Sheet Last Modified: 05-04-2021        
School:  Parkway Northwest High School former Hill, JE (Hill-Freedman)
Vendor: Goldner Goldner Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
108 Room 676 45 676 15 15 Unit Ventilator
109 Room 333 22 714 16 16 Fan Coil Unit
110 Room 168 11 1015 23 11 Unit Ventilator
130 Room 564 37 630 14 14 Unit Ventilator
131 Room 476 31 580 13 13 Unit Ventilator
132 Room 528 35 580 13 13 Unit Ventilator
133 Room 452 30 469 10 10 Unit Ventilator
134 Room 496 33 1015 23 23 Unit Ventilator
135 Room 304 20 812 18 18 Unit Ventilator
136 Room 424 28 424 9 9 Unit Ventilator
203 Room 409 27 600 13 13 Unit Ventilator
204 Room 363 24 667 15 15 Unit Ventilator
205 Room 376 25 720 16 16 Unit Ventilator
206 Room 350 23 810 18 18 Unit Ventilator
207 Room 371 24 783 17 17 Unit Ventilator
210 Room 482 32 1116 25 25 Fan Coil Unit
211 Room 329 21 957 21 21 Unit Ventilator
221 Room 300 20 580 13 13 Unit Ventilator
222 Room 75 5 580 13 5 Unit Ventilator
223 Room 523 34 580 13 13 Unit Ventilator
224 Room 717 47 580 13 13 Unit Ventilator
225 Room 250 16 580 13 13 Unit Ventilator
226 Room 163 10 580 13 10 Unit Ventilator
- Auditurium 912 60 1050 23 23 Unit Ventilator
- Gym 969 64 2460 55 55 Unit Ventilator
- Main Office 0 0 Yes 399 9 9 Unit Ventilator