Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
2 - 1,283 85 2800 63 63 Carrier / Perimeter Heater
3 - 500 33 1344 30 30 Carrier / Perimeter Heater
4 - 70 4 Yes 1332 30 30 Carrier / Perimeter Heater
5 - 146 9 Yes 527 11 11 Carrier / Perimeter Heater
6 - 38 2 Yes 744 16 16 Carrier / Perimeter Heater
7 - 70 4 Yes 912 20 20 Carrier / Perimeter Heater
8 - 317 21 460 10 10 Carrier / Perimeter Heater
9 - 311 20 480 10 10 Carrier / Perimeter Heater
10 - 291 19 504 11 11 Carrier / Perimeter Heater
11 - 290 19 504 11 11 Carrier / Perimeter Heater
12 - 292 19 744 16 16 Carrier / Perimeter Heater
13 - 210 14 760 17 14 Carrier / Perimeter Heater
14 - 244 16 760 17 16 Carrier / Perimeter Heater
15 - 224 14 760 17 14 Carrier / Perimeter Heater
16 - 225 15 760 17 15 Carrier / Perimeter Heater
17 - 260 17 760 17 17 Carrier / Perimeter Heater
18 - 304 20 760 17 17 Carrier / Perimeter Heater
19 - 0 0 Yes 760 17 17 Carrier / Perimeter Heater
20 - 356 23 760 17 17 Carrier / Perimeter Heater
21 - 271 18 760 17 17 Carrier / Perimeter Heater
22 - 282 18 760 17 17 Carrier / Perimeter Heater
23 - 275 18 760 17 17 Carrier / Perimeter Heater
24 - 0 0 Yes 760 17 17 Carrier / Perimeter Heater
25 - 192 12 Yes 1014 23 23 Carrier / Perimeter Heater
26 - 2,008 133 891 20 20 Air Handling Unit
27 - 416 27 620 14 14 Air Handling Unit
28 - 416 27 925 21 21 Air Handling Unit
31A - 0 0 Yes 190 4 4 Carrier / Perimeter Heater
31B Nurse's Office 0 0 Yes 196 4 4 Carrier / Perimeter Heater
32 - 0 0 Yes 272 6 6 Carrier / Perimeter Heater
33 - 396 26 1271 28 26 Carrier / Perimeter Heater
34 - 622 41 1470 33 33 Carrier / Perimeter Heater
35A - 265 17 720 16 16 Carrier / Perimeter Heater
35B - 222 14 1107 25 14 Carrier / Perimeter Heater
35C - 0 0 Yes 364 8 8 Carrier / Perimeter Heater
36 - 0 0 Yes 1288 29 29 Carrier / Perimeter Heater
37 - 235 15 600 13 13 Carrier / Perimeter Heater
38 - 257 17 600 13 13 Carrier / Perimeter Heater
39 - 88 5 Yes 462 10 10 Carrier / Perimeter Heater
40 - 115 7 Yes 472 10 10 Carrier / Perimeter Heater
41 - 235 15 702 15 15 Carrier / Perimeter Heater
46 Small Cafeteria 182 12 Yes 1347 30 30 Carrier / Perimeter Heater
47 - 75 5 Yes 315 7 7 Carrier / Perimeter Heater
48 - 90 6 Yes 817 18 18 Carrier / Perimeter Heater
103 - 290 19 840 19 19 Carrier / Perimeter Heater
104 - 310 20 840 19 19 Carrier / Perimeter Heater
105 - 410 27 810 18 18 Carrier / Perimeter Heater
106 - 300 20 868 19 19 Carrier / Perimeter Heater
107 - 530 35 850 19 19 Carrier / Perimeter Heater
108 - 489 32 840 19 19 Carrier / Perimeter Heater
109 - 40 2 Yes 840 19 19 Carrier / Perimeter Heater
110 - 550 36 840 19 19 Carrier / Perimeter Heater
101 - 430 28 1271 28 28 Carrier / Perimeter Heater
102A - 124 8 140 3 3 Carrier / Perimeter Heater
102B - 165 11 140 3 3 Carrier / Perimeter Heater
111A - 98 6 140 3 3 Carrier / Perimeter Heater
111B - 110 7 140 3 3 Carrier / Perimeter Heater
112 - 905 60 1271 28 28 Carrier / Perimeter Heater
- Auditorium 1,042 69 4087 92 69 Air Handling Unit
- Cafeteria 918 61 2720 61 61 Carrier / Perimeter Heater
- Computer Lab 320 21 Yes 943 21 21 Air Handling Unit
- Food Service "A & B" 0 0 Yes 1320 30 30 Carrier / Perimeter Heater
- Game Room 577 38 675 15 15 Carrier / Perimeter Heater
- GYM 174 11 3721 84 11 Air Handling Unit
- Kitchen 3,011 200 1191 27 27 Make-Up Air Unit
- Music Room 2,765 184 2040 46 46 Air Handling Unit
- Pool 0 0 7467 169 0 Air Handling Unit