Sheet Last Modified: | 04-06-2021 | |||||||||||||
School: | General George G. Meade Elementary-Middle School | |||||||||||||
Vendor: | EMCOR Test 1 | EMCOR Test 2 | ||||||||||||
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. | ||||||||||||||
Classroom ID / Area ID Number | Classroom / Area Type supplied | Actual Mechanical System Outside Air CFM (OA) | Mechanical System Occupancy (OA CFM / 15) | Active Pure Unit Installed | Classroom / Area Square Footage | Square Footage Occupancy (SqFt / 44) | Maximum Occupancy per Room | Type of Unit | ||||||
15 | Classroom | 378 | 25 | Yes | 644 | 14 | 14 | Unit Ventilator | ||||||
16 | Classroom | 336 | 22 | 833 | 18 | 18 | Unit Ventilator | |||||||
17 | Classroom | 184 | 12 | 330 | 7 | 7 | Unit Ventilator | |||||||
18 | Classroom | 686 | 45 | Yes | 1101 | 25 | 25 | Unit Ventilator | ||||||
101 | Classroom | 294 | 19 | 892 | 20 | 19 | Unit Ventilator | |||||||
102 | Classroom | 299 | 19 | Yes | 765 | 17 | 17 | Unit Ventilator | ||||||
103 | Classroom | 360 | 24 | Yes | 823 | 18 | 18 | Unit Ventilator | ||||||
104 | Classroom | 281 | 18 | 705 | 16 | 16 | Unit Ventilator | |||||||
105 | Classroom | 445 | 29 | 674 | 15 | 15 | Unit Ventilator | |||||||
106 | Classroom | 405 | 27 | 846 | 19 | 19 | Unit Ventilator | |||||||
107 | Classroom | 332 | 22 | 526 | 11 | 11 | Unit Ventilator | |||||||
108 | Classroom | 294 | 19 | 670 | 15 | 15 | Unit Ventilator | |||||||
109 | Classroom | 279 | 18 | 705 | 16 | 16 | Unit Ventilator | |||||||
115 | Classroom | 640 | 42 | Yes | 865 | 19 | 19 | Unit Ventilator | ||||||
116 | Classroom | 325 | 21 | Yes | 413 | 9 | 9 | Unit Ventilator | ||||||
117 | Classroom | 433 | 28 | Yes | 837 | 19 | 19 | Unit Ventilator | ||||||
118 | Classroom | 664 | 44 | Yes | 849 | 19 | 19 | Unit Ventilator | ||||||
200 | Classroom | 193 | 12 | 349 | 7 | 7 | Unit Ventilator | |||||||
201 | Classroom | 414 | 27 | 667 | 15 | 15 | Unit Ventilator | |||||||
202 | Classroom | 53 | 3 | 673 | 15 | 3 | Unit Ventilator | |||||||
203 | Classroom | 275 | 18 | 666 | 15 | 15 | Unit Ventilator | |||||||
204 | Classroom | 360 | 24 | 669 | 15 | 15 | Unit Ventilator | |||||||
205 | Classroom | 343 | 22 | 701 | 15 | 15 | Unit Ventilator | |||||||
206 | Classroom | 280 | 18 | 705 | 16 | 16 | Unit Ventilator | |||||||
207 | Classroom | 303 | 20 | 671 | 15 | 15 | Unit Ventilator | |||||||
208 | Classroom | 259 | 17 | 576 | 13 | 13 | Unit Ventilator | |||||||
209 | Classroom | 0 | 0 | 540 | 12 | 0 | Unit Ventilator | |||||||
210 | Classroom | 311 | 20 | 511 | 11 | 11 | Unit Ventilator | |||||||
211 | Classroom | 222 | 14 | 720 | 16 | 14 | Unit Ventilator | |||||||
215 | Classroom | 550 | 36 | 843 | 19 | 19 | Unit Ventilator | |||||||
216 | Classroom | 306 | 20 | 855 | 19 | 19 | Unit Ventilator | |||||||
217 | Classroom | 169 | 11 | 842 | 19 | 11 | Unit Ventilator | |||||||
218 | Classroom | 631 | 42 | 852 | 19 | 19 | Unit Ventilator | |||||||
285 | Classroom | 273 | 18 | 0 | 0 | 0 | Unit Ventilator | |||||||
301 | Classroom | 883 | 58 | 2031 | 46 | 46 | Unit Ventilator | |||||||
304 | Classroom | 276 | 18 | 670 | 15 | 15 | Unit Ventilator | |||||||
305 | Classroom | 346 | 23 | 702 | 15 | 15 | Unit Ventilator | |||||||
306 | Classroom | 319 | 21 | 706 | 16 | 16 | Unit Ventilator | |||||||
307 | Classroom | 347 | 23 | 670 | 15 | 15 | Unit Ventilator | |||||||
308 | Classroom | 112 | 7 | 852 | 19 | 7 | Unit Ventilator | |||||||
309 | Classroom | 333 | 22 | 309 | 7 | 7 | Unit Ventilator | |||||||
310 | Classroom | 247 | 16 | 510 | 11 | 11 | Unit Ventilator | |||||||
311 | Classroom | 351 | 23 | 706 | 16 | 16 | Unit Ventilator | |||||||
312 | Classroom | 305 | 20 | 514 | 11 | 11 | Unit Ventilator | |||||||
315 | Classroom | 289 | 19 | 838 | 19 | 19 | Unit Ventilator | |||||||
316 | Classroom | 285 | 19 | 855 | 19 | 19 | Unit Ventilator | |||||||
317 | Classroom | 548 | 36 | 847 | 19 | 19 | Unit Ventilator | |||||||
318 | Classroom | 647 | 43 | 852 | 19 | 19 | Unit Ventilator | |||||||
- | Main Office | 0 | Yes | 305.08 | 6 | 6 | N/A | |||||||
- | Nurse Office | 0 | Yes | 242.55 | 5 | 5 | N/A | |||||||
- | 1st Floor Hall | 310 | 20 | 2688 | 61 | 20 | Unit Ventilator | |||||||
- | 1st Floor Nurse RR | 0 | 0 | 244 | 5 | 0 | N/A | |||||||
- | 1st Floor Staff Womens RR | 0 | 0 | 393 | 8 | 0 | N/A | |||||||
- | 2nd Floor Hall | 0 | 0 | 2066 | 46 | 0 | Unit Ventilator | |||||||
- | 2nd Floor Mens RR | 99 | 6 | 355 | 8 | 6 | N/A | |||||||
- | 2nd Floor Womens RR | 236 | 15 | 328 | 7 | 7 | N/A | |||||||
- | 3rd Floor Hall | 289 | 19 | 2661 | 60 | 19 | Unit Ventilator | |||||||
- | 3rd Floor Mens RR | 95 | 6 | 259 | 5 | 5 | N/A | |||||||
- | 3rd Floor Womens RR | 219 | 14 | 328 | 7 | 7 | N/A | |||||||
- | Cafeteria | 754 | 50 | 5223 | 118 | 50 | Unit Ventilator | |||||||
- | Bsmt: Boys RR | 0 | 0 | 765 | 17 | 0 | N/A | |||||||
- | Bsmt: Grils RR | 0 | 0 | 697 | 15 | 0 | N/A | |||||||
- | Staff Restroom: 1st Floor | 0 | 0 | 168 | 3 | 0 | N/A | |||||||
- | Library | 0 | 0 | 2062.2 | 46 | 0 | Unit Ventilator | |||||||
- | Staff Restroom: 2nd Floor | 0.0 | 0 | 305 | 6 | 0 | N/A | |||||||
- | Staff Restroom: 3rd Floor | 0.0 | 0 | 308 | 7 | 0 | N/A | |||||||