Sheet Last Modified: 03-18-2021    
School:  Paul Robeson High School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B-2 Classroom 0.0 0 1,073 24 0 Fan Coil Unit
100 Classroom 380.0 25 940 21 21 Unit Ventilator
106 Classroom 470.0 31 840 19 19 Unit Ventilator
108 Classroom 11.0 0 828 18 0 Unit Ventilator
200 Classroom 89.0 5 696 15 5 Unit Ventilator
202 Classroom 231.0 15 696 15 15 Unit Ventilator
204 Classroom 301.0 20 696 15 15 Unit Ventilator
205 Classroom 304.0 20 672 15 15 Unit Ventilator
206 Classroom 200.0 13 696 15 13 Unit Ventilator
207 Classroom 191.0 12 696 15 12 Unit Ventilator
208 Classroom 125.0 8 696 15 8 Unit Ventilator
209 Classroom 178.0 11 384 8 8 Unit Ventilator
210 Classroom 200.0 13 690 15 13 Unit Ventilator
211 Classroom 262.0 17 851 19 17 Unit Ventilator
212 Classroom 280.0 18 875 19 18 Unit Ventilator
213 Classroom 0.0 0 875 19 0 Unit Ventilator
- AUDITORIUM 0.0 0 2,793 63 0 Air Handling Unit
- Cafeteria 862.0 57 2,343 53 53 Unit Ventilator
- GYM 812.0 54 3,478 79 54 Air Handling Unit
- MAIN OFFICE 0.0 0 552 12 0 Unit Ventilator
- Student Lounge 64.0 4 552 12 4 Unit Ventilator