom 175.0 11 840 19 11 Unit Ventilator
224 Classroom 94.0 6 840 19 6 Unit Ventilator
A-1 Classroom 242 16 884 20 16 Unit Ventilator
A-2 Classroom 254 16 884 20 16 Unit Ventilator
A-3 Classroom 298 19 884 20 19 Unit Ventilator
A-4 Classroom 281 18 884 20 18 Unit Ventilator
- A-wing Mech. Rm 0.0 0 358 8 0 Unit Ventilator
- Auditorium 0.0 0 3600 81 0 Air Handling Unit
B-1 Classroom 314 20 806 18 18 Unit Ventilator
B-2 Classroom 311 20 806 18 18 Unit Ventilator
B-3 Classroom 300 20 806 18 18 Unit Ventilator
B-4 Classroom 313 20 806 18 18 Unit Ventilator
B-5 Classroom 287 19 806 18 18 Unit Ventilator
B-6 Classroom 297 19 905 20 19 Unit Ventilator
B-7 Classroom 285 19 905 20 19 Unit Ventilator
B-8 Classroom 304 20 905 20 20 Unit Ventilator
B-9 Classroom 282 18 905 20 18 Unit Ventilator
- Backstage 0.0 0 180 4 0 Unit Ventilator
- Backstage Dressing Rm. 172.0 11 252 5 5 Unit Ventilator
- Cafeteria 0.0 0 Yes 5540 125 125 Air Handling Unit
- GYM 0.0 0 4496 102 0 Air Handling Unit
- Library 0.0 0 1131 25 0 Unit Ventilator
- Main Office 292.0 19 992 22 19 Unit Ventilator
- Nurse's Office 94.0 6 706 16 6 Unit Ventilator
- Principal's Office 148.0 9 308 7 7 Unit Ventilator