Sheet Last Modified: 03-22-2021      
School:  Alexander Adaire Elementary School House Fan Abated/Final Report     Min 0
Vendor: Chadwick Devine Devine Retest Max 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. Average 1.5
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit cu-ft
8 ft ceiling
AUC Cert Level
- Auditorium 2,417 161 3,234 73 73 Air Handling Unit 25,872 6 2
- Gym/Cafeteria 322 21 3,432 78 21 Air Handling Unit 27,456 1 0
- Main Ofiice 161 10 468 10 10 Unit Ventilator 3,744 3 1
100 Classroom 452 30 960 21 21 Unit Ventilator 7,680 4 1
101 Classroom 480 32 960 21 21 Unit Ventilator 7,680 4 1
102 Classroom 509 33 960 21 21 Unit Ventilator 7,680 4 1
103 Classroom 409 27 960 21 21 Unit Ventilator 7,680 3 1
104 Classroom 514 34 960 21 21 Unit Ventilator 7,680 4 2
105 Classroom 523 34 960 21 21 Unit Ventilator 7,680 4 2
106 Classroom 125 8 Yes 782 17 17 Unit Ventilator 6,256 1 1
107 Classroom 272 18 380 8 8 Unit Ventilator 3,040 5 2
108 Faculty Room 0 0 104 2 0 Unit Ventilator 832 0 0
109 Classroom 485 32 1,470 33 32 Unit Ventilator 11,760 2 1
200 Classroom 546 36 912 20 20 Unit Ventilator 7,296 4 2
201 Classroom 607 40 912 20 20 Unit Ventilator 7,296 5 2
202 Classroom 613 40 936 21 21 Unit Ventilator 7,488 5 2
203 Library 593 39 1,080 24 24 Unit Ventilator 8,640 4 2
204 Classroom 480 32 912 20 20 Unit Ventilator 7,296 4 1
205 Classroom 182 12 Yes 960 21 21 Unit Ventilator 7,680 1 1
206 Classroom 317 21 984 22 21 Unit Ventilator 7,872 2 1
207 Classroom 798 53 456 10 10 Unit Ventilator 3,648 13 3
208 Classroom 577 38 960 21 21 Unit Ventilator 7,680 5 2
209 Classroom 458 30 960 21 21 Unit Ventilator 7,680 4 1
210 Classroom 519 34 960 21 21 Unit Ventilator 7,680 4 2
211 Classroom 534 35 1,008 22 22 Unit Ventilator 8,064 4 1
212 Classroom 1,568 104 960 21 21 Unit Ventilator 7,680 12 3
214 Classroom 340 22 960 21 21 Unit Ventilator 7,680 3 1
216 Classroom 617 41 456 10 10 Unit Ventilator 3,648 10 3
218 Classroom 424 28 782 17 17 Unit Ventilator 6,256 4 2
1.5
Sheet Last Modified: 03-24-2021    
School:  Ethan Allen Elementary-Middle School Min 0
Vendor: Devine  Devine Retest Max 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. Average 1.7
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit cu-ft
8 ft ceiling
AUC Cert Level
B1 Classroom 545 36 736 16 16 House Fan 5,888 6 2
B2 Classroom 708 47 352 8 8 House Fan 2,816 15 3
B3 Classroom 421 28 506 11 11 House Fan 4,048 6 2
B4 Classroom 453 30 452 10 10 House Fan 3,616 8 2
- Auditorium 2,183 145 3432 78 78 House Fan 27,456 5 2
- Boys Basement Restroom 130 8 383 8 8 AC Bathroom 3,064 3 1
- Girls Basement Restroom 787 52 524 11 11 AC Bathroom 4,192 11 3
101 Classroom 600 40 920 20 20 House Fan 7,360 5 2
102 Classroom 405 27 690 15 15 House Fan 5,520 4 2
103 Classroom 190 12 Yes 736 16 16 House Fan 5,888 2 1
104 Classroom 505 33 690 15 15 House Fan 5,520 5 2
105 Classroom 1,216 81 690 15 15 House Fan 5,520 13 3
106 Classroom 1,055 70 690 15 15 House Fan 5,520 11 3
107 Classroom 1,312 87 690 15 15 House Fan 5,520 14 3
108 Classroom 1,307 87 736 16 16 House Fan 5,888 13 3
109 Classroom 874 58 690 15 15 House Fan 5,520 10 2
110 Classroom 1,349 89 736 16 16 House Fan 5,888 14 3
210 Classroom 1,375 91 736 16 16 House Fan 5,888 14 3
202 Classroom 298 19 690 15 15 House Fan 5,520 3 1
203 Classroom 209 13 736 16 13 House Fan 5,888 2 1
204 Classroom 373 24 690 15 15 House Fan 5,520 4 2
205 Classroom 574 38 690 15 15 House Fan 5,520 6 2
206 Classroom 580 38 690 15 15 House Fan 5,520 6 2
207 Classroom 919 61 690 15 15 House Fan 5,520 10 2
208 Classroom 1,175 78 736 16 16 House Fan 5,888 12 3
209 Classroom 753 50 690 15 15 House Fan 5,520 8 2
210 Classroom 1,638 109 736 16 16 House Fan 5,888 17 3
214 Classroom 0 Yes 341 7 7 House Fan 2,728 0 0
301 Classroom 880 58 736 16 16 House Fan 5,888 9 2
302 Classroom 319 21 690 15 15 House Fan 5,520 3 1
303 Classroom 74 4 736 16 4 House Fan 5,888 1 0
304 Classroom 141 9 690 15 9 House Fan 5,520 2 1
305 Classroom 151 10 690 15 10 House Fan 5,520 2 1
306 Classroom 268 17 690 15 15 House Fan 5,520 3 1
307 Classroom 921 61 690 15 15 House Fan 5,520 10 3
308 Classroom 520 34 736 16 16 House Fan 5,888 5 2
309 Classroom 121 8 690 15 8 House Fan 5,520 1 1
310 Classroom 290 19 736 16 16 House Fan 5,888 3 1
314 Classroom 421 28 720 16 16 House Fan 5,760 4 2
- Main Office 0 Yes 309 7 7 House Fan 2,472 0 0
- Prinicipal Office 0 Yes 177 4 4 House Fan 1,416 0 0
- Nurse Office 0 Yes 186 4 4 House Fan 1,488 0 0
- Conselor Office 0 Yes 177 4 4 House Fan 1,416 0 0
- Pyschologist Office 0 Yes 108 2 2 House Fan 864 0 0
- Gym 0 Yes 3422 77 77 Hydroxyl Unit 27,376 0 0
Sheet Last Modified: 03-16-2021    
School:  Dr. Ethel Allen Elementary School Min 0
Vendor: Chadwick Chadwick Retest Max 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. Average 0.5
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit cu-ft
8 ft ceiling
AUC Cert Level
101-A Classroom 528 35 896 20 20 Unit Ventilator 7,168 4 2
101-B Classroom 100 6 1036 23 6 Unit Ventilator 8,288 1 0
102-A Classroom 70 4 1110 25 4 Unit Ventilator 8,880 0 0
102-B Classroom 485 32 1110 25 25 Unit Ventilator 8,880 3 1
102-C Classroom 0 0 1110 25 0 Unit Ventilator 8,880 0 0
102-D Classroom 0 1110 25 0 Unit Ventilator 8,880 0 0
103 Classroom 1233 82 Yes 2277 51 51 Unit Ventilator 18,216 4 2
103-A Classroom 76 5 0 0 Unit Ventilator 0
104 Classroom 419 27 1260 28 27 Unit Ventilator 10,080 2 1
105 Classroom 472 31 1260 28 28 Unit Ventilator 10,080 3 1
106 Classroom 152 10 1184 26 10 Unit Ventilator 9,472 1 0
107 Classroom 0 1260 28 0 Unit Ventilator 10,080 0 0
109 Classroom 172 11 Yes 1260 28 28 Unit Ventilator 10,080 1 1
110 Classroom 0 1036 23 0 Unit Ventilator 8,288 0 0
112 Classroom 29 1 1056 24 1 Unit Ventilator 8,448 0 0
113 Classroom 26 1 1056 24 1 Unit Ventilator 8,448 0 0
114 Classroom 380 25 1056 24 24 Unit Ventilator 8,448 3 1
200 Classroom 511 34 1500 34 34 Unit Ventilator 12,000 3 1
200C Classroom 0 0 Yes 784 17 17 Unit Ventilator 6,272 0 0
201B Classroom 0 840 19 0 Unit Ventilator 6,720 0 0
202 Classroom 367 24 983 22 22 Unit Ventilator 7,864 3 1
202 Classroom 0 0 0 Unit Ventilator 0
203A Classroom 0 1036 23 0 Unit Ventilator 8,288 0 0
203B Classroom 0 1036 23 0 Unit Ventilator 8,288 0 0
203C Classroom 0 1036 23 0 Unit Ventilator 8,288 0 0
203D Classroom 0 1036 23 0 Unit Ventilator 8,288 0 0
204 Classroom 525 35 980 22 22 Unit Ventilator 7,840 4 2
206 Classroom 194 12 1200 27 12 Unit Ventilator 9,600 1 1
206 Classroom 170 11 0 0 Unit Ventilator 0
207A Classroom 0 1260 28 0 Unit Ventilator 10,080 0 0
207B Classroom 0 1260 28 0 Unit Ventilator 10,080 0 0
208A Classroom 108 7 1260 28 7 Unit Ventilator 10,080 1 0
208B Classroom 0 1260 28 0 Unit Ventilator 10,080 0 0
208C Classroom 0 1260 28 0 Unit Ventilator 10,080 0 0
209 Classroom 907 60 0 0 Unit Ventilator 0
Sheet Last Modified: 04-29-2021      
School:  Add B. Anderson Elementary School   Min 0
Vendor: Devine Brothers Part 2     Max 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. Average 1.0
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit cu-ft
8 ft ceiling
AUC Cert Level
- Auditorium 5,840 389 2,589 58 58 Air Handling Unit 20,712 17 3
- Gym 2,392 159 2,200 50 50 Air Handling Unit 17,600 8 2
- Main Office 84 5 Yes 451 10 10 Unit Ventilator 3,608 1 1
- Principal's Office 0 Yes 350 7 7 Convector 2,800 0 0
- Nurse's Office 0 Yes 350 7 7 Convector 2,800 0 0
- Stage 2,534 168 1,008 22 22 Air Handling Unit 8,064 19 3
100 Classroom 281 18 467 10 10 Unit Ventilator 3,736 5 2
101 Classroom 32 2 355 8 2 Unit Ventilator 2,840 1 0
102 Classroom 102 6 Yes 540 12 12 Unit Ventilator 4,320 1 1
103 Classroom 40 2 Yes 628 14 14 Unit Ventilator 5,024 0 0
104 Classroom 287 19 395 8 8 Unit Ventilator 3,160 5 2
105 Classroom 295 19 521 11 11 Unit Ventilator 4,168 4 2
106 Classroom 290 19 446 10 10 Unit Ventilator 3,568 5 2
108 Classroom 283 18 405 9 9 Unit Ventilator 3,240 5 2
200 Classroom 82 5 Yes 476 10 10 Unit Ventilator 3,808 1 1
201 Classroom 128 8 Yes 627 14 14 Unit Ventilator 5,016 2 1
202 Classroom 408 27 576 13 13 Unit Ventilator 4,608 5 2
204 Classroom 323 21 683 15 15 Unit Ventilator 5,464 4 1
205 Classroom 80 5 Yes 658 14 14 Unit Ventilator 5,264 1 0
206 Classroom 329 21 637 14 14 Unit Ventilator 5,096 4 1
207 Classroom 82 5 Yes 587 13 13 Unit Ventilator 4,696 1 1
208 Classroom 129 8 Yes 720 16 16 Unit Ventilator 5,760 1 1
209 Classroom 305 20 629 14 14 Unit Ventilator 5,032 4 1
210 Classroom 41 2 241 5 2 Unit Ventilator 1,928 1 1
211 Classroom 56 3 385 8 3 Unit Ventilator 3,080 1 1
212 Classroom 319 21 603 13 13 Unit Ventilator 4,824 4 1
213 Classroom 49 3 Yes 290 6 6 Unit Ventilator 2,320 1 1
214 Classroom 112 7 Yes 741 16 16 Unit Ventilator 5,928 1 1
300 Classroom 35 2 Yes 947 21 21 Unit Ventilator 7,576 0 0
301 Classroom 63 4 Yes 900 20 20 Unit Ventilator 7,200 1 0
302 Classroom 87 5 Yes 588 13 13 Unit Ventilator 4,704 1 1
303 Classroom 85 5 Yes 571 12 12 Unit Ventilator 4,568 1 1
304 Classroom 293 19 431 9 9 Unit Ventilator 3,448 5 2
305 Classroom 58 3 Yes 504 11 11 Unit Ventilator 4,032 1 0
306 Classroom 286 19 415 9 9 Unit Ventilator 3,320 5 2
307 Classroom 97 6 Yes 501 11 11 Unit Ventilator 4,008 1 1
308 Classroom 79 5 Yes 686 15 15 Unit Ventilator 5,488 1 0
310 Classroom 106 7 Yes 592 13 13 Unit Ventilator 4,736 1 1
311 Classroom 53 3 Yes 441 10 10 Unit Ventilator 3,528 1 0
312 Classroom 18 1 Yes 465 10 10 Unit Ventilator 3,720 0 0
313 Classroom 72 4 Yes 463 10 10 Unit Ventilator 3,704 1 1
314 Classroom 61 4 Yes 533 12 12 Unit Ventilator 4,264 1 0
Sheet Last Modified: 04-30-2021    
School:  Chester A. Arthur Elementary School
Vendor: Devine Retest Devine 3rd Retest Min 0
  Devine 4th Retest Devine 5th Retest Max 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. Average 0.9
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit cu-ft
8 ft ceiling
AUC Cert Level
B001 Classroom 380 25 551 12 12 Unit Ventilator 4,408 5 2
B002 Classroom 0 0 100 2 0 N/A 800 0 0
100 Classroom 309 20 792 18 18 Unit Ventilator 6,336 3 1
102 Classroom 335 22 792 18 18 Unit Ventilator 6,336 3 1
104 Classroom 295 19 792 18 18 Unit Ventilator 6,336 3 1
106 Classroom 346 23 792 18 18 Unit Ventilator 6,336 3 1
107A Teacher's Lounge 0 Yes 448 10 10 Unit Ventilator 3,584 0 0
200 Classroom 335 22 792 18 18 Unit Ventilator 6,336 3 1
201 Classroom 304 20 364 8 8 Unit Ventilator 2,912 6 2
202 Classroom 320 21 792 18 18 Unit Ventilator 6,336 3 1
203 Classroom 299 19 864 19 19 Unit Ventilator 6,912 3 1
204 Classroom 333 22 792 18 18 Unit Ventilator 6,336 3 1
205 Classroom 374 24 864 19 19 Unit Ventilator 6,912 3 1
206 Classroom 280 18 792 18 18 Unit Ventilator 6,336 3 1
207 Classroom 341 22 864 19 19 Unit Ventilator 6,912 3 1
207A Classroom 0 Yes 425 9 9 Unit Ventilator 3,400 0 0
209 Classroom 311 20 792 18 18 Unit Ventilator 6,336 3 1
300 Classroom 293 19 857 19 19 Unit Ventilator 6,856 3 1
301 Classroom 273 18 364 8 8 Unit Ventilator 2,912 6 2
302 Classroom 355 23 857 19 19 Unit Ventilator 6,856 3 1
303 Classroom 328 21 864 19 19 Unit Ventilator 6,912 3 1
304 Classroom 350 23 792 18 18 Unit Ventilator 6,336 3 1
305 Classroom 274 18 900 20 18 Unit Ventilator 7,200 2 1
306 Classroom 304 20 792 18 18 Unit Ventilator 6,336 3 1
307 Classroom 350 23 864 19 19 Unit Ventilator 6,912 3 1
307A Classroom 0 Yes 425 9 9 Unit Ventilator 3,400 0 0
309 Classroom 331 22 792 18 18 Unit Ventilator 6,336 3 1
- Auditorium 753 50 4335 98 50 HV Unit 34,680 1 1
- Gym 2,466 164 3055 69 69 HV Unit 24,440 6 2
- IMC 383 25 1472 33 25 Unit Ventilator 11,776 2 1
- Resource Room/Storage 0 0 Yes 300 6 6 Unit Ventilator 2,400 0 0
- Main Office 401 26 1104 25 25 Unit Ventilator 8,832 3 1
- BE Office 63 4 240 5 4 Unit Ventilator 1,920 2 1
- Nurse Office 0 0 Yes 276 6 6 2,208 0 0
- Principal's Office 0 Yes 240 5 5 1,920 0 0
Sheet Last Modified: 04-26-2021    
School:  Alexander D. Bache Elementary School Bache Part 2
School:  W.E. Martin Building Martin Part 2 Min 0
Vendor: EMCOR Fluidics Max 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. Average 1.0
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit cu-ft
8 ft ceiling
AUC Cert Level
Bache Building
1 Classroom 274 18 768 17 17 Unit Ventilator 6,144 3 1
2 Classroom 295 19 768 17 17 Unit Ventilator 6,144 3 1
3 Classroom 305 20 768 17 17 Unit Ventilator 6,144 3 1
4 Classroom 289 19 768 17 17 Unit Ventilator 6,144 3 1
5 Classroom 330 22 768 17 17 Unit Ventilator 6,144 3 1
6 Classroom 273 18 768 17 17 Unit Ventilator 6,144 3 1
7 Classroom 312 20 528 12 12 Unit Ventilator 4,224 4 2
8 Classroom 406 27 768 17 17 Unit Ventilator 6,144 4 1
9 Classroom 455 30 768 17 17 Unit Ventilator 6,144 4 2
10 Classroom 400 26 768 17 17 Unit Ventilator 6,144 4 1
11 Classroom 346 23 768 17 17 Unit Ventilator 6,144 3 1
12 Classroom 388 25 768 17 17 Unit Ventilator 6,144 4 1
13 Teacher's Lounge 339 22 768 17 17 Unit Ventilator 6,144 3 1
14 Classroom 288 19 768 17 17 Unit Ventilator 6,144 3 1
15 Classroom 424 28 768 17 17 Unit Ventilator 6,144 4 2
16 Library 296 19 720 16 16 Unit Ventilator 5,760 3 1
17 Library 294 19 720 16 16 Unit Ventilator 5,760 3 1
18 Classroom 338 22 768 17 17 Unit Ventilator 6,144 3 1
19 Classroom 114 7 Yes 768 17 17 Unit Ventilator 6,144 1 1
20 Classroom 302 20 720 16 16 Unit Ventilator 5,760 3 1
21 Classroom 278 18 704 16 16 Unit Ventilator 5,632 3 1
22 Classroom 328 21 660 15 15 Unit Ventilator 5,280 4 1
23 Classroom 360 24 704 16 16 Unit Ventilator 5,632 4 1
24 Classroom 347 23 660 15 15 Unit Ventilator 5,280 4 1
25 Classroom 377 25 768 17 17 Unit Ventilator 6,144 4 1
26 Classroom 381 25 720 16 16 Unit Ventilator 5,760 4 1
27 Classroom 436 29 768 17 17 Unit Ventilator 6,144 4 2
- Cafeteria 0 0 Yes 1891 42 42 Unit Ventilator 15,128 0 0
Martin Building 0
101 Classroom 405 27 713 16 16 Unit Ventilator 5,704 4 2
102 Classroom 415 27 713 16 16 Unit Ventilator 5,704 4 2
103 Classroom 308 20 660 15 15 Unit Ventilator 5,280 4 1
104 Classroom 289 19 768 17 17 Unit Ventilator 6,144 3 1
105 Classroom 355 23 570 12 12 Unit Ventilator 4,560 5 2
106 Classroom 339 22 638 14 14 Unit Ventilator 5,104 4 1
107A Classroom 317 21 900 20 20 Unit Ventilator 7,200 3 1
107B Classroom 0 0 Yes 736 16 16 Unit Ventilator 5,888 0 0
108 Classroom 0 Yes 420 9 9 3,360 0 0
110 Classroom 518 34 782 17 17 Unit Ventilator 6,256 5 2
111 Classroom 354 23 667 15 15 Unit Ventilator 5,336 4 1
112 Classroom 328 21 690 15 15 Unit Ventilator 5,520 4 1
113 Classroom 389 25 1092 24 24 Unit Ventilator 8,736 3 1
114 Classroom 663 44 1036 23 23 Unit Ventilator 8,288 5 2
115 Classroom 422 28 814 18 18 Unit Ventilator 6,512 4 1
117 Classroom 536 35 782 17 17 Unit Ventilator 6,256 5 2
119 Classroom 480 32 713 16 16 Unit Ventilator 5,704 5 2
120 Classroom 277 18 690 15 15 Unit Ventilator 5,520 3 1
121 Classroom 0 0 Yes 720 16 16 Unit Ventilator 5,760 0 0
122 Classroom 0 0 744 16 0 Unit Ventilator 5,952 0 0
124 Classroom 273 18 759 17 17 Unit Ventilator 6,072 3 1
127 Classroom 0 Yes 690 15 15 N/A 5,520 0 0
128 Homemaking 288 19 768 17 17 Unit Ventilator 6,144 3 1
129 Classroom 280 18 500 11 11 Unit Ventilator 4,000 4 2
130 Classroom 321 21 644 14 14 Unit Ventilator 5,152 4 1
131 Classroom 283 18 638 14 14 Unit Ventilator 5,104 3 1
133 Classroom 337 22 403 9 9 Unit Ventilator 3,224 6 2
134 Counselor office 279 18 512 11 11 Unit Ventilator 4,096 4 2
135 Custodial supply room 0 0 512 11 0 Unit Ventilator 4,096 0 0
136 Classroom 276 18 403 9 9 Unit Ventilator 3,224 5 2
- Main Office 0 Yes 529 12 12 4,232 0 0
- Principals Office 0 Yes 221 5 5 1,768 0 0
- Nurses Office 0 Yes 308 7 7 2,464 0 0
- Auditorium 109 7 1702 38 7 Unit Ventilator 13,616 0 0
- Cafe 642 42 2451 55 42 Unit Ventilator 19,608 2 1
- Gym 364 24 1914 43 24 Unit Ventilator 15,312 1 1
- Hallway 157 10 0 0 Unit Ventilator 0
- Staff Lounge 0 525 11 0 4,200 0 0
Sheet Last Modified: 04-28-2021    
School:  Charles Carmine Antonio Baldi Middle School Min 0
Vendor: Goldner Max 4
Please visit https://bit.ly/3mA7rMY for more information on how to read this report. Average 0.8
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit cu-ft
8 ft ceiling
AUC Cert Level
22 Classroom 903 60 799 18 18 Air Handling Unit 6,392 8 2
23 Classroom 552 36 844 19 19 Unit Ventilator 6,752 5 2
24 Classroom 670 44 853 19 19 Unit Ventilator 6,824 6 2
26B Classroom 383 25 818 18 18 Unit Ventilator 6,544 4 1
27A Classroom 444 29 818 18 18 Unit Ventilator 6,544 4 2
28 Science Lab 1347 89 1213 27 27 Unit Ventilator 9,704 8 2
29 Room 733 48 1280 29 29 Unit Ventilator 10,240 4 2
30 Science Lab 1295 86 1213 27 27 Unit Ventilator 9,704 8 2
31A Classroom 696 46 831 18 18 Unit Ventilator 6,648 6 2
31B Classroom 772 51 818 18 18 Unit Ventilator 6,544 7 2
32A Classroom 1064 70 852 19 19 Unit Ventilator 6,816 9 2
32B Classroom 395 26 818 18 18 Unit Ventilator 6,544 4 1
33A Classroom 1195 79 853 19 19 Unit Ventilator 6,824 11 3
34a Classroom 310 20 844 19 19 Unit Ventilator 6,752 3 1
34b Classroom 232 15 799 18 15 Unit Ventilator 6,392 2 1
35 Science Lab 433 28 1227 27 27 Unit Ventilator 9,816 3 1
35 Lounge 133 8 435 9 8 Unit Ventilator 3,480 2 1
38 Lounge 0 0 435 9 0 Unit Ventilator 3,480 0 0
39 Lounge 0 0 435 9 0 Unit Ventilator 3,480 0 0
40 Seminar Room 1766 117 411 9 9 Unit Ventilator 3,288 32 4
40 Classroom 353 23 411 9 9 Unit Ventilator 3,288 6 2
42 SGI Room 205 13 435 9 9 Unit Ventilator 3,480 4 1
43 SGI Room 226 15 485 11 11 Unit Ventilator 3,880 3 1
44A Classroom 243 16 854 19 16 Unit Ventilator 6,832 2 1
44B Classroom 194 12 847 19 12 Unit Ventilator 6,776 2 1
45 Teachers IPO Room 0 0 980 22 0 Unit Ventilator 7,840 0 0
46 Conf. Room 56 3 980 22 3 Unit Ventilator 7,840 0 0
46 IPO Materials Room 76 5 980 22 5 Unit Ventilator 7,840 1 0
47 Faculty Lounge Room 0 0 435 9 0 Unit Ventilator 3,480 0 0
47a Classroom 195 13 841 19 13 Air Handling Unit 6,728 2 1
47b Classroom 191 12 844 19 12 Air Handling Unit 6,752 2 1
48 Science Lab 858 57 1227 27 27 Unit Ventilator 9,816 5 2
B4 Room 0 853 19 0 6,824 0 0
G5 Room 0 853 19 0 6,824 0 0
G100 Classroom 0 Yes 565 12 12 4,520 0 0
G101 Classroom 0 1227 27 0 9,816 0 0
G102 Classroom 0 799 18 0 6,392 0 0
G103 Classroom 0 844 19 0 6,752 0 0
G104 Classroom 0 853 19 0 6,824 0 0
G105 Classroom 0 853 19 0 6,824 0 0
Y3 Room 0 818 18 0 6,544 0 0
Y5 Room 0 852 19 0 6,816 0 0
Y104 Room 0 818 18 0 6,544 0 0
Y105 Room 0 852 19 0 6,816 0 0
100 Common Area 0 0 3443 78 0 Unit Ventilator 27,544 0 0
127 Art Lab 0 0 Yes 2279 51 51 Unit Ventilator 18,232 0 0
128 Art Lab 0 0 Yes 2184 49 49 Unit Ventilator 17,472 0 0
129 Faculty Dining Room 0 0 435 9 0 Unit Ventilator 3,480 0 0
137 Classroom 1440 96 818 18 18 Unit Ventilator 6,544 13 3
138 Classroom 1218 81 831 18 18 Unit Ventilator 6,648 11 3
139 Lab 2473 164 1213 27 27 Unit Ventilator 9,704 15 3
140 Large Group Room 1508 100 1280 29 29 Unit Ventilator 10,240 9 2
141 Science Lab 1291 86 1213 27 27 Unit Ventilator 9,704 8 2
142 Classroom 1844 122 831 18 18 Unit Ventilator 6,648 17 3
143 Classroom 1560 104 818 18 18 Unit Ventilator 6,544 14 3
144 Classroom 391 26 818 18 18 Unit Ventilator 6,544 4 1
145 Classroom 619 41 852 19 19 Unit Ventilator 6,816 5 2
146 Classroom 265 17 853 19 17 Unit Ventilator 6,824 2 1
147 Classroom 562 37 853 19 19 Unit Ventilator 6,824 5 2
148 Classroom 592 39 844 19 19 Unit Ventilator 6,752 5 2
149 Classroom 385 25 799 18 18 Unit Ventilator 6,392 4 1
150 Science Lab 611 40 1233 28 28 Unit Ventilator 9,864 4 1
200 Classroom 0 Yes 566 12 12 4,528 0 0
200 Office Office 0 Yes 374 8 8 2,992 0 0
201 Classroom 0 Yes 1085 24 24 8,680 0 0
202 Classroom 0 Yes 893 20 20 7,144 0 0
203 Classroom 0 1029 23 0 8,232 0 0
205 Classroom 0 Yes 1575 35 35 12,600 0 0
211 Classroom 0 Yes 930 21 21 7,440 0 0
212 Classroom 0 Yes 600 13 13 4,800 0 0
213 Classroom 0 Yes 870 19 19 6,960 0 0
214 Classroom 0 Yes 1326 30 30 10,608 0 0
215 Classroom 0 980 22 0 7,840 0 0
225 Library 0 0 1230 27 0 Unit Ventilator 9,840 0 0
226 Study Area 0 0 3510 79 0 Unit Ventilator 28,080 0 0
227 Computer Lab 0 0 980 22 0 Unit Ventilator 7,840 0 0
228 Mech. Room 0 0 411 9 0 Unit Ventilator 3,288 0 0
155A Teachers Office 0 0 948 21 0 Unit Ventilator 7,584 0 0
156A Teachers Office 0 0 948 21 0 Unit Ventilator 7,584 0 0
225A Office 0 0 948 21 0 Unit Ventilator 7,584 0 0
225B Office 0 0 1029 23 0 Unit Ventilator 8,232 0 0
225C Storage 0 0 1000 22 0 Unit Ventilator 8,000 0 0
225D Office 0 0 299 6 0 Unit Ventilator 2,392 0 0
Computer Lab A Lab 0 2640 60 0 21,120 0 0
Computer Lab B Lab 0 2067 46 0 16,536 0 0
Computer Lab C Lab 0 2262 51 0 18,096 0 0
Main Office Office 0 Yes 875 19 19 7,000 0 0
Principal Office 0 Yes 270 6 6 Mobile Mini 2,160 0 0
Vice Principal Office 0 Yes 144 3 3 Mobile Mini 1,152 0 0
Vice Principal Office 0 Yes 144 3 3 Mobile Mini 1,152 0 0
Vice Principal Office 0 Yes 153 3 3 Mobile Mini 1,224 0 0
- Boys Gym 0 0 5418 123 0 Unit Ventilator 43,344 0 0
- Boys Locker Room 0 0 1824 41 0 Unit Ventilator 14,592 0 0
- Corridor/Hall 1107 73 435 9 9 Unit Ventilator 3,480 19 3
Cafeteria 1 Dining 0 0 2179 49 0 Unit Ventilator 17,432 0 0
Cafeteria 2 Dining 0 2179 49 0 17,432 0 0
Cafeteria 3 Dining 0 2179 49 0 17,432 0 0
Cafeteria 4 Dining 0 2179 49 0 17,432 0 0
- Girls Gym 4087 272 Yes 5418 123 123 Air Handling Unit 43,344 6 2
- IPO Bathrooms 129 8 411 9 8 Unit Ventilator 3,288 2 1
- IPO Office 1 0 435 9 0 Unit Ventilator 3,480 0 0
- IPO Office 1 40 2 435 9 2 Unit Ventilator 3,480 1 0
- IPO Office 3 46 3 435 9 3 Unit Ventilator 3,480 1 0
- Lounge 104 6 485 11 6 Unit Ventilator 3,880 2 1
Sheet Last Modified: 03-12-2021      
School:  New Commodore John Barry Elementary School
Vendor: EMCOR Exhaust  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.            
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit            
100 Room 0 Yes 425 9 9 Rooftop Unit
104 Room 116 7 Yes 1008 22 22 Rooftop Unit
105 Room 133 8 Yes 1134 25 25 Rooftop Unit
106 Room 0 Yes 1140 25 25 Rooftop Unit
107 Room 308 20 1118 25 20 Rooftop Unit
108 Room 303 20 1140 25 20 Rooftop Unit
109 Room 1254 83 2100 47 47 Rooftop Unit
116 Room 125 8 0 0 Rooftop Unit
202 Room 147 9 Yes 551 12 12 Rooftop Unit
203 Room 148 9 Yes 551 12 12 Rooftop Unit
204 Room 139 9 Yes 418 9 9 Rooftop Unit
205 Room 202 13 Yes 551 12 12 Rooftop Unit
206 Room 145 9 Yes 728 16 16 Rooftop Unit
207 Room 185 12 Yes 728 16 16 Rooftop Unit
208 Room 139 9 Yes 728 16 16 Rooftop Unit
209 Room 313 20 728 16 16 Rooftop Unit
210 Room 272 18 630 14 14 Rooftop Unit
211 Room 192 12 756 17 12 Rooftop Unit
212 Room 154 10 Yes 900 20 20 Rooftop Unit
213 Room 130 8 Yes 900 20 20 Rooftop Unit
214 Room 268 17 812 18 17 Rooftop Unit
215 Room 219 14 Yes 756 17 17 Rooftop Unit
216 Room 223 14 Yes 756 17 17 Rooftop Unit
301 Room 210 14 630 14 14 Rooftop Unit
302A Room 0 104 2 0 Rooftop Unit
302B Room 0 117 2 0 Rooftop Unit
302C Room 0 104 2 0 Rooftop Unit
303 Room 99 6 651 14 6 Rooftop Unit
304 Room 0 110 2 0 Rooftop Unit
305 Room 237 15 756 17 15 Rooftop Unit
306 Room 156 10 756 17 10 Rooftop Unit
307 Room 265 17 784 17 17 Rooftop Unit
308 Room 192 12 Yes 864 19 19 Rooftop Unit
309 Room 208 13 810 18 13 Rooftop Unit
310 Room 296 19 810 18 18 Rooftop Unit
311 Room 249 16 812 18 16 Rooftop Unit
312 Room 210 14 840 19 14 Rooftop Unit
313 Room 96 6 810 18 6 Rooftop Unit
314 Room 219 14 810 18 14 Rooftop Unit
315 Room 105 7 812 18 7 Rooftop Unit
316 Room 143 9 812 18 9 Rooftop Unit
320 Room 212 14 620 14 14 Rooftop Unit
323 Room 230 15 620 14 14 Rooftop Unit
401 Room 215 14 Yes 1260 28 28 Rooftop Unit
403A Room 0 240 5 0 Rooftop Unit
403B Room 0 210 4 0 Rooftop Unit
403C Room 0 240 5 0 Rooftop Unit
404 Room 0 Yes 1024 23 23 Rooftop Unit
405 Room 382 25 1476 33 25 Rooftop Unit
406 Room 0 1462 33 0 Rooftop Unit
407 Room 0 1054 23 0 Rooftop Unit
408 Room 561 37 1280 29 29 Rooftop Unit
409 Room 213 14 1160 26 14 Rooftop Unit
- Café 593 39 4,800 109 39 Rooftop Unit
- Gym 0 Yes 6240 141 141 Rooftop Unit
- Library 0 Yes 1961 44 44 Rooftop Unit
- Main Office 0 924 21 0 Rooftop Unit
- Nurse's Office 0 143 3 0 Rooftop Unit
Sheet Last Modified: 03-16-2021        
School:  Clara Barton      
Vendor:        
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B7 Classroom 0 0 Yes 601 13 13 House Fan
B8 Classroom 0 0 Yes 848 19 19 House Fan
B10 Classroom 0 0 686 15 0 House Fan
B11 Classroom 0 0 806 18 0 House Fan
100 Classroom 0 0 Yes 742 16 16 House Fan
101 Classroom 0 0 Yes 650 14 14 House Fan
102 Office 0 0 Yes 452 10 10 House Fan
102 A Classroom 0 0 70 1 0 House Fan
102 B Office 0 0 122 2 0 House Fan
103 C Office 0 0 90 2 0 House Fan
103 Classroom 0 0 Yes 627 14 14 House Fan
104 Library 0 0 Yes 645 14 14 House Fan
105 Library 0 0 Yes 658 14 14 House Fan
106 Library 0 0 Yes 653 14 14 House Fan
107 Classroom 0 0 Yes 632 14 14 House Fan
108 Classroom 0 0 Yes 640 14 14 House Fan
109 Classroom 0 0 Yes 694 15 15 House Fan
110 Classroom 0 0 Yes 683 15 15 House Fan
111 Classroom 0 0 Yes 650 14 14 House Fan
112 Nurse's Office 0 0 Yes 118 2 2 House Fan
- Main Office 0 0 Yes 297 6 6 House Fan
- Principal's Office 0 0 Yes 159 3 3 House Fan
200 Classroom 0 0 Yes 663 15 15 House Fan
200 A Office 0 0 Yes 226 5 5 House Fan
200 B Classroom 0 0 Yes 158 3 3 House Fan
201 Classroom 0 0 Yes 635 14 14 House Fan
202 Classroom 0 0 Yes 713 16 16 House Fan
203 Classroom 0 0 Yes 645 14 14 House Fan
204 Classroom 0 0 Yes 624 14 14 House Fan
205 Classroom 0 0 Yes 624 14 14 House Fan
206 Classroom 0 0 Yes 653 14 14 House Fan
207 Classroom 0 0 Yes 664 15 15 House Fan
208 Classroom 0 0 Yes 638 14 14 House Fan
209 Classroom 0 0 Yes 662 15 15 House Fan
210 Classroom 0 0 Yes 694 15 15 House Fan
211 Classroom 0 0 Yes 616 14 14 House Fan
211 A Office 0 0 115 2 0 House Fan
- Teacher Lounge 0 0 Yes 340 7 7 House Fan
215 Classroom 0 Yes 345 7 7 house Fan
300 Classroom 0 0 Yes 640 14 14 House Fan
300A Office 0 Yes 264 6 6 House Fan
301 Classroom 0 0 Yes 668 15 15 House Fan
301 A Office 0 0 203 4 0 House Fan
302 Classroom 0 0 Yes 639 14 14 House Fan
303 Classroom 0 0 Yes 692 15 15 House Fan
304 Classroom 0 0 Yes 627 14 14 House Fan
305 Classroom 0 0 Yes 655 14 14 House Fan
306 Classroom 0 0 Yes 664 15 15 House Fan
307 Classroom 0 0 Yes 642 14 14 House Fan
308 Classroom 0 0 Yes 663 15 15 House Fan
309 Classroom 0 0 Yes 605 13 13 House Fan
310 Classroom 0 0 Yes 673 15 15 House Fan
311 Classroom 0 0 Yes 660 15 15 House Fan
312 Classroom 0 0 634 14 0 House Fan
312 A Office 0 0 112 2 0 House Fan
- Counselor Office 0 Yes 152 3 3 House Fan
- Gym 0 0 Yes 3,436 78 78 N/A
- Kitchen 0 0 Yes 1,140 25 25 House Fan
- Cafeteria 0 0 Yes 1,478 33 33 House Fan
Sheet Last Modified: 04-26-2021    
School:  John Bartram High School
Vendor: Devine Brothers Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 590 39 1196 27 27 Unit Ventilator
102 Classroom 359 23 851 19 19 Unit Ventilator
103 Classroom 759 50 828 18 18 Unit Ventilator
104 Classroom 646 43 920 20 20 Unit Ventilator
105 Classroom 582 38 851 19 19 Unit Ventilator
106 Classroom 696 46 989 22 22 Unit Ventilator
107 Classroom 980 65 946 21 21 Unit Ventilator
108 Classroom 575 38 1012 23 23 Unit Ventilator
110 Office 0 0 238 5 0 Unit Ventilator
111 Classroom 418 27 805 18 18 Unit Ventilator
112 Room 416 27 920 20 20 Unit Ventilator
113 Classroom 416 27 690 15 15 Unit Ventilator
115 Classroom 343 22 690 15 15 Unit Ventilator
116 Classroom 467 31 1357 30 30 Unit Ventilator
117 Classroom 352 23 690 15 15 Unit Ventilator
118 Classroom 325 21 690 15 15 Unit Ventilator
119 Classroom 346 23 690 15 15 Unit Ventilator
120 Classroom 0 0 690 15 0 Unit Ventilator
121 Office 0 0 Yes 227 5 5 Unit Ventilator
123 Room 498 33 1242 28 28 Unit Ventilator
124 Office 0 0 Yes 309 7 7 Unit Ventilator
124A Office 0 0 Yes 218 4 4 Unit Ventilator
125 Room 356 23 690 15 15 Unit Ventilator
126 Room 339 22 276 6 6 Unit Ventilator
127 Room 349 23 644 14 14 Unit Ventilator
127a Room 331 22 345 7 7 Unit Ventilator
128 Office 0 0 230 5 0 Unit Ventilator
130 Room 288 19 375 8 8 Unit Ventilator
130A Office 0 0 236 5 0 Unit Ventilator
131 Office 0 0 Yes 237 5 5 Unit Ventilator
133 Office 0 0 Yes 333 7 7 Unit Ventilator
134 Main Office 593 39 1656 37 37 Unit Ventilator
201 Classroom 617 41 989 22 22 Unit Ventilator
202 Classroom 282 18 805 18 18 Unit Ventilator
203 Classroom 632 42 989 22 22 Unit Ventilator
204 Classroom 309 20 690 15 15 Unit Ventilator
205 Classroom 516 34 989 22 22 Unit Ventilator
206 Classroom 324 21 690 15 15 Unit Ventilator
207 Classroom 363 24 989 22 22 Unit Ventilator
208 Classroom 291 19 690 15 15 Unit Ventilator
209 Classroom 0 0 Yes 309 7 7 Unit Ventilator
210 Classroom 297 19 690 15 15 Unit Ventilator
211 Room 0 0 Yes 321 7 7 Unit Ventilator
211A copy Room 0 0 227 5 0 Unit Ventilator
214 Classroom 370 24 690 15 15 Unit Ventilator
215 Classroom 337 22 690 15 15 Unit Ventilator
216 Classroom 327 21 690 15 15 Unit Ventilator
217 Classroom 282 18 690 15 15 Unit Ventilator
218 Classroom 563 37 690 15 15 Unit Ventilator
219 Office 0 0 Yes 272 6 6 Unit Ventilator
220A Office 0 0 Yes 169 3 3 Unit Ventilator
221 Classroom 97 6 Yes 851 19 19 Unit Ventilator
222 Classroom 320 21 851 19 19 Unit Ventilator
223 Classroom 329 21 690 15 15 Unit Ventilator
224 Classroom 302 20 690 15 15 Unit Ventilator
225 Classroom 437 29 690 15 15 Unit Ventilator
226 Classroom 315 21 690 15 15 Unit Ventilator
227 Classroom 299 19 690 15 15 Unit Ventilator
228 Classroom 302 20 690 15 15 Unit Ventilator
229 Classroom 407 27 690 15 15 Unit Ventilator
230 Classroom 290 19 690 15 15 Unit Ventilator
231 Classroom 331 22 322 7 7 Unit Ventilator
232 Classroom 0 0 Yes 690 15 15 Unit Ventilator
234 Office 0 0 Yes 298 6 6 Unit Ventilator
236 Office 0 0 Yes 299 6 6 Unit Ventilator
236A Copy room 0 0 203 4 0 Unit Ventilator
301 Classroom 0 816 18 0 Air Handling Unit
302 Classroom 0 816 18 0 Air Handling Unit
305 Classroom 0 1000 22 0 Air Handling Unit
306 Classroom 0 136 3 0 Air Handling Unit
307 Classroom 0 696 15 0 Air Handling Unit
309 Classroom 0 225 5 0 Air Handling Unit
313 Faculty 309 20 832 18 18 Unit Ventilator
320 Classroom 618 41 1080 24 24 Unit Ventilator
321 Classroom 574 38 1100 25 25 Unit Ventilator
324 Classroom 553 36 945 21 21 Unit Ventilator
325 Classroom 394 26 1080 24 24 Unit Ventilator
328 Room 0 0 Yes 169 3 3 Unit Ventilator
331 Classroom 351 23 805 18 18 Unit Ventilator
332 Classroom 361 24 1081 24 24 Unit Ventilator
333 Classroom 321 21 690 15 15 Unit Ventilator
334 Classroom 284 18 690 15 15 Unit Ventilator
335 Classroom 286 19 667 15 15 Unit Ventilator
336 Classroom 295 19 690 15 15 Unit Ventilator
337 Classroom 86 5 Yes 690 15 15 Unit Ventilator
338 Classroom 280 18 667 15 15 Unit Ventilator
339 Classroom 366 24 506 11 11 Unit Ventilator
340 Classroom 274 18 484 11 11 Unit Ventilator
341 Classroom 356 23 484 11 11 Unit Ventilator
342 Classroom 289 19 529 12 12 Unit Ventilator
344 Room 0 0 Yes 233 5 5 Unit Ventilator
346 Classroom 291 19 675 15 15 Unit Ventilator
B12 Room 0 0 383 8 0 Unit Ventilator
B13 BE Office 0 0 238 5 0 Unit Ventilator
B17 Room 0 0 209 4 0 Unit Ventilator
Bc Room 0 0 Yes 244 5 5 Unit Ventilator
C1 Classroom 398 26 1000 22 22 Unit Ventilator
C2 Classroom 0 0 1000 22 0 Unit Ventilator
C3 Classroom 1,212 80 1000 22 22 Unit Ventilator
C4 Classroom 0 0 1000 22 0 Unit Ventilator
C5 Classroom 0 0 1000 22 0 Unit Ventilator
C7 Classroom 881 58 968 22 22 Unit Ventilator
C7A Classroom 0 0 909 20 0 Unit Ventilator
- School police 0 0 Yes 192 4 4 Unit Ventilator
- 3rd Floor C Wing 0 0 0 0 Air Handling Unit
- Auditorium 0 0 11625 264 0 Air Handling Unit
- Boys Gym 5,931 395 5280 120 120 Air Handling Unit
- Library 866 57 4526 102 57 Unit Ventilator
- Corridor 0 0 0 0 Unit Ventilator
- Girls Gym 6,806 453 5280 120 120 Air Handling Unit
- Nurse Area 255 17 936 21 17 Unit Ventilator
- Cafeteria 0 0 Yes 6262 142 142 Unit Ventilator
Sheet Last Modified: 04-05-2021    
School:  Mary McLeod Bethune School
Vendor: Capital Devine Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 300.0 20 1350 30 20 Unit Ventilator
2 Classroom 278.0 18 1350 30 18 Unit Ventilator
3 Classroom 395.0 26 1350 30 26 Unit Ventilator
4 Classroom 425.0 28 1296 29 28 Unit Ventilator
5 Classroom 314.0 20 1296 29 20 Unit Ventilator
100 Classroom 614.0 40 960 21 21 Unit Ventilator
101 Classroom 597.0 39 1024 23 23 Unit Ventilator
101A Instructional Storage 0 0 0 0 HUV
102 Classroom 560.0 37 690 15 15 Unit Ventilator
103 Classroom 555.0 37 690 15 15 Unit Ventilator
104 Classroom 575.0 38 690 15 15 Unit Ventilator
105 Classroom 618.0 41 690 15 15 Unit Ventilator
106 Class Area 163 10 625 14 10 Unit Ventilator
106A IT room 280.0 18 304 6 6 Unit Ventilator
107 Class Area 155 10 1050 23 10 Unit Ventilator
108 Class Area 141 9 1050 23 9 Unit Ventilator
109 Class Area 143 9 625 14 9 Unit Ventilator
110 Class Area 159 10 690 15 10 Unit Ventilator
111 Class Area 164 10 690 15 10 Unit Ventilator
112 Class Area 142 9 690 15 9 Unit Ventilator
113 Class Area 149 9 690 15 9 Unit Ventilator
114 Class Area 137 9 690 15 9 Unit Ventilator
114A Team Planning 0 0 360 8 0 HUV
115 Class 141 9 690 15 9 Unit Ventilator
118D Main Office 0.0 0 150 3 0 Unit Ventilator
119A Instructional Storage 0 0 0 0 HUV
119B Building Engineer's Office 305 20 450 10 10 Unit Ventilator
120 Instructional Materials Center 303 20 2520 57 20 Unit Ventilator
122 Main Office 394 26 600 13 13 Unit Ventilator
122C Main Office 301 20 130 2 2 Unit Ventilator
122D Principal's Office 383.0 25 216 4 4 Unit Ventilator
123 Teacher's Dining 355.0 23 594 13 13 Unit Ventilator
123A Teacher's Lounge 298.0 19 270 6 6 Unit Ventilator
127 Corridor 0 0 0 0 HUV
150 Storage 163 10 360 8 8 Unit Ventilator
153 Corridor 0 0 0 0 HUV
165 Gym Office  152 10 130 2 2 Unit Ventilator
184 Examination 153 10 130 2 2 Unit Ventilator
200 Classroom 622.0 41 1350 30 30 Unit Ventilator
201 Classroom 530 35 690 15 15 Unit Ventilator
201A Instructional Storage 0 0 0 0 HUV
202 Classroom 519.0 34 690 15 15 Unit Ventilator
203 Classroom 434 28 690 15 15 Unit Ventilator
204 Classroom 550.0 36 690 15 15 Unit Ventilator
205 Classroom 436.0 29 690 15 15 Unit Ventilator
206 Classroom 500.0 33 690 15 15 Unit Ventilator
206A Team Planning 149 9 270 6 6 Unit Ventilator
207 Classroom 327.0 21 945 21 21 Unit Ventilator
208 Corridor 0 0 0 0 HUV
208 Classroom 509.0 33 690 15 15 Unit Ventilator
209 Classroom 552 36 625 14 14 Unit Ventilator
210 Classroom 694.0 46 690 15 15 Unit Ventilator
211 Classroom 531.0 35 690 15 15 Unit Ventilator
212 Classroom 379.0 25 690 15 15 Unit Ventilator
213 Classroom 688.0 45 690 15 15 Unit Ventilator
214 Classroom 382.0 25 690 15 15 Unit Ventilator
214A Instructional Storage 0 0 0 0 HUV
215 Classroom 370.0 24 840 19 19 Unit Ventilator
216 Classroom 388 25 805 18 18 Unit Ventilator
217 Classroom 413.0 27 792 18 18 Unit Ventilator
218 Classroom 328.0 21 625 14 14 Unit Ventilator
218C Classroom 286.0 19 960 21 19 Unit Ventilator
219 Classroom 862 57 1800 40 40 Unit Ventilator
220 Classroom 980 65 1350 30 30 Unit Ventilator
221 Classroom 342 22 625 14 14 Unit Ventilator
234 Corridor 0 0 0 0 HUV
244 Counselor 0 0 0 0 HUV
- Nurse's Office 279 18 150 3 3 Unit Ventilator
Sheet Last Modified: 03-18-2021    
School:  James G. Blaine Elementary School
Vendor: Devine Brothers Retest 2nd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Gym / Cafe. 1104 73 3749 85 73 Air Handling Unit
- Auditorium 577 38 3161 71 38 Air Handling Unit
100 Classroom 437 29 1415 32 29 Unit Ventilator
101 Classroom 684 45 1476 33 33 Unit Ventilator
102 Classroom 625 41 1460 33 33 Unit Ventilator
103 Classroom 461 30 1465 33 30 Unit Ventilator
104 Classroom 319 21 856 19 19 Unit Ventilator
105 Classroom 306 20 655 14 14 Unit Ventilator
106 Classroom 452 30 921 20 20 Unit Ventilator
107 Classroom 274 18 970 22 18 Unit Ventilator
108 Custodial 251 16 835 18 16 Unit Ventilator
110 Nurse 0 Yes 452 10 10 Unit Ventilator
200 Classroom 297 19 947 21 19 Unit Ventilator
201 Classroom 246 16 649 14 14 Unit Ventilator
202 Classroom 414 27 936 21 21 Unit Ventilator
203 Classroom 230 15 937 21 15 Unit Ventilator
204 Classroom 359 23 958 21 21 Unit Ventilator
205 Classroom 286 19 937 21 19 Unit Ventilator
206 Classroom 447 29 952 21 21 Unit Ventilator
207 Classroom 291 19 956 21 19 Unit Ventilator
208 Classroom 314 20 968 22 20 Unit Ventilator
209 Classroom 349 23 975 22 22 Unit Ventilator
210 Classroom 236 15 931 21 15 Unit Ventilator
211 Classroom 287 19 982 22 19 Unit Ventilator
212 Classroom 362 24 953 21 21 Unit Ventilator
213 Classroom 296 19 957 21 19 Unit Ventilator
214 Classroom 378 25 956 21 21 Unit Ventilator
215 Classroom 288 19 603 13 13 Unit Ventilator
216 Classroom 406 27 942 21 21 Unit Ventilator
217 Classroom 407 27 656 14 14 Unit Ventilator
300 Classroom 332 22 956 21 21 Unit Ventilator
301 Classroom 333 22 601 13 13 Unit Ventilator
302 Classroom 249 16 864 19 16 Unit Ventilator
303 Classroom 341 22 859 19 19 Unit Ventilator
304 Classroom 270 18 863 19 18 Unit Ventilator
305 Classroom 286 19 862 19 19 Unit Ventilator
306 Classroom 254 16 861 19 16 Unit Ventilator
307 Classroom 348 23 865 19 19 Unit Ventilator
308 Classroom 334 22 859 19 19 Unit Ventilator
309 Classroom 287 19 972 22 19 Unit Ventilator
310 Classroom 324 21 852 19 19 Unit Ventilator
311 Classroom 306 20 958 21 20 Unit Ventilator
312 Classroom 483 32 950 21 21 Unit Ventilator
313 Classroom 460 30 944 21 21 Unit Ventilator
314 Classroom 238 15 951 21 15 Unit Ventilator
315 Classroom 359 23 667 15 15 Unit Ventilator
316 Classroom 315 21 952 21 21 Unit Ventilator
317 Classroom 288 19 651 14 14 Unit Ventilator
- Main Office 0 Yes 1235 28 28 Unit Ventilator
- Principal 0 Yes 361 8 8 Unit Ventilator
Sheet Last Modified: 04-20-2021          
School:  Randolph Blankenburg Elementary-Middle School House fan Abated  
Vendor: Devine Devine Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
K-1 Classroom 906 60 704 16 16 House Fan
K-4 Classroom 828 55 704 16 16 House Fan
B27 Classroom 517 34 1047 23 23 House Fan
10A Vice Principal 0 0 Yes 176 4 4 N/A
29 Classroom 594 39 704 16 16 House Fan
30 Classroom 930 62 836 19 19 House Fan
101 Classroom 890 59 704 16 16 House Fan
102 Classroom 63 4 Yes 704 16 16 House Fan
103 Classroom 954 63 704 16 16 House Fan
105 Classroom 907 60 704 16 16 House Fan
106 Classroom 988 65 704 16 16 House Fan
107 Classroom 959 63 704 16 16 House Fan
208 Classroom 620 41 704 16 16 House Fan
208A Nurse's Office 0 0 176 4 0 N/A
209 Classroom 695 46 704 16 16 House Fan
210 Classroom 930 62 704 16 16 House Fan
211 Classroom 887 59 704 16 16 House Fan
212 Classroom 751 50 704 16 16 House Fan
213 Classroom 955 63 704 16 16 House Fan
214 Classroom 950 63 704 16 16 House Fan
316 Classroom 0 0 Yes 880 20 20 House Fan
317 Classroom 361 24 484 11 11 House Fan
318 Classroom 588 39 704 16 16 House Fan
319 Classroom 341 22 704 16 16 House Fan
320 Classroom 483 32 704 16 16 House Fan
321 Classroom 743 49 704 16 16 House Fan
322 Classroom 877 58 704 16 16 House Fan
323 Classroom 642 42 748 17 17 House Fan
324 Classroom 818 54 704 16 16 House Fan
325 Classroom 809 53 704 16 16 House Fan
326 Classroom 565 37 704 16 16 House Fan
327 Classroom 698 46 704 16 16 House Fan
328 Classroom 151 10 Yes 704 16 16 House Fan
329 Classroom 0 0 Yes 264 6 6 House Fan
2121 Storage 0 0 Yes 399 9 9 House Fan
- Auditorium 2451 163 3520 80 80 House Fan
- Counselor Office 0 0 Yes 220 5 5 N/A
- Gym 0 0 Yes 3872 88 88 N/A
- Kitchen 634 42 880 20 20 House Fan
- Library 865 57 1675 38 38 House Fan
- Main Office 0 0 Yes 308 7 7 N/A
- Principal Office 0 0 Yes 160 3 3 N/A
- SEL Classroom 970 64 704 16 16 House Fan
- Staff Lounge 0 0 Yes 399 9 9 N/A
Sheet Last Modified: 03-17-2021        
School:  Bodine      
           
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
401 Classroom  0 660 15 0
402 classroom 0 616 14 0
403 Classroom 0 598 13 0
404 Classroom 0 644 14 0
405 A Dept Head 0 98 2 0
405 B Counselor 0 133 3 0
406 Classroom 0 672 15 0
407 Classroom 0 644 14 0
408 Computer 0 726 16 0
409 Classroom 0 638 14 0
301 Classroom 0 667 15 0
302 Classroom 0 638 14 0
303 Classroom 0 644 14 0
304 Classroom 0 621 14 0
305 Faculty Area 0 450 10 0
306 Classroom 0 644 14 0
307 Classroom 0 644 14 0
308 Classrrom 0 638 14 0
309 Classroom 0 638 14 0
201 Classroom 0 638 14 0
202 Classroom 0 660 15 0
203 Library  0 1,058 24 0
203 Library office 0 140 3 0
205 Classroom 0 644 14 0
206 Classroom 0 621 14 0
207 Classroom 0 638 14 0
208 Classroom 0 638 14 0
102 Classroom 0 880 20 0
103 Counselor 0 110 2 0
104 Teacher Lounge 0 345 7 0
105 A  Office 0 63 1 0
105 B Office 0 108 2 0
105 C Office 0 81 1 0
108 Room 0 638 14 0
109 Room 0 638 14 0
2 Art Room 0 484 11 0
- Main Office 0 322 7 0
- Principal Office 0 96 2 0
- Conferance Room 0 220 5 0
- Gym / Lunchroom 0 2,760 62 0
- Kitchen 0 648 14 0
Sheet Last Modified: 04-28-2021      
School:  Amedee F. Bregy Elementary-Middle School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Auditorium 6957 463 4017 91 91 House Fan
- Cafeteria 934 62 1584 36 36 House Fan
- Gym 0 0 Yes 3872 88 88 House Fan
- Library 991 66 1739 39 39 House Fan
- Basement Science Classroom 557 37 1064 24 24 House Fan
- Basement Storage 143 9 396 9 9 House Fan
- Basement Boy's Bathroom 471 31 528 12 12 House Fan
- Basement Girl's Bathroom 434 28 528 12 12 House Fan
101 Classroom 271 18 660 15 15 House Fan
102 Classroom 312 20 660 15 15 House Fan
1K1 Classroom 823 54 660 15 15 House Fan
103 Classroom 51 3 650 14 3 House Fan
104 Classroom 564 37 650 14 14 House Fan
105 Classroom 255 17 616 14 14 House Fan
106 Classroom 723 48 616 14 14 House Fan
107 Classroom 664 44 616 14 14 House Fan
208 Classroom 866 57 660 15 15 House Fan
209 Classroom 751 50 660 15 15 House Fan
210 Classroom 128 8 Yes 652 14 14 House Fan
211 Classroom 663 44 616 14 14 House Fan
212 Classroom 669 44 660 15 15 House Fan
213 Classroom 694 46 660 15 15 House Fan
214 Classroom 629 41 660 15 15 House Fan
215 Classroom 279 18 660 15 15 House Fan
316 Classroom 404 26 660 15 15 House Fan
317 Classroom 0 0 Yes 656 14 14 House Fan
318 Classroom 577 38 660 15 15 House Fan
319 Classroom 231 15 660 15 15 House Fan
320 Classroom 726 48 704 16 16 House Fan
321 Classroom 298 19 704 16 16 House Fan
322 Classroom 511 34 704 16 16 House Fan
323 Classroom 702 46 660 15 15 House Fan
324 Classroom 375 25 660 15 15 House Fan
325 Classroom 623 41 616 14 14 House Fan
326 Classroom 557 37 654 14 14 House Fan
327 Classroom 525 35 654 14 14 House Fan
328 Classroom 664 44 660 15 15 House Fan
- Principal Office 0 Yes 108 2 2 House Fan
- Nurse Office 0 Yes 220 5 5 House Fan
Sheet Last Modified: 04-07-2021    
School:  Bridesburg Elementary School
Vendor: Goldner Goldner Part 2
  Devine Annex Retest
School:  Bridesburg Elementary School Annex
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
102 Classroom 422 28 846 19 19 Unit Ventilator
103 Classroom 377 25 686 15 15 Unit Ventilator
104 Classroom 476 31 993 22 22 Unit Ventilator
105 Classroom 300 20 672 15 15 Unit Ventilator
106 Classroom 536 35 972 22 22 Unit Ventilator
107 Classroom 334 22 737 16 16 Unit Ventilator
108 Classroom 322 21 1030 23 21 Unit Ventilator
109 Classroom 294 19 684 15 15 Unit Ventilator
110A Counselor's Office 198 13 130 2 2 Unit Ventilator
111 Classroom 372 24 253 5 5 Unit Ventilator
112 Nurse's Office 272 18 369 8 8 Unit Ventilator
112A Classroom 0 0 218 4 0 Unit Ventilator
112B Classroom 0 0 218 4 0 Unit Ventilator
113 Classroom 137 9 117 2 2 Unit Ventilator
114 Classroom 327 21 930 21 21 Unit Ventilator
115 Classroom 281 18 659 14 14 Unit Ventilator
116 Library 1510 100 1700 38 38 Unit Ventilator
200 Classroom 0 0 Yes 754 17 17 Unit Ventilator
201 Classroom 136 9 609 13 9 Unit Ventilator
202 Classroom 312 20 539 12 12 Unit Ventilator
203 Classroom 377 25 714 16 16 Unit Ventilator
204 Classroom 152 10 695 15 10 Unit Ventilator
205 Classroom 1577 105 1129 25 25 Unit Ventilator
206 Classroom 157 10 715 16 10 Unit Ventilator
207 Classroom 247 16 725 16 16 Unit Ventilator
208 Classroom 351 23 650 14 14 Unit Ventilator
209 Classroom 0 0 Yes 709 16 16 Unit Ventilator
210 Classroom 147 9 759 17 9 Unit Ventilator
211 Classroom 147 9 735 16 9 Unit Ventilator
212 Classroom 180 12 787 17 12 Unit Ventilator
213 Classroom 283 18 665 15 15 Unit Ventilator
214 Classroom 1248 83 845 19 19 Unit Ventilator
215 Classroom 457 30 677 15 15 Unit Ventilator
217 Classroom 282 18 735 16 16 Unit Ventilator
218 Classroom 292 19 601 13 13 Unit Ventilator
220 Classroom 287 19 706 16 16 Unit Ventilator
- Hallway 0 0 0 HRU
- Hallway 2 0 0 0 HRU
- Hallway Right 0 0 0 HRU
- Hallways 2 Center 0 0 0 HRU
- Gym 0 0 3925 89 0 N/A
- Cafeteria 0 0 3080 70 0 N/A
- Kitchen 0 0 697 15 0 N/A
- Main Office 1167 77 752 17 17 HRU
Bridesburg Elementary School Annex
1 Classroom 0 Yes 710 16 16 N/A
2 Staff Lounge 0 Yes 504 11 11 N/A
3 Classroom 0 Yes 575 13 13 N/A
4 Vice Principal 0 Yes 245 5 5 N/A
5 Classroom 0 Yes 693 15 15 N/A
6 Classroom 0 Yes 732 16 16 N/A
7 Classroom 0 Yes 773 17 17 N/A
8 Classroom 0 Yes 589 13 13 N/A
9 Classroom 0 Yes 610 13 13 N/A
10 Classroom 0 Yes 623 14 14 N/A
11 Classroom 0 Yes 581 13 13 N/A
12 Classroom 0 Yes 569 12 12 N/A
13 Classroom 0 Yes 625 14 14 N/A
14 Classroom 0 Yes 576 13 13 N/A
15 Classroom 0 Yes 547 12 12 N/A
- Support Room 0 Yes 140 3 3 N/A
- Speech Room 0 Yes 152 3 3 N/A
- Nurse Office 0 Yes 144 3 3 N/A
- Main Office 0 Yes 334 7 7 N/A
Sheet Last Modified: 04-23-2021    
School:  Henry A. Brown Elementary School
Vendor: Devine Retest Report  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Admin   418.0 27 1058 24 24 FCU
- Cafeteria 2,904.0 193 1994 45 45 AHU
- Gym 1,581.0 105 3360 76 76 AHU
- Library 488.0 32 1486 33 32 FCU
- Nurses Room 133.0 8 290 6 6 FCU
- Outside Library 366.0 24 900 20 20 FCU
100 Classroom 328.0 21 705 16 16 Unit Ventilator
101 Classroom 395.0 26 730 16 16 Unit Ventilator
113 Classroom 296.0 19 745 16 16 Unit Ventilator
114 Classroom 309.0 20 700 15 15 Unit Ventilator
151 Classroom 779.0 51 784 17 17 FCU
153 Classroom 689.0 45 895 20 20 FCU
154 Classroom 590.0 39 780 17 17 FCU
156 Classroom 647.0 43 835 18 18 FCU
200 Classroom 608.0 40 905 20 20 Unit Ventilator
201 Classroom 633.0 42 900 20 20 Unit Ventilator
202 Classroom 0 Yes 655 14 14
206 Classroom 0 Yes 795 18 18
209 Classroom 0 Yes 655 14 14
211 Classroom 470.0 31 895 20 20 Unit Ventilator
212 Classroom 307.0 20 905 20 20 Unit Ventilator
213 Classroom 782.0 52 875 19 19 Unit Ventilator
214 Classroom 616.0 41 875 19 19 Unit Ventilator
217 Classroom 250.0 16 665 15 15 Unit Ventilator
226 South Classroom 405.0 27 777 17 17 Unit Ventilator
226 West Classroom 458.0 30 777 17 17 Unit Ventilator
227 Classroom 487.0 32 740 16 16 Unit Ventilator
228 Classroom 685.0 45 775 17 17 Unit Ventilator
229 Computer Lab 103.0 6 Yes 990 22 22 FCU
300 Classroom 582.0 38 905 20 20 Unit Ventilator
301 Classroom 535.0 35 890 20 20 Unit Ventilator
302 Classroom 151.0 10 695 15 10 Unit Ventilator
304 Classroom 445.0 29 825 18 18 Unit Ventilator
310 Classroom 657.0 43 715 16 16 Unit Ventilator
311 Classroom 241.0 16 935 21 16 Unit Ventilator
312 Classroom 426.0 28 935 21 21 Unit Ventilator
313 Classroom 327.0 21 920 20 20 Unit Ventilator
314 Classroom 512.0 34 920 20 20 Unit Ventilator
317 Classroom 165.0 11 660 15 11 Unit Ventilator
318 Classroom 473.0 31 1090 24 24 FCU
319 Classroom 284.0 18 1125 25 18 FCU
322 South Classroom 174.0 11 745 16 11 Unit Ventilator
322 West Classroom 107.0 7 745 16 7 Unit Ventilator
323 Classroom 472.0 31 730 16 16 Unit Ventilator
324 Classroom 784.0 52 765 17 17 Unit Ventilator
325 West Classroom 533.0 35 890 20 20 Unit Ventilator
325 North Classroom 581.0 38 890 20 20 Unit Ventilator
Sheet Last Modified: 04-27-2021      
School:  Joseph H. Brown Elementary School
Vendor: Emcor Mechanical Retest Emcor Exhaust Report
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.                
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- GYM 921 61 3510 79 61 Unit Ventilator
- CAFE 921 61 1440 32 32 Unit Ventilator
101 classroom 519 34 667 15 15 Unit Ventilator
102 classroom 562 37 667 15 15 Unit Ventilator
103 classroom 358 23 713 16 16 Unit Ventilator
104 classroom 932 62 851 19 19 Unit Ventilator
105 classroom 844 56 920 20 20 Unit Ventilator
106 classroom 786 52 920 20 20 Unit Ventilator
107 classroom 985 65 1104 25 25 Unit Ventilator
108 classroom 836 55 851 19 19 Unit Ventilator
109 Counselor Office 0 Yes 112 2 2
110 Nurse Room 0 224 5 0 N/A
111 Medical Waiting 0 Yes 120 2 2
200 Classroom 0 Yes 667 15 15
201 classroom 394 26 690 15 15 Unit Ventilator
202 classroom 0 0 Yes 667 15 15 Unit Ventilator
203 classroom 417 27 667 15 15 Unit Ventilator
204 classroom 408 27 690 15 15 Unit Ventilator
205 classroom 550 36 690 15 15 Unit Ventilator
206 classroom 750 50 950 21 21 Unit Ventilator
206A Room 0 Yes 288 6 6
207 classroom 484 32 506 11 11 Unit Ventilator
207A Office 0 Yes 168 3 3
208 classroom 513 34 690 15 15 Unit Ventilator
209 classroom 723 48 713 16 16 Unit Ventilator
210 classroom 495 33 713 16 16 Unit Ventilator
211 classroom 376 25 667 15 15 Unit Ventilator
300 classroom 0 Yes 150 3 3
301 classroom 605 40 667 15 15 Unit Ventilator
302 classroom 457 30 690 15 15 Unit Ventilator
303 classroom 389 25 690 15 15 Unit Ventilator
304 classroom 469 31 713 16 16 Unit Ventilator
305 classroom 0 0 Yes 713 16 16 Unit Ventilator
306 classroom 0 0 Yes 874 19 19 Unit Ventilator
307 classroom 419 27 690 15 15 Unit Ventilator
308 classroom 0 Yes 713 16 16
Principal Office 0 Yes 160 3 3
- Main Office 0 Yes 368 8 8 N/A
Sheet Last Modified: 04-29-2021        
School:  William C Bryant Elementary School House fan Abated
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.          
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Gym 1,521 101 2,765 62 62 House Fan
- Shop Classroom 795 53 740 16 16 House Fan
- Art Room 0 0 740 16 0 House Fan
- Cafeteria/Auditorium 1,853 123 2,479 56 56 AHU
- Principal's Office 0 0 Yes 204 4 4 House Fan
- Office 0 0 135 3 0 House Fan
101 Classroom 1,717 114 1,013 23 23 House Fan
102 Classroom 888 59 696 15 15 House Fan
103 Classroom 853 56 690 15 15 House Fan
104 Classroom 653 43 740 16 16 House Fan
105 Classroom 0 0 Yes 700 15 15 House Fan
106 Classroom 0 0 Yes 740 16 16 House Fan
107 Classroom 0 0 Yes 718 16 16 House Fan
108 Classroom 0 0 Yes 795 18 18 House Fan
110 Nurse Office 0 0 Yes 219 4 4 House Fan
111 - 0 731 16 0 House Fan
112 Main Office 0 Yes 707 16 16 House Fan
113 Classroom 0 0 Yes 674 15 15 House Fan
114 Classroom 0 0 Yes 713 16 16 House Fan
201 Classroom 1,845 123 1,013 23 23 House Fan
202 Classroom 843 56 686 15 15 House Fan
203 Classroom 108 7 Yes 690 15 15 House Fan
204 Classroom 893 59 740 16 16 House Fan
205 Classroom 0 0 Yes 700 15 15 House Fan
206 Classroom 0 0 Yes 740 16 16 House Fan
207 Classroom 0 0 Yes 718 16 16 House Fan
208 Classroom 0 0 Yes 795 18 18 House Fan
209 Classroom 0 0 753 17 0 House Fan
210 Classroom 0 0 Yes 715 16 16 House Fan
211 Classroom 0 0 731 16 0 House Fan
212 Classroom 0 0 Yes 707 16 16 House Fan
213 Classroom 0 0 Yes 674 15 15 House Fan
214 Classroom 0 0 713 16 0 House Fan
- IMC - Library 0 0 2,788 63 0 Roof Top Unit
- 2nd Flr Teacher's Lounge 0 0 349 7 0 House Fan
301 Classroom 387 25 1,013 23 23 House Fan
302 Classroom 748 49 686 15 15 House Fan
303 Classroom 68 4 Yes 690 15 15 House Fan
304 Classroom 156 10 Yes 740 16 16 House Fan
305 Classroom 0 0 Yes 700 15 15 House Fan
306 Classroom 0 0 Yes 740 16 16 House Fan
307 Classroom 0 0 718 16 0 House Fan
308 Classroom 0 0 795 18 0 House Fan
309 Classroom 0 0 753 17 0 House Fan
310 Classroom 0 0 Yes 715 16 16 House Fan
311 Classroom 0 0 Yes 731 16 16 House Fan
312 Classroom 0 0 Yes 707 16 16 House Fan
313 Classroom 0 0 Yes 674 15 15 House Fan
314 Classroom 0 0 Yes 713 16 16 House Fan
- 3rd Flr Teacher's Lounge 0 0 349 7 0 House Fan
Sheet Last Modified: 03-17-2021        
School:  Building 21 (Kinsey)      
         
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.          
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
600 Classroom   0 810 18 0
2 Classroom   0 1,104 25 0
4 Classroom   0 884 20 0
5 Kitchen 0 910 20 0
112 Classroom   0 710 16 0
112A Nurse 0 99 2 0
111 Office 0 319 7 0
111A Office 0 140 3 0
111B Office 0 168 3 0
113 Office 0 475 10 0
113A Office 0 81 1 0
113B Office 0 81 1 0
110 Main Office 0 710 16 0
115 Classroom   0 140 3 0
114 Classroom   0 81 1 0
109 Classroom   0 710 16 0
108 Classroom   0 710 16 0
107 Classroom   0 710 16 0
106 Classroom   0 710 16 0
105 Classroom   0 710 16 0
104 Classroom   0 710 16 0
103 Classroom   0 710 16 0
102 Classroom   0 710 16 0
101 Classroom   0 710 16 0
116 Aud 0 5,244 119 0
201 Classroom   0 710 16 0
202 Classroom   0 710 16 0
203 Classroom   0 710 16 0
204 Classroom   0 710 16 0
205 Classroom   0 710 16 0
206 Classroom   0 710 16 0
207 Classroom   0 710 16 0
208 Classroom   0 710 16 0
210 Classroom   0 710 16 0
211 Classroom   0 710 16 0
212 Classroom   0 710 16 0
213 Nurse 0 295 6 0
214 Office 0 140 3 0
209 Classroom   0 710 16 0
215 Office 0 140 3 0
301 Classroom   0 710 16 0
302 Classroom   0 710 16 0
303 Classroom   0 710 16 0
304 Classroom   0 710 16 0
305 Classroom   0 710 16 0
306 Classroom   0 710 16 0
307 Classroom   0 710 16 0
308 Classroom   0 710 16 0
309 Classroom   0 710 16 0
310 Classroom   0 710 16 0
311 Classroom   0 710 16 0
Sheet Last Modified: 04-21-2021          
School:  Camelot Academy @ Boone      
Vendor: Devine Brothers      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
300 Office 292 19 370 8 8 Univent
301 Classroom 335 22 803 18 18 Univent
302 Classroom 281 18 816 18 18 Univent
304 Classroom 292 19 1,808 41 19 Univent
305 (309) Classroom 330 22 851 19 19 Univent
306 Classroom 364 24 966 21 21 Univent
307 Classroom 348 23 1,647 37 23 Univent
308 Office 266 17 494 11 11 Univent
310 Office 135 9 399 9 9 Univent
312 Classroom 293 19 663 15 15 Univent
314 Classroom 218 14 458 10 10 Univent
316 Classroom 367 24 877 19 19 Univent
- Principal Office 424 28 312 7 7 ERU
200 Classroom 332 22 807 18 18 Univent
201 Classroom 305 20 593 13 13 Univent
202 Classroom 287 19 589 13 13 Univent
204 Classroom 300 20 1,084 24 20 Univent
206 Classroom 434 28 962 21 21 Univent
207 Classroom 326 21 880 20 20 Univent
208 Office 239 15 494 11 11 Univent
209 Classroom 349 23 879 19 19 Univent
- Academic Office 308 20 311 7 7 Univent
- Operations Office 348 23 395 8 8 ERU
212 Classroom 380 25 567 12 12 Univent
214 Classroom 397 26 652 14 14 Univent
216 Classroom 408 27 651 14 14 Univent
104 Conference Room 424 28 497 11 11 Univent
- Main Office 372 24 1,055 23 23 Univent
102 Computer Lab 304 20 Yes 1,019 23 23 Univent
B5 Classroom 310 20 1,248 28 20 Univent
B6 Cosmo Room 1 290 19 535 12 12 Univent
B7 Hair Salon 443 29 693 15 15 Univent
B8 Barbershop 275 18 539 12 12 Univent
Sheet Last Modified: 04-14-2021    
School:  Philadelphia High School for the Creative & Performing Arts
Vendor: Chadwick Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
109 Room 714 47 1215.8 27 27
108 Room 0 0 872.49 19 0
107 Room 468 31 1182.7 26 26
105 Room 0 0 1171.6 26 0
110 Office 45 3 171.71 3 3
- First Floor North Corridor 290 19 3004.3 68 19
- First Floor South Corridor 118 7 1139.3 25 7
116 Room -100 -6 216.61 4 -6
106  Editing Suite 15 1 112.47 2 1
106 Room 0 1119.1 25 0
114 Room -61 -4 845.65 19 -4
116 Control Room 219 14 327.76 7 7
- Second Floor South Corridor Outside Stair 4 45 3 2223.7 50 3
- Second Floor South Corridor 0 0 1642.3 37 0
- Second Floor North Corridor 301 20 1642.3 37 20
202 Room 78 5 275.81 6 5
203 Room 142 9 1209.4 27 9
204 Room 616 41 1059.9 24 24
205 Room 607 40 874.01 19 19
206 Room 0 0 1206.6 27 0
207 Room 613 40 891.99 20 20
208 Room 809 53 870.75 19 19
209 Room 584 38 871.76 19 19
210 Room 304 20 791.75 17 17
211 Room 420 28 1119.8 25 25
213 Room -85 -5 815.15 18 -5
214 Room 567 37 1351.8 30 30
304 Room 15 1 1059.9 24 1
305 Room 70 4 192.7 4 4
306 Room 122 8 888.58 20 8
307 Room 0 0 251.97 5 0
308 Room 533 35 1094.9 24 24
310 Room 527 35 877.6 19 19
311 Room 824 54 1209 27 27
312 Room 101 6 892.16 20 6
313 Room -121 -8 870.18 19 -8
314 Room 342 22 771.96 17 17
315 Room -455 -30 888.8 20 -30
316 Room 1,080 72 1532.3 34 34
317 Room 754 50 850.53 19 19
318 Room 849 56 1015 23 23
320 Room -20 -1 94.85 2 -1
321 Room -15 -1 77.87 1 -1
322 Room -17 -1 58.45 1 -1
323 Room 35 2 1013.7 23 2
324 Room 30 2 257.05 5 2
326 Room -297 -19 0 -19
- Third Floor North Corridor 303 20 1655.3 37 20
- Third Floor South Corridor 0 0 1655.3 37 0
400 Room 932 62 1893.6 43 43
401 Room 302 20 1794.2 40 20
402 Room 615 41 2176.1 49 41
403 Room -67 -4 216.87 4 -4
403 Print Room 130 8 275.87 6 6
403 Room 52 3 2280.1 51 3
404 Room 226 15 1882.5 42 15
405 Room 390 26 1656.39 37 26
405 Prep Room 45 3 0 0
406 Room 710 47 0 0
407 Room 113 7 0 0
408 Room 0 0 217.94 4 0
- 4th Floor Corridor South 0 0 1677.4 38 0
Sheet Last Modified: 04-23-2021          
School:  Laura H. Carnell Elementary School    
  Laura H. Carnell Little School House House Fan Abated  
Vendor: Devine Brothers LSH Retest  
  EMCOR Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
- Basement Corridor 0 0 450 10 0 Unit Ventilator
- Gym Office 0 0 144 3 0 N/A
B-3 Art 0 0 920 20 0 House Fan
B-4 Music 0 0 660 15 0 House Fan
B1 Counselors 0 0 630 14 0 House Fan
B2 Family Resource 0 0 1023 23 0 House Fan
B5 Classroom 519 34 800 18 18 Unit Ventilator
B6 Classroom 110 7 800 18 7 Unit Ventilator
B7 Classroom 421 28 800 18 18 Unit Ventilator
- 1st flr Corridor 0 828 18 0 Unit Ventilator
- Main Office 0 0 483 10 0 N/A
- Principal's Office 0 0 304 6 0 N/A
- 1st Flr Security 0 0 81 1 0 N/A
- 1st Flr Counselors 0 0 126 2 0 N/A
- 1st Flr Office 0 216 4 0 N/A
101 Classroom 0 0 Yes 957 21 21 House Fan
102 Classroom 0 0 870 19 0 House Fan
103 Classroom 0 0 899 20 0 House Fan
104 Classroom 0 0 Yes 870 19 19 House Fan
105 Classroom 0 0 900 20 0 House Fan
106 Classroom 0 0 870 19 0 House Fan
107 Classroom 0 0 Yes 900 20 20 House Fan
108 Classroom 0 0 Yes 930 21 21 House Fan
109 Classroom 0 0 Yes 900 20 20 House Fan
110 Classroom 0 0 960 21 0 House Fan
111 Classroom 0 0 768 17 0 House Fan
112 Classroom 0 0 768 17 0 House Fan
113 Classroom 0 0 768 17 0 House Fan
- 2nd flr Corridor 0 828 18 0 Unit Ventilator
- 2nd Flr Nurse's 0 0 216 4 0 N/A
- 2nd Flr. Office 0 0 126 2 0 N/A
- Asst. Principal 0 0 312 7 0 N/A
201 Classroom 0 0 Yes 928 21 21 House Fan
202 Classroom 0 0 870 19 0 House Fan
203 Classroom 0 0 899 20 0 House Fan
206 Classroom 0 0 870 19 0 House Fan
207 Classroom 0 0 900 20 0 House Fan
208 Classroom 0 0 Yes 930 21 21 House Fan
209 Computer Lab 0 0 900 20 0 House Fan
210 Computer Lab 0 0 960 21 0 House Fan
211 Classroom 0 0 768 17 0 House Fan
212 Classroom 0 0 768 17 0 House Fan
213 Classroom 0 0 768 17 0 House Fan
217 Teachers Lounge 0 0 552 12 0 N/A
- 3rd flr Corridor 0 828 18 0 Unit Ventilator
- 3rd Flr. Office 0 0 126 2 0 N/A
300 East Classroom 0 0 720 16 0 House Fan
300 West Office 0 0 99 2 0 N/A
301 Classroom 0 0 Yes 928 21 21 House Fan
302 Classroom 0 0 Yes 870 19 19 House Fan
303 Classroom 0 0 899 20 0 House Fan
304 Classroom 0 0 Yes 870 19 19 House Fan
305 Classroom 0 0 Yes 900 20 20 House Fan
306 Classroom 0 0 870 19 0 House Fan
307 Classroom 0 0 Yes 900 20 20 House Fan
308 Classroom 0 0 Yes 930 21 21 House Fan
309 Classroom 0 0 900 20 0 House Fan
310 Classroom 0 0 960 21 0 House Fan
312 Classroom 544 36 768 17 17 Unit Ventilator
313 Classroom 479 31 768 17 17 Unit Ventilator
314 Classroom 65 4 768 17 4 Unit Ventilator
317 Speech 0 0 117 2 0 N/A
- Auditorium 0 0 3456 78 0 House Fan
- Cafeteria 0 0 986 22 0 N/A
- Dean's Office 0 0 108 2 0 N/A
- Gym 0 0 3306 75 0 N/A
- IMC Classroom 0 0 1363 30 0 House Fan
- IMC Office 0 0 95 2 0 House Fan
Little School House
A-1 Classroom 293 19 1056 24 19 AHU
A-3 Classroom 296 19 1056 24 19 AHU
A-2 Classroom 331 22 1056 24 22 AHU
A-4 Classroom 343 22 1056 24 22 AHU
A-5 Classroom 0 1056 24 0 BCU
A-5 Storage 0 52 1 0 BCU
A-7 Classroom 0 1056 24 0 BCU
A-6 Classroom 321 21 1056 24 21 AHU
A-8 Classroom 355 23 1056 24 23 AHU
A-9 Classroom 364 24 1056 24 24 AHU
A-11 Classroom 396 26 1056 24 24 AHU
A-10 Classroom 292 19 1056 24 19 AHU
A-12 Classroom 285 19 1056 24 19 AHU
- Corridor 0 0 1056 24 0 AHU
- Cafeteria 2789 185 1850 42 42 AHU
- BE Office 76 5 88 2 2 AHU
- Main Office 215 14 168 3 3 AHU
- Vice Principal 93 6 100 2 2 AHU
- Counselor 105 7 100 2 2 AHU
- Comm Closet 54 3 50 1 1 AHU
- Storage 73 4 250 5 4 AHU
- Lobby 66 4 216 4 4 AHU
- Store Room 1 Ceiling 43 2 250 5 2 BCU
- Store Room 2 26 1 70 1 1 BCU
- Store Room 3 27 1 70 1 1 BCU
- Janitors Closet 20 1 32 0 0 BCU
- Storage next to B.E. 22 1 99 2 1 BCU
Sheet Last Modified: 04-30-2021      
School:  George Washington Carver High School for Engineering and Science
Vendor: Devine Brothers Devine Retest Devine 2nd Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Carver Commons- in IMC Room 147 0 0 96 2 0
2 Carver Commons- in IMC Room 147 0 0 147 3 0
3 Carver Commons- in IMC Room 147 0 0 143 3 0
4 Carver Commons- in IMC Room 147 0 0 99 2 0
104 Room 783 52 625 14 14
107 Room 158 10 704 16 10
114 Room 0 0 840 19 0
115 Room 305 20 840 19 19
123 Room 181 12 920 20 12
124 Room 85 5 480 10 5
125 Room 643 42 1753 39 39
126 Room 399 26 750 17 17
134 Room 221 14 566 12 12
135 Room 0 0 400 9 0
136 Room 86 5 200 4 4
137 Womens Room 0 0 280 6 0
138 Weight Room 417 27 1500 34 27
139 PE Office 0 0 176 4 0
139 Training Room 0 0 139 3 0
139A Lavatory 0 0 96 2 0
144 Room 235 15 1311 29 15
145 Env. Science Lab 373 24 2349 53 24
147 IMC 1,282 85 4087 92 85
201 Room 0 0 1200 27 0
202 Room 371 24 864 19 19
203 Room 294 19 864 19 19
209 Room 401 26 952 21 21
211 Room 367 24 960 21 21
212 Room 292 19 960 21 19
213 Room 295 19 960 21 19
214 Room 0 0 960 21 0
217 Room 271 18 1250 28 18
220 Room 0 0 1408 32 0
221 Room 95 6 1680 38 6
222 Room 201 13 1200 27 13
224 Room 392 26 1680 38 26
226 Room 309 20 1680 38 20
229 Room 0 0 1600 36 0
230 Room 162 10 1680 38 10
301 Room 0 0 1157 26 0
302 Room 834 55 864 19 19
303 Room 281 18 864 19 18
309 Room 462 30 864 19 19
311 Room 533 35 1041 23 23
312 Room 201 13 1118 25 13
313 Room 243 16 816 18 16
314 Room 389 25 816 18 18
317 Room 0 0 816 18 0
318 Room 170 11 768 17 11
320 Room 142 9 1056 24 9
321 Room 487 32 1200 27 27
322 Room 460 30 1200 27 27
324 Room 75 5 1200 27 5
327 Room 226 15 1519 34 15
329 Room 400 26 1440 32 26
- Art Room 756 50 2500 56 50
- Auditorium 4,245 283 5612 127 127
- Cafeteria 6,739 449 3826 86 86
- Dance Area 104 6 1920 43 6
- Dance Studio 1,644 109 336 7 7
- Gymnasium 13,040 869 8949 203 203
- Female Student Locker Room 579 38 1200 27 27
- Male Student Locker Room 176 11 1200 27 11
- Female Staff Locker Room 52 3 117 2 2
- Male Staff Locker Room 446 29 112 2 2
- Male Staff Locker Room 446 29 112 2 2
Sheet Last Modified: 04-06-2021  
School:  Lewis C. Cassidy Elementary School
Vendor: Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Boy's Gang Bathroom 560 37 575 13 13 House Fan
- Girl's Gang Bathroom 326 21 396 9 9 House Fan
B Teachers Lounge 384 25 308 7 7 House Fan
B2 Office 0 0 Yes 748 17 17
B3 Classroom 741 49 742 16 16 House Fan
B7 Gym 0 0 Yes 3872 88 88 N/A
B8 Classroom 527 35 968 22 22 House Fan
101 Classroom 542 36 660 15 15 House Fan
102 Classroom 478 31 660 15 15 House Fan
103 Classroom 538 35 660 15 15 House Fan
104 Classroom 473 31 616 14 14 House Fan
105 Office 0 0 132 3 0 N/A
106 Classroom 682 45 704 16 16 House Fan
107 Classroom 741 49 616 14 14 House Fan
108 Classroom 812 54 660 15 15 House Fan
109 Classroom 734 48 660 15 15 House Fan
201 Nurses Office 0 0 Yes 176 4 4 N/A
202 Classroom 551 36 792 18 18 House Fan
203 Classroom 389 25 660 15 15 House Fan
204 Classroom 471 31 660 15 15 House Fan
205 Teachers Lounge 0 0 Yes 308 7 7 N/A
206 Asst Principal 0 0 Yes 207 4 4 N/A
207 Classroom 525 35 660 15 15 House Fan
208 Small Classroom 0 0 Yes 220 5 5 House Fan
209 Classroom 675 45 660 15 15 House Fan
210 Classroom 551 36 616 14 14 House Fan
211 Classroom 565 37 660 15 15 House Fan
212 Classroom 611 40 660 15 15 House Fan
213 Office 0 0 Yes 264 6 6 N/A
301 Office 0 0 Yes 264 6 6 N/A
302 Classroom 562 37 704 16 16 House Fan
303 Classroom 430 28 704 16 16 House Fan
304 Classroom 392 26 616 14 14 House Fan
305 Classroom 507 33 616 14 14 House Fan
306 Classroom 112 7 Yes 704 16 16 House Fan
307 Classroom 465 31 748 17 17 House Fan
308 Classroom 378 25 899 20 20 House Fan
309 Classroom 378 25 704 16 16 House Fan
310 Classroom 154 10 660 15 10 House Fan
311 Classroom 518 34 616 14 14 House Fan
312 Classroom 718 47 616 14 14 House Fan
313 Classroom 550 36 660 15 15 House Fan
314 Classroom 561 37 660 15 15 House Fan
315 Storage 0 0 264 6 0 N/A
- Attwood Lunch Rm 940 62 836 19 19 House Fan
- Auditorium 1895 126 3608 82 82 House Fan
- Backstage Office 0 0 132 3 0 N/A
- Lunch Room 660 44 880 20 20 House Fan
- Library 732 48 704 16 16 House Fan
- Main Office 0 0 Yes 308 7 7 N/A
- Principal's Office 0 0 Yes 132 3 3 N/A
Sheet Last Modified: 04-19-2021      
School:  Joseph W. Catharine Elementary School
Vendor: EMCOR Main Building Part 2  
School: Joseph W. Catharine Elementary School Annex
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
- Lunch 503 33 1247 28 28 Unit Ventilator
- Gym 976 65 4544 103 65 Unit Ventilator
102 Classroom 270 18 681 15 15 Unit Ventilator
103 Classroom 313 20 550 12 12 Unit Ventilator
104 Classroom 670 44 953 21 21 Unit Ventilator
105 Classroom 0 0 Yes 953 21 21 Unit Ventilator
106 Classroom 0 0 Yes 842 19 19 Unit Ventilator
107 Classroom 627 41 1062 24 24 Unit Ventilator
108 Classroom 307 20 836 19 19 Unit Ventilator
- Office 212 14 367 8 8 Unit Ventilator
201 Classroom 407 27 676 15 15 Unit Ventilator
202 Classroom 331 22 683 15 15 Unit Ventilator
203 Classroom 306 20 673 15 15 Unit Ventilator
204 Classroom 144 9 Yes 708 16 16 Unit Ventilator
205 Classroom 300 20 678 15 15 Unit Ventilator
206 Classroom 0 0 Yes 855 19 19 Unit Ventilator
207 Classroom 0 0 Yes 504 11 11 Unit Ventilator
208 Classroom 0 0 Yes 672 15 15 Unit Ventilator
209 Classroom 0 0 Yes 709 16 16 Unit Ventilator
210 Classroom 0 0 Yes 705 16 16 Unit Ventilator
211 Classroom 0 0 Yes 673 15 15 Unit Ventilator
301 Classroom 0 0 Yes 684 15 15 Unit Ventilator
302 Classroom 0 0 Yes 684 15 15 Unit Ventilator
303 Classroom 0 0 Yes 679 15 15 Unit Ventilator
304 Classroom 173 11 Yes 708 16 16 Unit Ventilator
305 Classroom 209 13 Yes 698 15 15 Unit Ventilator
306 Classroom 0 0 Yes 872 19 19 Unit Ventilator
307 Classroom 0 0 Yes 675 15 15 Unit Ventilator
308 Classroom 198 13 Yes 674 15 15 Unit Ventilator
309 Classroom 284 18 705 16 16 Unit Ventilator
310 Classroom 297 19 707 16 16 Unit Ventilator
311 Classroom 0 0 Yes 674 15 15 Unit Ventilator
- Principal's office 0 0 Yes 359 8 8
- Nurse office 0 0 Yes 324 7 7
- Counselor Office 0 0 Yes 109 2 2
Joseph W. Catherine Elementary School Annex
100 Office 0 Yes 273 6 6 N/A
102 K-1 Room 0 Yes 680 15 15 N/A
104 K-2 Room 0 Yes 714 16 16 N/A
213 K-3 0 Yes 1056 24 24 N/A
Sheet Last Modified: 04-28-2021    
School:  Cayuga Elementary School (former St. Henry’s)
Vendor: Chadwick Devine Brothers Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 classroom 355.0 23 830 18 18 Unit Ventilator
102 classroom 375.0 25 740 16 16 Unit Ventilator
103 classroom 315.0 21 795 18 18 Unit Ventilator
104 classroom 280.0 18 796 18 18 Unit Ventilator
105 Nurse's Office 0 Yes 330 7 7 N/A
106 classroom 275.0 18 403 9 9 Unit Ventilator
117 classroom 736.0 49 806 18 18 Unit Ventilator
118 classroom 625.0 41 688 15 15 Unit Ventilator
119 classroom 586.0 39 845 19 19 Unit Ventilator
120 classroom 335.0 22 670 15 15 Unit Ventilator
201 classroom 325.0 21 830 18 18 Unit Ventilator
202 classroom 305.0 20 740 16 16 Unit Ventilator
203 classroom 380.0 25 795 18 18 Unit Ventilator
204 classroom 360.0 24 796 18 18 Unit Ventilator
205 classroom 355.0 23 765 17 17 Unit Ventilator
206 classroom 310.0 20 780 17 17 Unit Ventilator
214 classroom 375.0 25 728 16 16 Unit Ventilator
215 classroom 365.0 24 693 15 15 Unit Ventilator
216 classroom 330.0 22 737 16 16 Unit Ventilator
217 classroom 1,606.0 107 822 18 18 Unit Ventilator
301 classroom 345.0 23 830 18 18 Unit Ventilator
302 classroom 275.0 18 740 16 16 Unit Ventilator
303 classroom 380.0 25 795 18 18 Unit Ventilator
304 classroom 380.0 25 796 18 18 Unit Ventilator
305 classroom 553.0 36 765 17 17 Unit Ventilator
306 classroom 315.0 21 790 17 17 Unit Ventilator
- Gym 1,213.0 80 2754 62 62 AHU
- Basement Corridor 90.0 6 0 0 AHU
- Main Entrance Corridor 46.0 3 0 0 AHU
- 1st Floor Corridor 31.0 2 0 0 AHU
- Cafeteria 936.0 62 3432 78 62 AHU
Sheet Last Modified: 04-29-2091    
School:  Central High School
Vendor: Devine Brothers Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Ceramic 253 16 723 16 16
2 Kiln 58 3 128 2 2
3 Drafting Studio 403 26 1366 31 26
4 Fashion 40 2 290 6 2
5 Office 64 4 349 7 4
6 Photography 32 2 171 3 2
7 Computer Lab 31 2 148 3 2
8 Art Studio 356 23 1452 33 23
9 Printing Studio 70 4 390 8 4
12 Classroom 333 22 840 19 19
13 Classroom 388 25 709 16 16
82 Classroom 301 20 1714 38 20
84 Classroom 300 20 1531 34 20
85 Classroom 300 20 1594 36 20
89 Classroom 389 25 1327 30 25
95 Classroom 604 40 1307 29 29
97 Classroom 605 40 1216 27 27
98 Classroom 428 28 1374 31 28
99 Classroom 432 28 1258 28 28
101 Classroom 376 25 876 19 19
102 Classroom 370 24 852 19 19
103 Classroom 387 25 876 19 19
104 Classroom 316 21 700 15 15
105 Classroom 305 20 675 15 15
106 Classroom 283 18 687 15 15
107 Classroom 288 19 706 16 16
108 Classroom 329 21 700 15 15
109 Classroom 0 0 675 15 0
110 Office 248 16 339 7 7
111 Classroom 0 0 654 14 0
119 Classroom 0 0 470 10 0
120 Classroom 332 22 857 19 19
121 Classroom 366 24 694 15 15
122 Classroom 346 23 724 16 16
123 Classroom 297 19 694 15 15
124 Classroom 280 18 680 15 15
125 Classroom 427 28 683 15 15
126 Classroom 415 27 720 16 16
127 Classroom 290 19 722 16 16
136 Classroom 281 18 297 6 6
138 Principal 176 11 235 5 5
141 Classroom 293 19 690 15 15
142 Office 377 25 982 22 22
143 Classroom 405 27 700 15 15
144 Roster Office 179 11 652 14 11
201 Classroom 0 0 530 12 0
202 Classroom 288 19 834 18 18
203 Classroom 293 19 681 15 15
204 Classroom 288 19 692 15 15
205 Classroom 283 18 676 15 15
206 Classroom 344 22 681 15 15
207 Classroom 344 22 705 16 16
208 Classroom 286 19 682 15 15
209 Classroom 306 20 694 15 15
210 Office 226 15 336 7 7
211 Classroom 0 0 650 14 0
224 Classroom 646 43 831 18 18
225 Classroom 289 19 800 18 18
226 Classroom 286 19 700 15 15
227 Classroom 0 0 693 15 0
229 Classroom 377 25 676 15 15
230 Classroom 358 23 680 15 15
231 Classroom 0 0 680 15 0
232 Classroom 315 21 638 14 14
233 Classroom 246 16 597 13 13
244 Classroom 357 23 840 19 19
245 Classroom 316 21 840 19 19
246 Classroom 315 21 683 15 15
247 Classroom 368 24 686 15 15
248 Classroom 401 26 705 16 16
249 Classroom 379 25 694 15 15
250 Classroom 314 20 687 15 15
251 Classroom 458 30 705 16 16
252 Classroom 364 24 670 15 15
253 Classroom 314 20 330 7 7
302 classroom 483 32 1260 28 28
303 Classroom 331 22 1145 26 22
304 Classroom 291 19 670 15 15
305 Theater 250 16 480 10 10
306 Classroom 430 28 661 15 15
307 Classroom 478 31 657 14 14
308 Classroom 209 13 624 14 13
309 Classroom 200 13 700 15 13
311 Computer Lab 64 4 827 18 4
321C Storage 210 14 157 3 3
323 Classroom 256 17 1082 24 17
325 Computer Lab 314 20 654 14 14
326 Classroom 294 19 654 14 14
327 Computer Lab 356 23 654 14 14
328 Music Room 289 19 647 14 14
329 Computer Lab 205 13 296 6 6
402 Classroom 625 41 941 21 21
403 Classroom 391 26 779 17 17
406 Classroom 531 35 1102 25 25
407 Classroom 510 34 1102 25 25
Gym Gym 0 Yes 16550 376 376
- Office Break Rm 240 16 170 3 3
Sheet Last Modified: 5-3-2021        
School:  George W. Childs Elementary School @ Barratt  
         
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 0 Yes 1,575 35 35
2 Classroom 0 Yes 1,075 24 24
3 Head Start Kitchen 0 Yes 696 15 15 House Fan
4 - 0 1,224 27 0 House Fan
5 - 0 Yes 1,035 23 23 House Fan
8 Classroom 0 704 16 0 House Fan
100B VP's Office 0 143 3 0 House Fan
100C Conference Room 0 221 5 0 House Fan
102 Classroom 0 Yes 1,012 23 23 House Fan
103 Classroom 0 Yes 1,012 23 23 House Fan
105 Classroom 0 Yes 851 19 19 House Fan
105a - 0 Yes 575 13 13 House Fan
106 Classroom 0 Yes 800 18 18 House Fan
107 Classroom 0 Yes 667 15 15 House Fan
109A Counsleor 0 240 5 0 House Fan
109C Dicipline Room 0 240 5 0
118 Classroom 0 Yes 736 16 16 House Fan
119 Nurse 0 Yes 420 9 9 House Fan
121 Classroom 0 Yes 736 16 16 House Fan
201 Classroom 0 Yes 667 15 15 House Fan
203 Classroom 0 Yes 667 15 15 House Fan
205 Classroom 0 Yes 460 10 10 House Fan
206 Classroom 0 Yes 667 15 15 House Fan
207 Classroom 0 Yes 504 11 11 House Fan
208 Classroom 0 Yes 912 20 20 House Fan
209 Classroom 0 Yes 828 18 18 House Fan
210 - 0 Yes 912 20 20 House Fan
212 Classroom 0 Yes 902 20 20 House Fan
214 Classroom 0 Yes 966 21 21 House Fan
215 Classroom 0 Yes 748 17 17 House Fan
216 Classroom 0 Yes 1,012 23 23 House Fan
217 - 0 Yes 1,450 32 32 House Fan
219 Classroom 0 1,450 32 0 House Fan
220 Classroom 0 Yes 1,058 24 24 House Fan
222 - 0 Yes 1,058 24 24 House Fan
224 Classroom 0 Yes 704 16 16 House Fan
224B - 0 Yes 689 15 15 House Fan
226 Classroom 0 704 16 0 House Fan
2nd Floor Special Needs Changing Room 0 Yes 180 4 4
301 Classroom 0 Yes 989 22 22 House Fan
302 Classroom 0 Yes 989 22 22 House Fan
304 - 0 704 16 0 House Fan
305 - 0 Yes 704 16 16 House Fan
306 - 0 Yes 704 16 16 House Fan
307 Classroom 0 Yes 552 12 12 House Fan
308 Classroom 0 Yes 667 15 15 House Fan
309 Classroom 0 Yes 667 15 15 House Fan
310 Classroom 0 Yes 805 18 18 House Fan
311 Classroom 0 Yes 704 16 16 House Fan
313 Classroom 0 Yes 667 15 15 House Fan
314 Classroom 0 Yes 704 16 16 House Fan
315 Classroom 0 Yes 704 16 16 House Fan
316 Teacher's Lounge 0 Yes 704 16 16 House Fan
401 - 0 989 22 0 House Fan
402 - 0 Yes 989 22 22 House Fan
404 Classroom 0 Yes 989 22 22 House Fan
405 Classroom 0 460 10 0 House Fan
406 - 0 Yes 989 22 22 House Fan
407 - 0 Yes 828 18 18 House Fan
408 Classroom 0 Yes 989 22 22 House Fan
409 Classroom 0 Yes 704 16 16 House Fan
411 Classroom 0 Yes 704 16 16 House Fan
412 Classroom 0 Yes 704 16 16 House Fan
Auditorium 0 4,128 93 0
- Cafeteria 0 Yes 5,512 125 125 House Fan
- Special Needs Classroom 0 Yes 345 7 7 House Fan
- IMC 0 Yes 1,725 39 39 House Fan
- Main Office 0 Yes 726 16 16 House Fan
- Music Room 0 726 16 0 House Fan
- Principal 0 Yes 312 7 7 House Fan
Sheet Last Modified: 4-23-2021      
School:  Roberto Clemente Middle School and The LINC High School
Vendor: Chadwick Part 2    
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 126 8 664 15 8 1 Univent & 1 AHU
102 Classroom 54 3 664 15 3 Univent
103 Classroom 95 6 664 15 6 1 Univent & 1 AHU
104 Classroom 54 3 664 15 3 Univent
106 Classroom 24 1 312 7 1
107 Classroom 179 11 682 15 11 1 Unitvent & 2 AHU
108 Classroom 108 7 682 15 7 1 Univent & 1 AHU
109 Classroom 83 5 672 15 5 1 Univent & 1 AHU
110 Classroom 54 3 530 12 3 1 Univent & 1 AHU
111 Classroom 86 5 984 22 5 1 Univent & 1 AHU
112 Classroom 113 7 984 22 7 1 Univent & 1 AHU
113 Classroom 116 7 987 22 7 1 Univent & 1 AHU
114 Classroom 87 5 987 22 5 1 Univent & 1 AHU
115 Classroom 87 5 987 22 5 1 Univent & 1 AHU
116 Classroom 82 5 987 22 5 1 Univent & 1 AHU
121 - 24 1 264 6 1
125 Classroom 24 1 132 3 1
126 Classroom 24 1 132 3 1
128 Classroom 24 1 120 2 1
129 Classroom 24 1 120 2 1
131 Classroom 24 1 120 2 1
132 Classroom 24 1 120 2 1
144 Classroom 11 0 109 2 0
145 Classroom 11 0 70 1 0
146 Classroom 10 0 286 6 0
147 Classroom 10 0 160 3 0
148 Classroom 10 0 80 1 0
149 Classroom 10 0 90 2 0
150 Classroom 10 0 108 2 0
151 Classroom 10 0 70 1 0
152 Classroom 10 0 108 2 0
153 Classroom 10 0 108 2 0
201 Classroom 91 6 816 18 6 1 Univent & 1 AHU
202 Classroom 63 4 816 18 4 1 Univent & 1 AHU
203 Classroom 86 5 816 18 5 1 Univent & 1 AHU
204 Classroom 48 3 816 18 3 1 Univent & 1 AHU
205 Classroom 96 6 816 18 6 1 Univent & 1 AHU
206 Classroom 198 13 816 18 13 1 Univent & 1 AHU
207 Classroom 199 13 816 18 13 1 Univent & 1 AHU
208 Classroom 69 4 816 18 4 1 Univent & 1 AHU
209 Classroom 186 12 816 18 12 1 Univent & 1 AHU
210 Classroom 91 6 792 18 6 1 Univent & 1 AHU
211 Classroom 191 12 675 15 12 1 Univent & 1 AHU
212 Classroom 62 4 624 14 4 1 Univent & 1 AHU
213 Classroom 150 10 675 15 10 1 Univent & 1 AHU
214 Classroom 67 4 775 17 4 1 Univent & 1 AHU
215 Classroom 90 6 675 15 6 1 Univent & 1 AHU
216 Classroom 44 2 689 15 2 1 Univent & 1 AHU
217 Classroom 74 4 684 15 4 1 Univent & 1 AHU
218 Classroom 64 4 684 15 4 1 Univent & 1 AHU
219 Classroom 163 10 768 17 10 1 Univent & 1 AHU
220 Classroom 42 2 768 17 2 1 Univent & 1 AHU
221 Classroom 68 4 768 17 4 1 Univent & 1 AHU
222 Classroom 37 2 768 17 2 Univent
223 Classroom 417 27 768 17 17 1 Univent & 1 AHU
224 Classroom 69 4 768 17 4 1 Univent & 1 AHU
225 Classroom 136 9 768 17 9 1 Univent & 1 AHU
226 Classroom 63 4 816 18 4 1 Univent & 1 AHU
227 Classroom 125 8 744 16 8 1 Univent & 1 AHU
228 Classroom 58 3 744 16 3 1 Univent & 1 AHU
301 Classroom 121 8 816 18 8 1 Univent & 1 AHU
302 Classroom 98 6 816 18 6 1 Univent & 1 AHU
303 Classroom 69 4 816 18 4 Univent
304 Classroom 97 6 816 18 6 1 Univent & 1 AHU
305 Classroom 69 4 816 18 4 Univent
306 Classroom 132 8 816 18 8 1 Univent & 1 AHU
307 Classroom 172 11 816 18 11 1 Univent & 1 AHU
308 Classroom 95 6 816 18 6 1 Univent & 1 AHU
309 Classroom 238 15 816 18 15 1 Univent & 1 AHU
310 Classroom 210 14 792 18 14 1 Univent & 1 AHU
311 Classroom 153 10 675 15 10 1 Univent & 1 AHU
312 Classroom 103 6 624 14 6 1 Univent & 1 AHU
313 Classroom 69 4 675 15 4 Univent
314 Classroom 100 6 775 17 6 1 Univent & 1 AHU
315 Classroom 198 13 675 15 13 1 Univent & 1 AHU
316 Classroom 97 6 689 15 6 1 Univent & 1 AHU
317 Classroom 106 7 684 15 7 1 Univent & 1 AHU
318 Classroom 96 6 684 15 6 1 Univent & 1 AHU
319 Classroom 139 9 757 17 9 1 Univent & 1 AHU
320 Classroom 106 7 768 17 7 1 Univent & 1 AHU
321 Classroom 101 6 768 17 6 1 Univent & 1 AHU
322 Classroom 160 10 768 17 10 1 Univent & 1 AHU
323 Classroom 104 6 768 17 6 1 Univent & 1 AHU
324 Classroom 99 6 768 17 6 1 Univent & 1 AHU
325 Classroom 180 12 768 17 12 1 Univent & 1 AHU
326 Classroom 94 6 816 18 6 1 Univent & 1 AHU
327 Classroom 120 8 744 16 8 1 Univent & 1 AHU
328 Classroom 252 16 744 16 16 1 Univent & 1 AHU
503 Classroom 180 12 714 16 12 1 Univent & 1 AHU
504 Classroom 252 16 849 19 16 AHU
505 Classroom 149 9 1456 33 9 1 Univent & 1 AHU
507 Classroom 217 14 1458 33 14 1 Univent & 1 AHU
508 Classroom 149 9 765 17 9 Univent
509 Classroom 204 13 738 16 13 1 Univent & 1 AHU
510 Classroom 205 13 848 19 13 1 Univent & 1 AHU
511 Classroom 226 15 740 16 15 1 Univent & 1 AHU
512 Classroom 196 13 833 18 13 1 Univent & 1 AHU
- Auditorium  1,643 109 8015 182 109
- Basement / Cafe 62 4 5900 134 4
- cubicle-1 48 3 437 9 3
- GYM  2,494 166 2633 59 59
- library 288 19 2675 60 19
- mail room 24 1 153 3 1
- Link Main Office 201 13 809 18 13
- Clemente Main Office  24 1 240 5 1
Sheet Last Modified: 04-01-2021      
School:  Cleveland  
       
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
109 - 0 Yes 850 19 19
110 - 0 Yes 840 19 19
Sheet Last Modified: 04-19-2021    
School:  Benjamin B. Comegys Elementary School House fan Abated
Vendor: Devine EMCOR  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
K-1 Classroom  418 27 2240 50 27 Unit Ventilator
K-2 Classroom  462 30 2240 50 30 Unit Ventilator
100 Classroom  366 24 864 19 19 Unit Ventilator
101 Classroom  369 24 832 18 18 Unit Ventilator
103 Classroom  273 18 864 19 18 Unit Ventilator
104 Classroom  0 0 Yes 576 13 13 Unit Ventilator
105 Classroom  231 15 864 19 15 Unit Ventilator
106 Classroom  710 47 672 15 15 Unit Ventilator
200 Classroom  251 16 672 15 15 Unit Ventilator
201 Classroom  0 0 Yes 365 8 8 Radiator 
202 Classroom  371 24 672 15 15 Unit Ventilator
203 Classroom  1226 81 672 15 15 Unit Ventilator
204 Classroom  426 28 672 15 15 Unit Ventilator
205 Classroom  366 24 672 15 15 Unit Ventilator
206 Classroom  320 21 672 15 15 Unit Ventilator
207 Classroom  0 0 Yes 728 16 16 Unit Ventilator
208 Classroom  283 18 728 16 16 Unit Ventilator
209 Classroom  288 19 728 16 16 Unit Ventilator
210 Classroom  303 20 728 16 16 Unit Ventilator
211 Classroom  272 18 728 16 16 Unit Ventilator
212 Classroom  135 9 728 16 9 Unit Ventilator
213 Classroom  913 60 728 16 16 Unit Ventilator
214 Classroom  446 29 728 16 16 Unit Ventilator
300 Classroom  226 15 728 16 15 Unit Ventilator
301 Classroom  254 16 728 16 16 Unit Ventilator
302 Classroom  322 21 728 16 16 Unit Ventilator
303 Classroom  213 14 728 16 14 Unit Ventilator
304 Classroom  0 0 Yes 728 16 16 Unit Ventilator
305 Classroom  858 57 728 16 16 Unit Ventilator
306 Classroom  883 58 728 16 16 Unit Ventilator
307 Classroom  209 13 728 16 13 Unit Ventilator
- Art Classroom 385 25 616 14 14 Unit Ventilator
- Main Office 0 Yes 936 21 21 Radiator 
- Principal Office 0 Yes 360 8 8 Radiator 
- Counselor Office 0 Yes 391 8 8 Radiator 
- Nurse Office 0 Yes 280 6 6 Radiator 
- Auditorium 271 18 4320 98 18 AHU
- Gym / Cafe 477 31 3672 83 31 AHU
Sheet Last Modified: 04-29-2021        
School:  Watson Comly Elementary School House fan Abated
Vendor: Emcor Fluidics 2nd Retest 3rd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 Yes 690 15 15 House Fan
102 Classroom 0 Yes 690 15 15 House Fan
102A Classroom 0 155 3 0 House Fan
103 Classroom 0 Yes 690 15 15 House Fan
103A Classroom 0 164 3 0 House Fan
104 Classroom 0 Yes 690 15 15 House Fan
105 Classroom 555 37 910 20 20 Unit Ventilator
106 Classroom 581 38 910 20 20 Unit Ventilator
107 Classroom 609 40 910 20 20 Unit Ventilator
108 Classroom 0 Yes 910 20 20 Unit Ventilator
110 (ESOL) Classroom 0 Yes 439 9 9
201 Classroom 0 Yes 435 9 9
201A Classroom 0 Yes 306 6 6 House Fan
202 Classroom 0 Yes 690 15 15 House Fan
203 Classroom 0 Yes 690 15 15 House Fan
204 Classroom 0 Yes 690 15 15 House Fan
205 Classroom 0 Yes 690 15 15 Unit Ventilator
206 Classroom 0 Yes 936 21 21 Unit Ventilator
207 Classroom 0 Yes 936 21 21 Unit Ventilator
208 Classroom 0 Yes 936 21 21 Unit Ventilator
209 Classroom 0 Yes 936 21 21 Unit Ventilator
210 Classroom 0 Yes 812 18 18 Unit Ventilator
211 Classroom 147 9 812 18 9 Unit Ventilator
212 Classroom 199 13 Yes 812 18 18 Unit Ventilator
213 Classroom 197 13 812 18 13 Unit Ventilator
214 Classroom 156 10 Yes 812 18 18 Unit Ventilator
215 Classroom 510 34 812 18 18 Unit Ventilator
216 Classroom 385 25 812 18 18 Unit Ventilator
Art 1st Fl Art Room 342 22 1672 38 22 Unit Ventilator
- Art Teacher Office 205 13 308 7 7 MUA
- Special Needs Room 335 22 812 18 18 Unit Ventilator
- Music Room 383 25 594 13 13 Unit Ventilator
- Office - Main 183 12 169 3 3 Unit Ventilator
- Office-2 0 176 4 0
- 2nd Floor Counselors Office 0 Yes 182 4 4
- Counslor waiting rm 0 104 2 0
- Conference room 1st floor 0 338 7 0
- Amy's Room 0 156 3 0
- Principals Office 0 0 Yes 196 4 4 N/A
- Break Room 0 0 390 8 0 N/A
- 2nd Floor Staff room 0 170 3 0
- Nurse 1st  Floor 90 6 150 3 3 MUA
- Nurse Office 125 8 344 7 7 MUA
- Nurse waiting 0 Yes 202 4 4
- Cafeteria 0 Yes 3321 75 75
- Gym 0 4838 109 0
Sheet Last Modified: 04-20-2021    
School:  Russell Conwell Middle School / Conwell Annex
     
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Conwell Main Building
B1 - 0 1,575 35 0
B2 - 0 782 17 0
Main Office Office 0 Yes 396 9 9
Nurse Office 0 Yes 473 10 10
102 - 0 575 13 0
107 - 0 120 2 0
108 - 0 Yes 816 18 18
109 - 0 Yes 850 19 19
111 - 0 Yes 1,200 27 27
103/104/ IMC - 0 4,300 97 0
201 - 0 850 19 0
202 - 0 840 19 0
204 - 0 625 14 0
205 - 0 550 12 0
206 - 0 875 19 0
207 - 0 900 20 0
208 - 0 805 18 0
209 - 0 Yes 850 19 19
301 - 0 Yes 720 16 16
302 - 0 805 18 0
303 - 0 550 12 0
304 - 0 625 14 0
305 - 0 506 11 0
306 - 0 875 19 0
307 - 0 900 20 0
308 - 0 805 18 0
309 - 0 Yes 575 13 13
Conwell Annex
1 - 0 1,276 29 0
9 - 0 1,200 27 0
102 - 0 2,318 52 0
104 - 0 870 19 0
203 - 0 4,800 109 0
200 - 0 512 11 0
301 - 0 840 19 0
305 - 0 630 14 0
306 - 0 768 17 0
 
Sheet Last Modified: 04-29-2021    
School:  Cook-Wissahickon Elementary-Middle School
Vendor: Devine Devine Retest Capital
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 310 20 695 15 15 Unit Ventilator
2 Classroom 280 18 950 21 18 Unit Ventilator
3 Classroom 443 29 513 11 11 Unit Ventilator
15 - 131 8 0 0 Unit Ventilator
016A - 131 8 0 0 Unit Ventilator
101 Classroom 341 22 717 16 16 Unit Ventilator
102 Classroom 694 46 700 15 15 Unit Ventilator
103 Classroom 0 0 1495 33 0 Unit Ventilator
105 Classroom 337 22 1005 22 22 Unit Ventilator
106 Classroom 342 22 924 21 21 Unit Ventilator
107 Classroom 327 21 630 14 14 Unit Ventilator
108 Classroom 352 23 441 10 10 Unit Ventilator
109 Classroom 585 39 851 19 19 Unit Ventilator
110 Classroom 280 18 674 15 15 Unit Ventilator
111 Classroom 285 19 386 8 8 Unit Ventilator
200 Classroom 366 24 636 14 14 Unit Ventilator
200A Classroom 324 21 485 11 11 Unit Ventilator
201 Classroom 310 20 447 10 10 Unit Ventilator
202 Classroom 418 27 730 16 16 Unit Ventilator
203 Classroom 0 0 813 18 0 Unit Ventilator
204 Classroom 326 21 867 19 19 Unit Ventilator
205 Classroom 401 26 716 16 16 Unit Ventilator
206 Classroom 0 0 810 18 0 Unit Ventilator
207 Classroom 284 18 456 10 10 Unit Ventilator
208 Classroom 336 22 422 9 9 Unit Ventilator
209 Classroom 300 20 731 16 16 Unit Ventilator
210 Classroom 315 21 731 16 16 Unit Ventilator
211 Classroom 0 0 872 19 0 Unit Ventilator
212 Classroom 440 29 365 8 8 Unit Ventilator
213 Room 310 20 525 11 11 Air Handling Unit
- Cafeteria 2213 147 0 0 Air Handling Unit
- Copy Room 340 22 199 4 4 Air Handling Unit
- Gymnasium 1486 99 4325 98 98 Air Handling Unit
- Library 1180 78 2998 68 68 Air Handling Unit
- Main Office 789 52 396 9 9 Air Handling Unit
- Pricipal's office 498 33 358 8 8 Air Handling Unit
- Speech Room 330 22 358 8 8 Air Handling Unit
- Prep and lounge 0 602 13 0
Sheet Last Modified: 04-26-2021        
School:  Jay Cooke Elementary School House Fan Abated
Vendor: Devine Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100C Classroom 293 19 506 11 11 House Fan
101C Classroom 411 27 543 12 12 House Fan
102C Classroom 284 18 833 18 18 House Fan
103 Classroom 531 35 1082 24 24 House Fan
104 Classroom 279 18 809 18 18 House Fan
105 Classroom 369 24 695 15 15 House Fan
108 Classroom 328 21 858 19 19 House Fan
109 Office 313 20 548 12 12 House Fan
110 Classroom 422 28 665 15 15 House Fan
110A Office 335 22 333 7 7 House Fan
201 Classroom 335 22 711 16 16 House Fan
202 Classroom 515 34 674 15 15 House Fan
202A Classroom 347 23 1015 23 23 House Fan
203 Classroom 388 25 717 16 16 House Fan
205 Office 0 0 304 6 0 House Fan(partial Duct)
206 Office 0 0 Yes 240 5 5 House Fan(partial Duct)
207 Classroom 435 29 726 16 16 House Fan
207A Classroom 330 22 334 7 7 House Fan
208 Classroom 433 28 673 15 15 House Fan
208A Storage 279 18 720 16 16
209 Classroom 363 24 693 15 15 House Fan
210 Classroom 378 25 650 14 14 House Fan
211 Classroom 748 49 211 4 4 House Fan
212 Classroom 736 49 774 17 17 House Fan
213 Classroom 807 53 720 16 16 House Fan
214 Classroom 846 56 727 16 16 House Fan
215 Classroom 797 53 748 17 17 House Fan
216 Classroom 811 54 762 17 17 House Fan
217 Classroom 496 33 670 15 15 House Fan
301 Classroom 278 18 711 16 16 House Fan
302 Classroom 522 34 690 15 15 House Fan
302A Classroom 273 18 405 9 9 House Fan
303 Classroom 581 38 714 16 16 House Fan
303A Classroom 284 18 Yes 405 9 9 House Fan
303B Classroom 0 0 Yes 216 4 4
304 Classroom 633 42 882 20 20 House Fan
305 Classroom 437 29 907 20 20 House Fan
306 Classroom 456 30 815 18 18 House Fan
307 Classroom 541 36 798 18 18 House Fan
308 Classroom 469 31 1031 23 23 House Fan
309 Classroom 456 30 896 20 20 House Fan
310 Classroom 441 29 769 17 17 House Fan
311 Classroom 617 41 985 22 22 House Fan
312 Classroom 333 22 713 16 16 House Fan
312A Classroom 325 21 332 7 7 House Fan
313 Classroom 393 26 666 15 15 House Fan
313A Classroom 307 20 703 15 15 House Fan
314 Classroom 365 24 709 16 16 House Fan
315 Classroom 271 18 650 14 14 House Fan
316 Classroom 673 44 765 17 17 House Fan
317 Classroom 278 18 729 16 16 House Fan
318 Classroom 744 49 730 16 16 House Fan
319 Classroom 656 43 719 16 16 House Fan
320 Classroom 764 50 700 15 15 House Fan
321 Classroom 480 32 787 17 17 House Fan
322 Classroom 353 23 653 14 14 House Fan
- Asst. Principal Waiting Room 125 8 118 2 2 House Fan
- Asst. Principal Office 0 Yes 110 2 2
- Auditorium 3875 258 3793 86 86 House Fan
- Boy's Cafeteria 1403 93 2254 51 51 House Fan
- Boy's Gym 1455 97 2806 63 63 House Fan
- Counselor Waiting Room 134 8 123 2 2 House Fan
- Counselor Office 1 0 0 Yes 92 2 2 House Fan
- Counselor Office 2 0 0 101 2 0 House Fan
- Counselor Office 3 0 0 156 3 0
- Girl's Cafeteria 1178 78 1944 44 44 House Fan
- Girl's Gym 1461 97 2806 63 63 House Fan
- Kitchen 321 21 409 9 9 House Fan
- Library 1042 69 2053 46 46 House Fan
- Nurse Office 53 3 Yes 186 4 4 House Fan
- Principal Office 141 9 336 7 7 House Fan
- Weight Room 842 56 1027 23 23 House Fan
- CASST Office 0 0 Yes 264 6 6
- SPECM Speech Therapy Office 0 0 112 2 0
Sheet Last Modified: 04-29-2021    
School:  William Cramp Elementary School
Vendor: Devine Brothers Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
102 Office 27 1 133 3 1
102A Office 20 1 133 3 1
103 Small Classroom 103 6 533 12 6
106 Classroom 387 25 1033 23 23 Unit Ventilator
107 Counselor 137 9 385 8 8
108 Classroom 148 9 Yes 1220 27 27 Unit Ventilator
109 Classroom 405 27 1120 25 25 Unit Ventilator
110 Classroom 277 18 1543 35 18 Unit Ventilator
111 Classroom 318 21 1228 27 21 Unit Ventilator
112 Classroom 498 33 1170 26 26
112E Office 29 1 200 4 1
113 Classroom 338 22 1311 29 22 Unit Ventilator
13A Classroom 307 20 1073 24 20
13B Classroom 500 33 1294 29 29 Unit Ventilator
114 Art 385 25 876 19 19 AHU
115 Classroom 283 18 1559 35 18
119 Office 0 0 459 10 0
200 Classroom 763 50 967 21 21 Unit Ventilator
201 Classroom 605 40 825 18 18 Unit Ventilator
202 Counselor 26 1 151 3 1
203/212 Speech 27 1 151 3 1
204 Classroom 527 35 1050 23 23 Unit Ventilator
205 Classroom 128 8 902 20 8 Unit Ventilator
206 Classroom 437 29 1030 23 23 Unit Ventilator
207 Classroom 440 29 971 22 22 Unit Ventilator
208 Classroom 544 36 950 21 21 Unit Ventilator
209 Classroom 438 29 897 20 20 Unit Ventilator
210 Classroom 462 30 967 21 21 Unit Ventilator
211 Classroom 118 7 976 22 7 Unit Ventilator
300 Classroom 782 52 866 19 19 Unit Ventilator
301 Classroom 675 45 982 22 22 Unit Ventilator
302 Counselor 42 2 151 3 2
303/312 Office 48 3 151 3 3
304 Classroom 133 8 1050 23 8 Unit Ventilator
304 Classroom 330 22 1050 23 22
305 Classroom 393 26 968 22 22 Unit Ventilator
306 Classroom 122 8 855 19 8 Unit Ventilator
306 Classroom 501 33 855 19 19
307 Classroom 713 47 965 21 21 Unit Ventilator
308 Classroom 320 21 772 17 17 Unit Ventilator
309 Classroom 471 31 941 21 21 Unit Ventilator
310 Classroom 327 21 972 22 21 Unit Ventilator
311 Classroom 421 28 896 20 20 Unit Ventilator
313 Classroom 329 21 368 8 8 Unit Ventilator
- Gym 42 2 4800 109 2 AHU
- LGI 736 49 697 15 15 AHU
- Admin Office 827 55 251 5 5 AHU
- Cafeteria 630 42 7287 165 42 AHU
- Computer Lab 498 33 2840 64 33 Unit Ventilator
- Computer Room 1015 67 2437 55 55 AHU
- Conference/Storage 110 7 199 4 4
- IMC Office 40 2 141 3 2
- IMC Library 36 2 2456 55 2
- Kitchen 1510 100 972 22 22
- Library North Classroom 537 35 2635 59 35 Unit Ventilator
- Library South Classroom 443 29 362 8 8 Unit Ventilator
- Mail Room 47 3 133 3 3
- Main Office 113 7 571 12 7
- Nurse Office 109 7 374 8 7
- Nurse Exam Room 44 2 128 2 2
- Principals Office 60 4 258 5 4
- Teachers Lounge 354 23 775 17 17
- Vice Principal's Office 64 4 213 4 4
Sheet Last Modified: 04-05-2021    
School:  Kenneth C. Crossan Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Kindergarten Classroom 580 38 1088 24 24 House Fan
2 Classroom 555 37 900 20 20 House Fan
3 Classroom 522 34 930 21 21 House Fan
4 Classroom 299 19 840 19 19 House Fan
5 Kindergarten Classroom 0 Yes 900 20 20
5 Classroom 505 33 600 13 13 House Fan
6 Classroom 820 54 805 18 18 House Fan
7 Computer Classrm. 437 29 900 20 20 House Fan
8 Classroom 580 38 1094 24 24 House Fan
9 Classrom 444 29 840 19 19 House Fan
9A Teachers Rm. 0 0 Yes 450 10 10 N/A
10 Classroom 822 54 600 13 13
11 Classroom 466 31 720 16 16 House Fan
12 Classroom 606 40 720 16 16 House Fan
13 Classroom 626 41 720 16 16 House Fan
- Auditorium 1,107.00 73 2760 62 62 House Fan
- Cafeteria/Gym 0 0 2300 52 0 N/A
- Counselors Rm. 0 0 Yes 450 10 10 N/A
- Grnd. Fl. Boys Bathrm. 568 37 736 16 16 House Fan
- Grnd. Fl. Girls Bathrm. 620 41 775 17 17 House Fan
- Ind. Arts Classroom 0 0 600 13 0 N/A
- Library 525 35 1152 26 26 House Fan
- Main Office 0 0 Yes 460 10 10 N/A
- Nurse Office 0 Yes 450 10 10
- Art Room 0 Yes 600 13 13
- Principal's Ofice 0 0 450 10 0 N/A
Sheet Last Modified: 04-29-2021    
School:  Anne Blakiston Day Elementary School
Vendor: EMCOR / Chadwick
School:  Anne Blakiston Day Elementary School- Little School House
Vendor: Chadwick Part 2 and Exhaust Exhaust
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Anna Blakiston Day Elementary School- Main Building
101 classroom 186 12 Yes 880 20 20 Unit Ventilator
102 classroom 194 12 Yes 880 20 20 Unit Ventilator
103 classroom 45 3 Yes 880 20 20 Unit Ventilator
104 classroom 75 5 Yes 1440 32 32 Unit Ventilator
105 classroom 126 8 Yes 880 20 20 Unit Ventilator
106 classroom 0 0 Yes 880 20 20 Unit Ventilator
107 classroom 210 14 Yes 880 20 20 Unit Ventilator
108 classroom 0 0 Yes 880 20 20 Unit Ventilator
109 classroom 0 Yes 880 20 20
111 Classroom 0 Yes 880 20 20
112 Classroom 0 Yes 260 5 5
201 classroom 255 17 Yes 875 19 19 Unit Ventilator
202 classroom 257 17 Yes 880 20 20 Unit Ventilator
203 classroom 0 0 Yes 880 20 20 Unit Ventilator
204 classroom 365 24 Yes 880 20 20 Unit Ventilator
205 classroom 0 0 Yes 880 20 20 Unit Ventilator
206 classroom 84 5 Yes 880 20 20 Unit Ventilator
207 classroom 0 0 Yes 575 13 13 Unit Ventilator
208 classroom 47 3 Yes 880 20 20 Unit Ventilator
209 classroom 235 15 Yes 880 20 20 Unit Ventilator
210 classroom 0 0 Yes 880 20 20 Unit Ventilator
211 classroom 244 16 Yes 880 20 20 Unit Ventilator
214 Classroom 0 Yes 228 5 5
- Auditorium 0 0 3300 75 0 AHU
- GYM 573 38 5000 113 38 AHU
- Library 0 0 2700 61 0 RTU
Anna Blakiston Day Elementary School- Little School House
1 classroom 322.0 21 1056 24 21 AHU
2 classroom 274 18 1056 24 18 AHU
3 classroom 322.0 21 1056 24 21 AHU
4 classroom 510 34 1056 24 24 AHU
5 classroom 302.0 20 1056 24 20 AHU
6 classroom 325.0 21 1056 24 21 AHU
7 classroom 302.0 20 1056 24 20 AHU
8 classroom 325.0 21 1056 24 21 AHU
9 classroom 302.0 20 1056 24 20 AHU
10 classroom 325.0 21 1056 24 21 AHU
11 classroom 302.0 20 1056 24 20 AHU
12 classroom 325.0 21 1056 24 21 AHU
- Lunchroom 1,136.0 75 1750 39 39 AHU
- Staff Bathroom Staff Toilet 159.0 10 120 2 2 N/A
- Staff Bathroom Staff Toilet  277.0 18 120 2 2 N/A
- Various Office 392.0 26 0 0 AHU
- Corridor 224.0 14 0 0 FCU
- Various Storage  374.0 24 0 0 AHU
Sheet Last Modified: 04-21-2021    
School:  Julia deBurgos Elementary School
Vendor: Chadwick Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
108 storage  0 100 2 0 AHU-1
111 work rm 0 100 2 0 AHU-1
115 office  100 6 150 3 3 AHU-1
116 classroom 281 18 658 14 14 Univent 
118 classroom 0 400 9 0 AHU-1
120 classroom 380 25 759 17 17 Univent 
121 classroom 288 19 759 17 17 Univent 
123 classroom 486 32 759 17 17 Univent 
125 classroom 307 20 759 17 17 Univent 
129 classroom 335 22 640 14 14 Univent 
130 classroom 295 19 672 15 15 Univent 
132 classroom 470 31 704 16 16 Univent 
133 classroom 345 23 880 20 20 Univent 
134 classroom 301 20 667 15 15 AHU-5
135 classroom 552 36 750 17 17 Univent 
136 classroom 291 19 750 17 17 Univent 
138 classroom 734 48 748 17 17 AHU-5
139 classroom 0 0 Yes 704 16 16 AHU-5
139B PRACTICE RM  0 0 100 2 0 AHU-5
139C PRACTICE RM  0 0 100 2 0 AHU-5
148 office  244 16 350 7 7 AHU-5
148A office  130 8 100 2 2 AHU-5
148B office  54 3 110 2 2 AHU-5
148C office  37 2 100 2 2 AHU-5
148D office  51 3 100 2 2 AHU-5
148E office  67 4 100 2 2 AHU-5
148F office  89 5 100 2 2 AHU-5
148G office  44 2 100 2 2 AHU-5
148H office  26 1 100 2 1 AHU-5
148I office  64 4 100 2 2 AHU-5
148L office  126 8 242 5 5 AHU-5
149 office  59 3 100 2 2 AHU-5
- Nurse Office 0 Yes 180 4 4 AHU-5
151 WAITING RM  22 1 Yes 180 4 4 AHU-5
151A OFFICE  0 0 110 2 0 AHU-5
151B OFFICE  17 1 150 3 1 AHU-5
151C OFFICE  17 1 80 1 1 AHU-5
151E OFFICE  0 0 100 2 0 AHU-5
152f office  39 2 99 2 2 AHU-5
152g office  47 3 99 2 2 AHU-5
152h office  0 0 208 4 0 AHU-5
152j office  178 11 288 6 6 AHU-5
152k office  160 10 368 8 8 AHU-5
202 classroom 608 40 759 17 17 Univent 
203 classroom 481 32 759 17 17 Univent 
207 classroom 310 20 1081 24 20 Univent 
208 classroom 331 22 621 14 14 Univent 
211 classroom 300 20 759 17 17 Univent 
212 classroom 405 27 759 17 17 Univent 
213 classroom 345 23 759 17 17 Univent 
215 office 385 25 675 15 15 AHU-1
218 classroom 720 48 759 17 17 Univent 
220 classroom 360 24 759 17 17 Univent 
221 classroom 310 20 759 17 17 Univent 
225 classroom 413 27 759 17 17 Univent 
226 classroom 328 21 759 17 17 Univent 
228 classroom 345 23 759 17 17 Univent 
229 classroom 300 20 759 17 17 Univent 
230 classroom 345 23 1196 27 23 Univent 
236 classroom 83 5 494 11 5 AHU-5
236A STORAGE  150 10 171 3 3 AHU-5
236B OFFICE 0 0 171 3 0 AHU-5
237B STORAGE  37 2 165 3 2 AHU-5
237C OFFICE 63 4 165 3 3 AHU-5
238 classroom 442 29 759 17 17 Univent 
239 classroom 284 18 759 17 17 Univent 
302 classroom 430 28 1081 24 24 Univent 
306 classroom 289 19 526 11 11 Univent 
307 classroom 299 19 621 14 14 Univent 
308 classroom 285 19 504 11 11 Univent 
310 classroom 320 21 759 17 17 Univent 
311 classroom 365 24 759 17 17 Univent 
312 classroom 325 21 759 17 17 Univent 
313 office 453 30 675 15 15 AHU-1
316 classroom 345 23 759 17 17 Univent 
317 classroom 380 25 759 17 17 Univent 
319 classroom 307 20 989 22 20 Unit Ventilator
319A storage 233 15 367 8 8 Unit Ventilator
323 classroom 336 22 759 17 17 Univent 
324 classroom 384 25 759 17 17 Univent 
326 classroom 423 28 759 17 17 Univent 
327 classroom 453 30 759 17 17 Univent 
328 classroom 425 28 759 17 17 Univent 
335 STUDIO  389 25 798 18 18 AHU-8
336 classroom 366 24 759 17 17 Univent 
337 classroom 375 25 759 17 17 Univent 
- BOYS LOCKER ROOM 80 5 143 3 3 AHU-5
- FRONT IMC LIBRARY 118 7 171 3 3 AHU-5
- GIRLS LOCKER ROOM 84 5 143 3 3 AHU-5
- GYM OFFICE  41 2 225 5 2 AHU-5
- LIBRARY  892 59 3276 74 59 AHU-8
- Mail Room 159 10 200 4 4 AHU-5
- Main Office  618 41 924 21 21 AHU-5
- Principal Office 208 13 324 7 7 AHU-5
- Staff Locker Room 0 70 1 0 AHU-1
- Storage Office  38 2 100 2 2 AHU-5
- Cafeteria  4,650 310 6020 136 136 AHU-2
- Gym 3,322 221 5904 134 134 ahu-6
- Auditorium 3,405 227 2983 67 67 AHU-7
Sheet Last Modified: 04-27-2021      
School:  Stephen Decatur Elementary School
  Stephen Decatur Elementary School Annex
  Stephen Decatur Elementary School White Building
Vendor: EMCOR Devine Brothers Devine Retest Emcor Retest 2-15     
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Decatur Main Building
K-1 classroom 283 18 1450 32 18 Unit Ventilator
K-2 classroom 375 25 1450 32 25 Unit Ventilator
100 classroom 329 21 897 20 20 Unit Ventilator
101 classroom 271 18 805 18 18 Unit Ventilator
102 classroom 228 15 897 20 15 Unit Ventilator
103 classroom 253 16 805 18 16 Unit Ventilator
104 classroom 240 16 897 20 16 Unit Ventilator
105 classroom 321 21 805 18 18 Unit Ventilator
106 Nurse's Office 0 Yes 357 8 8 N/A
107 classroom 326 21 805 18 18 Unit Ventilator
108 classroom 322 21 897 20 20 Unit Ventilator
109 classroom 326 21 851 19 19 Unit Ventilator
110 classroom 301 20 702 15 15 Unit Ventilator
200 Classroom 352 23 805 18 18 Unit Ventilator
201 Classroom 0 Yes 805 18 18
202 Classroom 0 Yes 805 18 18
203 Classroom 234 15 854 19 15 Unit Ventilator
204 Classroom 0 Yes 805 18 18
205 Classroom 0 Yes 805 18 18
206 Classroom 0 Yes 805 18 18
208 Classroom 301 20 805 18 18 Unit Ventilator
210 Classroom 242 16 805 18 16 Unit Ventilator
212 Classroom 0 Yes 805 18 18
214 Classroom 247 16 391 8 8 Unit Ventilator
216/218 Classroom 599 39 1702 38 38 Unit Ventilator
217 Classroom 283 18 1352 30 18 Unit Ventilator
219 Classroom 274 18 798 18 18 Unit Ventilator
220 Classroom 184 12 Yes 865 19 19 Unit Ventilator
300 Classroom 0 Yes 910 20 20
301 Classroom 0 Yes 900 20 20
302 Classroom 0 Yes 900 20 20
303 Classroom 0 Yes 900 20 20
304 Classroom 0 Yes 900 20 20
305 Classroom 0 Yes 900 20 20
306 Classroom 0 Yes 900 20 20
308 Classroom 0 Yes 900 20 20
310 Classroom 0 Yes 910 20 20
312 Classroom 277 18 391 8 8 Unit Ventilator
314 Classroom 241 16 397 9 9 Unit Ventilator
316 Classroom 238 15 851 19 15 Unit Ventilator
317 Classroom 0 Yes 910 20 20
318 Classroom 0 Yes 850 19 19
319 Classroom 0 Yes 910 20 20
320 Classroom 0 Yes 910 20 20
- AP N/A 0 126 2 0 N/A
- Auditorium 675 45 2800 63 45 AHU
- Basement 0 0 456 10 0 N/A
B-1 - 0 Yes 731 16 16 Unit Ventilator
B-2 Counselors 356 23 875 19 19 Unit Ventilator
- Dean N/A 0 126 2 0 N/A
- ESOL 275 18 750 17 17 Unit Ventilator
- GYM 1543 102 4108 93 93 AHU
- IMC 301 20 1404 31 20 RTU
- Main Office 360 24 999 22 22 Unit Ventilator
- Cafeteria 0 0 Yes 6161 140 140 Unit Ventilator
Decatur Annex
A-1 classroom 335 22 875 19 19 Unit Ventilator
A-2 classroom 294 19 899 20 19 Unit Ventilator
A-3 classroom 329 21 874 19 19 Unit Ventilator
A-4 classroom 285 19 852 19 19 Unit Ventilator
A-5 classroom 326 21 861 19 19 Unit Ventilator
A-6 classroom 322 21 789 17 17 Unit Ventilator
A-7 classroom 317 21 899 20 20 Unit Ventilator
A-8 classroom 332 22 832 18 18 Unit Ventilator
A-9 classroom 288 19 879 19 19 Unit Ventilator
A-10 classroom 281 18 888 20 18 Unit Ventilator
Decatur White Building
1 classroom 315 21 875 19 19 Unit Ventilator
2 classroom 241 16 888 20 16 Unit Ventilator
3 classroom 340 22 878 19 19 Unit Ventilator
4 classroom 284 18 845 19 18 Unit Ventilator
Sheet Last Modified: 04-29-2021    
School:  William Dick Elementary School
Vendor: EMCOR Exhaust Report Retest Report
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 355 23 963 21 21 Unit Ventilator
102 Classroom 319 21 963 21 21 Unit Ventilator
103 Nurses Office 0 Yes 825 18 18
104 Classroom 481 32 1036 23 23 Unit Ventilator
105 Office 0 0 Yes 4046 91 91 Unit Ventilator
105-A Principal's Office 0 Yes 280 6 6
106 Small room 0 Yes 303 6 6
107 Classroom 328 21 1050 23 21 Unit Ventilator
108 Classroom 167 11 1055 23 11 Unit Ventilator
109 Classroom 237 15 Yes 1048 23 23 Unit Ventilator
111 Classroom 176 11 Yes 1272 28 28 Unit Ventilator
112 Classroom 345 23 1275 28 23 Unit Ventilator
200 Room 0 Yes 133 3 3
201 Classroom 356 23 747 16 16 Unit Ventilator
202 Classroom 286 19 1051 23 19 Unit Ventilator
203 Classroom 158 10 Yes 1052 23 23 Unit Ventilator
204 Classroom 142 9 Yes 1035 23 23 Unit Ventilator
205 Classroom 191 12 Yes 1057 24 24 Unit Ventilator
207 Classroom 199 13 Yes 1009 22 22 Unit Ventilator
208 Classroom 207 13 Yes 1049 23 23 Unit Ventilator
209 Classroom 317 21 1055 23 21 Unit Ventilator
211 Classroom 286 19 1049 23 19 Unit Ventilator
212 Classroom 344 22 1048 23 22 Unit Ventilator
213 Classroom 235 15 Yes 1049 23 23 Unit Ventilator
214 Classroom 119 7 Yes 1029 23 23 Unit Ventilator
300 Counselor's Office 0 Yes 164 3 3
301 Classroom 136 9 Yes 741 16 16 Unit Ventilator
302 Classroom 398 26 1053 23 23 Unit Ventilator
303 Library 241 16 Yes 1032 23 23 Unit Ventilator
304 Classroom 169 11 Yes 1049 23 23 Unit Ventilator
305 Classroom 330 22 1213 27 22 Unit Ventilator
307 Classroom 101 6 Yes 1057 24 24 Unit Ventilator
308 Classroom 133 8 Yes 1028 23 23 Unit Ventilator
309 Classroom 369 24 1048 23 23 Unit Ventilator
311 Classroom 406 27 1050 23 23 Unit Ventilator
312 Classroom 281 18 1046 23 18 Unit Ventilator
313 Classroom 53 3 Yes 1046 23 23 Unit Ventilator
314 Classroom 0 0 Yes 1047 23 23 Unit Ventilator
- Gymnasium 248 16 739 16 16 Unit Ventilator
- Auditorium 0 4436 100 0 AHU
- Building Engineer's Office 0 Yes 482 10 10
Sheet Last Modified: 04-03-2021    
School:  Hamilton Disston Elementary-Middle School
Vendor: Devine
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Mechanical Rm. 0 570 12 0 House Fan
B1 Cafeteria 1021 68 1680 38 38 House Fan
B2 Food Service 1059 70 816 18 18 House Fan
B3 Gym 0 0 Yes 3840 87 87 House Fan
- Gym Office 0 0 288 6 0 House Fan
B4 Classroom 0 0 Yes 1008 22 22 House Fan
B5 Classroom 1005 67 864 19 19 House Fan
B6 Classroom 768 51 984 22 22 House Fan
017B Basement Girls Bathroom 464 30 504 11 11 House Fan
011B Basement Boys Bathroom 271 18 528 12 12 House Fan
101 Classroom 545 36 816 18 18 House Fan
102 Classroom 764 50 720 16 16 House Fan
103 Classroom 821 54 864 19 19 House Fan
104 Classroom 593 39 766 17 17 House Fan
104A Office 0 0 Yes 168 3 3 House Fan
- Auditorium 3956 263 2784 63 63 House Fan
105 Classroom 635 42 766 17 17 House Fan
106 Classroom 403 26 864 19 19 House Fan
107 Classroom 574 38 720 16 16 House Fan
108 Classroom 593 39 816 18 18 House Fan
- Nurses Office 0 0 Yes 200 4 4 House Fan
201 Classroom 447 29 816 18 18 House Fan
202 Classroom 668 44 720 16 16 House Fan
203 Classroom 601 40 864 19 19 House Fan
203A Climate Office 0 0 Yes 280 6 6 House Fan
204 Classroom 548 36 816 18 18 House Fan
204A AP Office 0 0 180 4 0 House Fan
205 Classroom 301 20 816 18 18 House Fan
- Counselor's Office 0 0 Yes 260 5 5 House Fan
206 Classroom 570 38 864 19 19 House Fan
207 Classroom 421 28 720 16 16 House Fan
208 Classroom 281 18 816 18 18 House Fan
- Helping Hands Office 0 0 Yes 120 2 2 House Fan
301A Office 0 0 280 6 0 House Fan
301 Classroom 365 24 816 18 18 House Fan
302 Classroom 563 37 720 16 16 House Fan
303 Classroom 442 29 864 19 19 House Fan
304 Classroom 657 43 816 18 18 House Fan
305 Classroom 53 3 Yes 870 19 19 House Fan
306 Classroom 186 12 864 19 12 House Fan
307 Classroom 56 3 Yes 957 21 21 House Fan
308 Classroom 489 32 864 19 19 House Fan
309 Classroom 127 8 Yes 900 20 20 House Fan
310 Classroom 96 6 Yes 816 18 18 House Fan
311 Classroom 611 40 864 19 19 House Fan
312 Classroom 424 28 720 16 16 House Fan
313 Classroom 411 27 816 18 18 House Fan
313A Office 0 0 816 18 0 House Fan
- Library 747 49 2156 49 49 RTU-1
- Office 155 10 312 7 7 RTU-1
- Office 55 3 312 7 3 RTU-1
- Main Office 0 0 Yes 308 7 7 RTU-2
- Principal Office 0 0 160 3 0 RTU-2
- Faculty Lounge 0 0 312 7 0 RTU-2
- Modular Classroom 0 0 720 16 0 AHU
Sheet Last Modified: 04-19-2021    
School:  Murrell Dobbins Vocational High School
Vendor: Capital Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
016 B-5 Classroom 1,130 75 2511 57 57
016 B-6 Classroom 536 35 2511 57 35
016 B-7 Classroom 718 47 2424 55 47
016 B-8 Classroom 494 32 2543 57 32
120 Classroom 249 16 597 13 13
122-A Classroom 325 21 1226 27 21
122-B Classroom 391 26 1226 27 26
123-A Classroom 287 19 1445 32 19
123-B Classroom 0 0 1445 32 0
123C Classroom 0 0 136 3 0
123J Classroom 428 28 322 7 7
130 Classroom 284 18 1017 23 18
131-A Classroom 0 0 2226 50 0
131-B Classroom 458 30 2226 50 30
131-C Classroom 0 0 2226 50 0
131-D Classroom 232 15 2226 50 15
134 Classroom 0 0 596 13 0
201 Library/IMC 397 26 3115 70 26
220-A Classroom 760 50 435 9 9
220-B Classroom 452 30 210 4 4
220-C Classroom 398 26 210 4 4
220-D Classroom 411 27 308 7 7
222 Classroom 299 19 1228 27 19
223 Classroom 393 26 720 16 16
225 Classroom 394 26 735 16 16
227-A Classroom 505 33 871 19 19
227-B Classroom 335 22 871 19 19
231-A Classroom 0 0 1125 25 0
231-B Classroom 141 9 1125 25 9
233-A Classroom 371 24 2122 48 24
233-B Classroom 347 23 2122 48 23
233-C Classroom 319 21 2122 48 21
234 Classroom 0 0 771 17 0
236 Classroom 381 25 1030 23 23
236,234,233,
 232, & 231
Classrooms 6,741 449 792 18 18
- 2nd E/Center Corr 375 25 2310 52 25
- 2nd East Corr 312 20 2310 52 20
- 2nd W/Center Corr 292 19 2310 52 19
- 2nd West Corr 0 0 2310 52 0
300 Classroom 451 30 975 22 22
305,330,331,
 332, & 332A
Classrooms 7,434 495 792 18 18
315-A Classroom 300 20 1008 22 20
315-B Classroom 390 26 1008 22 22
317 Classroom 346 23 832 18 18
321,323,322,
 322A, &322B
Classrooms 5,053 336 792 18 18
322-A Classroom 0 0 3737 84 0
322-B Classroom 171 11 3737 84 11
322-C Classroom 0 0 3737 84 0
322-D Classroom 680 45 3737 84 45
322-E Classroom 756 50 3737 84 50
322B Classroom 89 5 187 4 4
323-A Classroom 682 45 1035 23 23
331-A Classroom 538 35 1852 42 35
331-B Classroom 221 14 1852 42 14
332-A Classroom 352 23 963 21 21
332-B Classroom 371 24 963 21 21
333-A Classroom 478 31 1862 42 31
333-B Classroom 0 0 1862 42 0
333-C Classroom 543 36 1862 42 36
335 Classroom 393 26 250 5 5
- 3rd E/Center Corr 296 19 2310 52 19
- 3rd East Corr 310 20 2310 52 20
- 3rd W/Center Corr 437 29 2310 52 29
- 3rd West Corr 0 0 2310 52 0
400-A Classroom 356 23 2045 46 23
400-B Classroom 333 22 2045 46 22
400, 402, 403, & 403A Classroom 21 1 2310 52 1
401-A Classroom 0 0 1080 24 0
401-B Classroom 168 11 1080 24 11
401A Storage 264 17 222 5 5
402-A Classroom 0 0 951 21 0
402-B Classroom 194 12 951 21 12
403-A Classroom 257 17 2279 51 17
403-B Classroom 81 5 2279 51 5
403-C Classroom 190 12 2279 51 12
403-D Classroom 226 15 2279 51 15
410-A Classroom 273 18 1058 24 18
410-B Classroom 273 18 1058 24 18
411-A Classroom 0 0 1067 24 0
411-B Classroom 0 0 1067 24 0
412 Classroom 422 28 1066 24 24
413 Classroom 0 0 952 21 0
414 Classroom 364 24 921 20 20
420-A Classroom 766 51 745 16 16
420-B Classroom 326 21 745 16 16
422-A Classroom 514 34 2438 55 34
422-B Classroom 417 27 2438 55 27
422-C Classroom 407 27 2438 55 27
423 & 420 Classrooms 0 0 576 13 0
423-A Classroom 0 0 1372 31 0
423-B Classroom 0 0 1372 31 0
430-A Classroom 300 20 1431 32 20
430-B Classroom 319 21 1431 32 21
430,431, & 432 Classrooms 8,038 535 792 18 18
431-A Classroom 673 44 2491 56 44
431-B Classroom 221 14 2491 56 14
431-C Classroom 533 35 2491 56 35
431-D Classroom 347 23 2491 56 23
431-E Classroom 325 21 2491 56 21
- 4th E/Center Corr 0 0 2310 52 0
- 4th East Corr 0 0 2310 52 0
- 4th W/ Center Corr 199 13 2310 52 13
- 4th West Corr 267 17 2310 52 17
500 Classroom 299 19 1160 26 19
500-A Classroom 301 20 270 6 6
501 Classroom 388 25 956 21 21
502-A Classroom 206 13 956 21 13
502-B Classroom 258 17 956 21 17
503-A Classroom 208 13 956 21 13
503-B Classroom 144 9 956 21 9
504-A Classroom 224 14 957 21 14
504-B Classroom 108 7 957 21 7
505 Classroom 0 0 863 19 0
506-A Classroom 0 0 833 18 0
506-B Classroom 280 18 833 18 18
507-A Classroom 221 14 1032 23 14
507-B Classroom 467 31 1032 23 23
510-A Classroom 313 20 1085 24 20
510-B Classroom 323 21 1085 24 21
511 Classroom 293 19 954 21 19
512 Classroom 344 22 712 16 16
513 Classroom 294 19 712 16 16
514 Classroom 311 20 665 15 15
515 Classroom 358 23 818 18 18
516 Classroom 394 26 819 18 18
520-B Classroom 0 0 221 5 0
522 Classroom 0 0 316 7 0
523 Classroom 0 0 795 18 0
524 Classroom 0 0 800 18 0
525 Classroom 378 25 851 19 19
526-A Classroom 57 3 961 21 3
526-B Classroom 377 25 961 21 21
530 Classroom 293 19 821 18 18
531-A Classroom 576 38 724 16 16
531-B Classroom 81 5 724 16 5
532 Classroom 292 19 879 19 19
533-A Classroom 225 15 800 18 15
533-B Classroom 0 0 800 18 0
534-A Classroom 438 29 1036 23 23
534-B Classroom 0 0 1036 23 0
535 Classroom 0 0 1006 22 0
- 5th E.Cent Corr 201 13 2310 52 13
- 5th East Corr. 0 0 2310 52 0
- 5th W.Cent Corr 276 18 2310 52 18
601-A Classroom 138 9 1553 35 9
601-B Classroom 0 0 1553 35 0
601-C Classroom 0 0 1553 35 0
603-A Classroom 0 0 962 21 0
603-B Classroom 229 15 962 21 15
604 Classroom 0 0 400 9 0
610 Classroom 331 22 738 16 16
611 Classroom 460 30 712 16 16
612 Classroom 298 19 704 16 16
613 Classroom 257 17 711 16 16
614 Classroom 270 18 800 18 18
615 Classroom 382 25 814 18 18
622-A Classroom 0 0 801 18 0
622-B Classroom 242 16 801 18 16
623 Classroom 682 45 679 15 15
624 Classroom 267 17 820 18 17
625 Classroom 174 11 680 15 11
627 Classroom 815 54 794 18 18
- 6th Center Corr. 0 0 792 18 0
- 6th East Corr. 466 31 792 18 18
- Admin 4,788 319 786 17 17
- Auditorium 0 0 Yes 10,676 242 242
- Boy's Gym 0 0 5,940 135 0
- Girl's Gym 0 0 5,696 129 0
- Lunch Rm 0 0 4,563 103 0
- Lunch Rm 0.0 0 4,563 103 0
Sheet Last Modified: 04-27-2021          
School:  James Dobson Middle School      
Vendor: EMCOR      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 0 Yes 108 2 2 House Fan
101 Classroom 0 Yes 968 22 22 House Fan
103 Classroom 0 Yes 660 15 15 House Fan
104 Classroom 0 Yes 660 15 15 House Fan
106 Office 0 Yes 638 14 14 House Fan
107 Classroom 0 Yes 660 15 15 House Fan
108 Classroom 0 Yes 660 15 15 House Fan
109 Classroom 0 Yes 120 2 2 House Fan
201 Classroom 0 Yes 660 15 15 House Fan
202 Classroom 0 Yes 690 15 15 House Fan
203 Classroom 0 Yes 660 15 15 House Fan
204 Classroom 0 Yes 660 15 15 House Fan
205 Office 0 Yes 342 7 7 House Fan
206 Classroom 0 Yes 660 15 15 House Fan
207 Classroom 0 Yes 660 15 15 House Fan
208 Classroom 0 Yes 660 15 15 House Fan
209 Classroom 0 Yes 660 15 15 House Fan
210 Office 0 Yes 660 15 15 House Fan
303/304 Classroom 0 Yes 1,320 30 30 House Fan
306/307 Classroom 0 Yes 1,320 30 30 House Fan
308 Classroom 0 Yes 660 15 15 House Fan
309 Classroom 0 Yes 660 15 15 House Fan
313 Classroom 0 Yes 858 19 19 House Fan
- Councelors office  0 Yes 243 5 5
- Main Office  0 Yes 510 11 11 House Fan
- Principals office  0 Yes 236 5 5 House Fan
- Gym 0 Yes 3080 70 70
- Cafeteria large 0 944 21 0
- Auditorium 0 3124 71 0
- Library 0 Yes 1320 30 30
- Nurses office 0 Yes 264 6 6
Cafeteria small 0 919 20
Sheet Last Modified: 04-21-2021    
School: Tanner Duckrey Elementary School
  Exhaust Report
Vendor: Chadwick Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B19 Art Room 358 23 1032 23 23 AHU
B21 Classroom 0 0 Yes 1029 23 23 Unit Ventilator
111 Classroom 718 47 1115 25 25 Unit Ventilator
114 Classroom 284 18 941 21 18 Unit Ventilator
117 Classroom 608 40 940 21 21 Unit Ventilator
118 Classroom 271 18 691 15 15 Unit Ventilator
119 - 276 18 Yes 1237 28 28 Unit Ventilator
120 Classroom 638 42 1024 23 23 Unit Ventilator
121A Classroom 367 24 715 16 16 Unit Ventilator
121B Classroom 315 21 795 18 18 Unit Ventilator
122 Classroom 413 27 1027 23 23 Unit Ventilator
124 Classroom 686 45 921 20 20 Unit Ventilator
126 Classroom 310 20 927 21 20 Unit Ventilator
128 Classroom 409 27 1012 23 23 Unit Ventilator
130 Classroom 429 28 1101 25 25 Unit Ventilator
200 - 639 42 1036 23 23 Unit Ventilator
201 - 803 53 1050 23 23 Unit Ventilator
204 - 564 37 952 21 21 Unit Ventilator
207 - 0 0 Yes 951 21 21 Unit Ventilator
208 - 786 52 917 20 20 Unit Ventilator
209 - 648 43 951 21 21 Unit Ventilator
210 - 638 42 953 21 21 Unit Ventilator
211 - 617 41 919 20 20 Unit Ventilator
212 - 0 Yes 1023 23 23
213 - 830 55 1088 24 24 Unit Ventilator
214 - 819 54 1037 23 23 Unit Ventilator
215 - 475 31 1035 23 23 Unit Ventilator
216 - 838 55 1039 23 23 Unit Ventilator
216A - 384 25 926 21 21 Unit Ventilator
217 - 546 36 922 20 20 Unit Ventilator
218 - 307 20 922 20 20 Unit Ventilator
219 - 348 23 925 21 21 Unit Ventilator
220 - 459 30 411 9 9 Unit Ventilator
220A - 290 19 330 7 7 Unit Ventilator
221 - 556 37 873 19 19 Unit Ventilator
221A - 432 28 194 4 4 Unit Ventilator
222 - 334 22 875 19 19 Unit Ventilator
223 - 538 35 872 19 19 Unit Ventilator
- Auditorium/Cafe 264 17 Yes 5376 122 122 AHU
- Faculty Lounge 1,156 77 513 11 11 Unit Ventilator
- Kitchen 203 13 2070 47 13 AHU
- Library 336 22 1914 43 22 AHU
- Main Office 1,063 70 903 20 20 Unit Ventilator
- Nurse 334 22 387 8 8 Unit Ventilator
- Science Room 1,464 97 799 18 18 Unit Ventilator
- Gym 215 14 4808 109 14 AHU
Sheet Last Modified: 04-06-2021        
School:  Paul L. Dunbar High School    
           
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
102 Clasroom 0 0 Yes 730 16 16 House Fan
103 office 0 0 Yes 682 15 15 House Fan
103 bathroom 0 0 49 1 0 House Fan
104 Lunchroom 0 0 Yes 1,413 32 32 House Fan
105 Classroom 0 0 Yes 730 16 16 House Fan
105 Bathroom 0 0 54 1 0 House Fan
107 Classroom  0 0 Yes 914 20 20 House Fan
107 Bathroom 0 0 41 0 0 House Fan
108 Classroom 0 0 Yes 682 15 15 House Fan
108 Bathroom 0 0 45 1 0 House Fan
109 Climate rm 0 0 Yes 251 5 5 House Fan
109 Bathroom 0 0 58 1 0 House Fan
201 Classroom 0 0 Yes 682 15 15 House Fan
202 Classroom 0 0 Yes 698 15 15 House Fan
203 Classroom 0 0 Yes 682 15 15 House Fan
204 Classroom 0 0 Yes 666 15 15 House Fan
205 Classroom 0 0 Yes 682 15 15 House Fan
206 Classroom 0 0 Yes 716 16 16 House Fan
207 Art room 0 0 Yes 838 19 19 House Fan
208 Classroom 0 0 Yes 679 15 15 House Fan
209 scc room 0 0 Yes 457 10 10 House Fan
300 computer lab 0 0 Yes 688 15 15 House Fan
301 Classroom 0 0 Yes 688 15 15 House Fan
302 Classroom 0 0 Yes 704 15 15 House Fan
303 Classroom 0 0 Yes 670 15 15 House Fan
304 Classroom 0 0 Yes 643 14 14 House Fan
305 Classroom 0 0 Yes 691 15 15 House Fan
306 Classroom 0 0 Yes 725 16 16 House Fan
307 Classroom 0 0 Yes 966 21 21 House Fan
308 0 688 0 House Fan
309 0 360 0 House Fan
310 0 172 0 House Fan
- Auditorium 0 0 3,202 72 0 House Fan
- Boys bathroom near rm 307 0 0 297 6 0 N/A
- Boys bathroom near Nurse's Office 0 0 144 3 0 N/A
- Basement Boys Bathroom 0 0 599 13 0 N/A
- Basement Boys Bathroom 0 0 317 7 0 N/A
- Girls bathroom near rm 301 0 0 415 9 0 N/A
- Basement Girls Bathroom 0 0 387 8 0 N/A
- Girls bathroom near rm 201 0 0 441 10 0 N/A
- Gym  0 0 2,723 61 0 House Fan
- IMC 0 0 Yes 1,168 26 26 House Fan
- Main Office 0 0 Yes 360 8 8 House Fan
- Nurse Office 0 0 Yes 175 3 3 House Fan
- Principal Office 0 0 Yes 231 5 5 House Fan
- Asst Principal Office 0 Yes 879 19 19 House Fan
- Counselor Office 0 Yes 458 10 10 House Fan
- Teachers Lounge  0 0 605 13 0 House Fan
Sheet Last Modified: 04-20-2021    
School:  Thomas Edison High School
Vendor: Devine Brothers Devine Retest
  Devine 2nd Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Office 85 5 568 12 5 AHU
102 Nurse 212 14 498 11 11 AHU
103A Mail room 261 17 414 9 9 AHU
104 Office 66 4 140 3 3 AHU
105 Office 171 11 284 6 6 AHU
105C Conference 79 5 242 5 5 AHU
106 Office 94 6 119 2 2 AHU
107 Office 68 4 112 2 2 AHU
108 Office 61 4 86 1 1 AHU
109 Office 56 3 74 1 1 AHU
110 Office 71 4 86 1 1 AHU
111 Office 68 4 86 1 1 AHU
112 Office 80 5 86 1 1 AHU
113 Office 63 4 86 1 1 AHU
114 Office 115 7 86 1 1 AHU
115 Office 124 8 86 1 1 AHU
116 Office 160 10 242 5 5 AHU
117 Office 92 6 20 0 0 AHU
118 Office 55 3 83 1 1 AHU
120 Office 70 4 90 2 2 AHU
121 Office 56 3 90 2 2 AHU
122 Office 69 4 90 2 2 AHU
123 Office 59 3 90 2 2 AHU
124 Office 57 3 90 2 2 AHU
125 Office 68 4 90 2 2 AHU
127B Office 136 9 174 3 3 AHU
128 Conference 658 43 676 15 15 AHU
129 Office 150 10 281 6 6 AHU
130 Office 262 17 345 7 7 AHU
131 Break Room 84 5 131 2 2 AHU
132 Classroom 292 19 713 16 16 AHU
133 Classroom 273 18 566 12 12 AHU
134 Classroom 575 38 2286 51 38 AHU
135 Classroom 460 30 1604 36 30 AHU
135A Kitchen 61 4 37 0 0 AHU
135B Office 78 5 137 3 3 AHU
136 Classroom 310 20 1144 26 20 AHU
136B Classroom 483 32 1142 25 25 AHU
137 Classroom 297 19 2086 47 19 AHU
137A Office 77 5 228 5 5 AHU
138 Womens Locker Room 1166 77 4342 98 77 AHU
138A Office 50 3 78 1 1 AHU
138B Office 124 8 314 7 7 AHU
139 Mens Locker Room 1278 85 3031 68 68 AHU
139A Office 122 8 77 1 1 AHU
139B Storage 66 4 178 4 4 AHU
141 Physical Fitness 603 40 1325 30 30 AHU
144A Bathroom 52 3 333 7 3 AHU
144B Bathroom 36 2 211 4 2 AHU
145 Plumbing Shop 6184 412 1635 37 37 AHU
145 Classroom 358 23 2286 51 23 AHU
145B Classroom 161 10 498 11 10 AHU
146 Office 297 19 1280 29 19 AHU
146 Office 332 22 276 6 6 AHU
147 Storage 87 5 476 10 5 AHU
147 Classroom 553 36 1497 34 34 AHU
148 Classroom 0 Yes 3146 71 71
149 Camera Room 88 5 208 4 4 AHU
150 Classroom 375 25 814 18 18 AHU
150A Office 0 0 165 3 0 AHU
150B Studio 114 7 1182 26 7 AHU
151A Classroom 534 35 1233 28 28 AHU
151B Classroom 912 60 1441 32 32 AHU
152 Classroom 655 43 794 18 18 AHU
152A Classroom 994 66 244 5 5 AHU
152B Classroom 901 60 1073 24 24 AHU
153A Classroom 321 21 533 12 12 AHU
153B Classroom 302 20 107 2 2 AHU
154A Office 278 18 175 3 3 AHU
154E Classroom 0 0 516 11 0 AHU
154H Classroom 304 20 407 9 9 AHU
154D 154A Theory 240 16 514 11 11 AHU
156 Classroom 293 19 514 11 11 AHU
157 Classroom 961 64 1255 28 28 AHU
158 Classroom 592 39 1234 28 28 AHU
160 Classroom 727 48 1267 28 28 AHU
160A Office 78 5 119 2 2 AHU
161 Classroom 551 36 1440 32 32 AHU
161A Office 88 5 120 2 2 AHU
161H Classroom 52 3 36 0 0 AHU
161I Practice room 9 0 36 0 0 AHU
161J Classroom 73 4 90 2 2 AHU
164 Classroom 1398 93 825 18 18 AHU
164B Classroom 402 26 159 3 3 AHU
171 Classroom 0 0 1392 31 0 AHU
201 Classroom 333 22 679 15 15 AHU
202 Classroom 334 22 677 15 15 AHU
203 Classroom 325 21 680 15 15 AHU
204 Classroom 436 29 770 17 17 AHU
205 Classroom 601 40 1444 32 32 AHU
205B Storage 153 10 375 8 8 AHU
207 Classroom 845 56 2973 67 56 AHU
209 Classroom 472 31 1646 37 31 AHU
209B Storage 112 7 279 6 6 AHU
210 Classroom 466 31 1552 35 31 AHU
210B Storage 190 12 331 7 7 AHU
212 Office 134 8 174 3 3 AHU
213A Classroom 384 25 721 16 16 AHU
213B Classroom 312 20 872 19 19 AHU
214 Classroom 282 18 703 15 15 AHU
215 Classroom 286 19 828 18 18 AHU
216 Office 164 10 397 9 9 AHU
217 Classroom 356 23 601 13 13 AHU
218 Classroom 352 23 639 14 14 AHU
219 Office 129 8 265 6 6 AHU
220 Classroom 444 29 715 16 16 AHU
220 Classroom 456 30 715 16 16 AHU
221 Classroom 321 21 720 16 16 AHU
222 Classroom 328 21 680 15 15 AHU
223 Classroom 299 19 781 17 17 AHU
224 Classroom 292 19 790 17 17 AHU
225 Classroom 284 18 749 17 17 AHU
226 Classroom 293 19 721 16 16 AHU
229 Library 1039 69 6194 140 69 AHU
229A Office 79 5 117 2 2 AHU
229B Office 148 9 229 5 5 AHU
229C Computer Lab 100 6 270 6 6 AHU
230 Office 79 5 218 4 4 AHU
231 Classroom 308 20 613 13 13 AHU
232 Office 144 9 931 21 9 AHU
233 Classroom 325 21 613 13 13 AHU
234 Classroom 334 22 700 15 15 AHU
235 Classroom 457 30 592 13 13 AHU
236 Classroom 431 28 720 16 16 AHU
237 Classroom 220 14 931 21 14 AHU
238 Classroom 112 7 606 13 7 AHU
239 Classroom 494 32 627 14 14 AHU
240 Classroom 957 63 1407 31 31 AHU
241 Classroom 318 21 714 16 16 AHU
241A Classroom 156 10 700 15 10 AHU
242 Classroom 1072 71 1512 34 34 AHU
243 Classroom 605 40 2253 51 40 AHU
245 Classroom 403 26 1908 43 26 AHU
245A Office 107 7 258 5 5 AHU
246 Classroom 380 25 2009 45 25 AHU
246B Classroom 308 20 510 11 11 AHU
247 Classroom 676 45 1992 45 45 AHU
247A Classroom 383 25 495 11 11 AHU
249 Classroom 307 20 888 20 20 AHU
250 Classroom 121 8 142 3 3 AHU
251 Classroom 223 14 504 11 11 AHU
253 Classroom 0 0 939 21 0 AHU
301 Science Lab 428 28 940 21 21 AHU
302 science prep 0 0 197 4 0 AHU
304 Classroom 448 29 1086 24 24 AHU
305 Classroom 428 28 469 10 10 AHU
307 Lab 150 10 370 8 8 AHU
307B Office 205 13 161 3 3 AHU
307C Office 152 10 92 2 2 AHU
308 Science Lab 360 24 1015 23 23 AHU
309 Science Prep 316 21 260 5 5 AHU
310 Classroom 331 22 990 22 22 AHU
311 Classroom 417 27 997 22 22 AHU
313 Classroom 389 25 716 16 16 AHU
314 Classroom 296 19 793 18 18 AHU
315 Classroom 410 27 804 18 18 AHU
316 Classroom 326 21 750 17 17 AHU
317A Office 58 3 213 4 3 AHU
317B Office 42 2 220 5 2 AHU
318 Classroom 378 25 678 15 15 AHU
319 Classroom 329 21 678 15 15 AHU
320 Classroom 325 21 678 15 15 AHU
321 Classroom 367 24 678 15 15 AHU
322 Faculty Lounge 34 2 196 4 2 AHU
324 Classroom 282 18 611 13 13 AHU
325 Classroom 326 21 703 15 15 AHU
326 Classroom 280 18 681 15 15 AHU
327 Classroom 310 20 702 15 15 AHU
328 Office 135 9 334 7 7 AHU
328A and B Office 229 15 391 8 8 AHU
329 Classroom 310 20 573 13 13 AHU
330 Classroom 330 22 573 13 13 AHU
331 Classroom 425 28 708 16 16 AHU
333 Classroom 304 20 697 15 15 AHU
334 Classroom 296 19 631 14 14 AHU
335 Classroom 280 18 614 13 13 AHU
336 Classroom 282 18 632 14 14 AHU
338 Classroom 283 18 678 15 15 AHU
339 Office 47 3 322 7 3 AHU
340 Classroom 281 18 931 21 18 AHU
341A Classroom 300 20 834 18 18 AHU
341B Classroom 122 8 262 5 5 AHU
342 Classroom 332 22 587 13 13 AHU
344 Classroom 311 20 820 18 18 AHU
345 Classroom 290 19 1154 26 19 AHU
- Main office Rear reception desk 79 5 429 9 5 AHU
- Main office 221 14 1109 25 14 AHU
- Student Store 236 15 339 7 7 AHU
- Teaching Kitchen 2167 144 2843 64 64 AHU
- Cafeteria 0 0 8970 203 0 AHU
- Teaching Kitchen 2480 165 1316 29 29 AHU
- Kitchen 1030 68 1361 30 30 AHU
- Kitchen Hood 3846 256 N/A 0 0 AHU
- Auditorium 6454 430 5600 127 127 AHU
- 1st Floor NE 176 11 20126 457 11 AHU
- Heavy Equipment 2723 181 3189 72 72 AHU
- Autobody 4337 289 444 10 10 AHU
- Welding 1296 86 520 11 11 AHU
- Sheet Metal 3436 229 514 11 11 AHU
- Warehouse Classroom 8094 539 533 12 12 AHU
- Gym 7088 472 15450 351 351 AHU
- Factory Lab 3833 255 417 9 9 AHU
- 1st Floor 210 14 2760 62 14 AHU
- Vending Machine Repair 317 21 3167 71 21 AHU
- Boiler Room 3303 220 4914 111 111 AHU
- Maint. Break room 153 10 461 10 10 AHU
- Eng. Office 128 8 187 4 4 AHU
- Weight Room 990 66 939 21 21 AHU
- Offices 3928 261 90 2 2 AHU
Sheet Last Modified: 04-21-2021    
School:  Franklin S. Edmonds Elementary School
Vendor: Devine Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B1 Classroom 0 0 Yes 400 9 9 Unit Ventilator
B2 Kitchen 75 5 572 13 5 Unit Ventilator
B3 Kitchen 165 11 480 10 10 Unit Ventilator
H2 Office 0 Yes 178 4 4
101 Classroom 165 11 Yes 1128 25 25 Unit Ventilator
102 Classroom 441 29 1056 24 24 Unit Ventilator
103 Classroom 397 26 864 19 19 Unit Ventilator
104 Classroom 455 30 1056 24 24 Unit Ventilator
105 Classroom 412 27 1128 25 25 Unit Ventilator
106 Classroom 460 30 1056 24 24 Unit Ventilator
107 Classroom 256 17 720 16 16 Unit Ventilator
108 Classroom 567 37 1056 24 24 Unit Ventilator
109 Classroom 527 35 1056 24 24 Unit Ventilator
110 Classroom 431 28 1056 24 24 Unit Ventilator
111 Classroom 634 42 1008 22 22 Unit Ventilator
112A Office 0 Yes 364 8 8 Not supplied
112B Office 0 Yes 210 4 4
113 Classroom 662 44 1008 22 22 Unit Ventilator
114 Office 0 Yes 364 8 8 Unit Ventilator
115 Classroom 551 36 1008 22 22 Unit Ventilator
115A Office 0 Yes 252 5 5
116 Classroom 169 11 Yes 736 16 16 Unit Ventilator
117 Classroom 299 19 912 20 19 Unit Ventilator
118 Classroom 281 18 912 20 18 Unit Ventilator
118A Office 0 175 3 0
119 Classroom 282 18 912 20 18 Unit Ventilator
120 Classroom 0 0 Yes 912 20 20 Unit Ventilator
121 Classroom 0 0 Yes 912 20 20 Unit Ventilator
122 Classroom 340 22 912 20 20 Unit Ventilator
201 Classroom 503 33 1056 24 24 Unit Ventilator
202 Classroom 418 27 1056 24 24 Unit Ventilator
203 Classroom 415 27 1056 24 24 Unit Ventilator
204 Classroom 395 26 1056 24 24 Unit Ventilator
205 Classroom 491 32 1056 24 24 Unit Ventilator
206 Classroom 414 27 1056 24 24 Unit Ventilator
207 Classroom 485 32 1056 24 24 Unit Ventilator
208 Classroom 348.0 23 1056 24 23 Unit Ventilator
209 Classroom 431.0 28 1056 24 24 Unit Ventilator
210 Classroom 304 20 1056 24 20 Unit Ventilator
211 Classroom 322 21 1056 24 21 Unit Ventilator
212 Classroom 31.0 2 Yes 1056 24 24 Unit Ventilator
213 Classroom 186.0 12 1008 22 12 Unit Ventilator
215 Classroom 509.0 33 1008 22 22 Unit Ventilator
216 Library 969.0 64 1008 22 22 Unit Ventilator
217 Classroom 503.0 33 1008 22 22 Unit Ventilator
217-A VP office 0 Yes 252 5 5 Convector
218 Classroom 0.0 0 Yes 864 19 19 Unit Ventilator
219 Classroom 44.0 2 1008 22 2 Unit Ventilator
- Auditorium 1860 124 1849 42 42 AHU
- Gym 1195 79 2795 63 63 AHU
- Lunch 0.0 0 780 17 0 Unit Ventilator
- Cafeteria 411 27 Yes 1560 35 35 Unit Ventilator
- Kitchen 0 0 Yes 400 9 9 Unit Ventilator
Women Helper 0 Yes 262 5 5
- Nurse 0 0 Yes 280 6 6 N/A
- Prin. Office 0 0 Yes 322 7 7 Convector
- Main Office 0 0 Yes 650 14 14 Convector
Sheet Last Modified: 04-26-2021      
School:  Lewis Elkin Elementary School  
Vendor: Devine Part 1 Devine Part 2 Devine Part 3  
School:  Elkin Little School House  
Vendor: Devine      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
101 Classroom 391 26 420 9 9 Unit Ventilator
102 Classroom 0 0 Yes 1136 25 25 Unit Ventilator Bad Motor
103 Classroom 299 19 Yes 1303 29 29 Unit Ventilator
104 Classroom 293 19 1201 27 19 Unit Ventilator
105 Classroom 301 20 Yes 1269 28 28 Unit Ventilator
106 Classroom 300 20 418 9 9 Unit Ventilator
107 Classroom 411 27 897 20 20 Unit Ventilator
108 Classroom 386 25 897 20 20 Unit Ventilator
109 Classroom 389 25 897 20 20 Unit Ventilator
110 Classroom 376 25 821 18 18 Unit Ventilator
111 Classroom 313 20 938 21 20 Unit Ventilator
112 Classroom 363 24 898 20 20 Unit Ventilator
113 Classroom 318 21 898 20 20 Unit Ventilator
114 Classroom 349 23 898 20 20 Unit Ventilator
115 Classroom 345 23 1024 23 23 Unit Ventilator
116 Lounge 133 8 309 7 7 Unit Ventilator
117 Classroom 129 8 215 4 4 Unit Ventilator
117 Office 96 6 317 7 6 Unit Ventilator
117A Classroom Vestibule 171 11 102 2 2 Unit Ventilator
118 Office 109 7 122 2 2 Unit Ventilator
119 Office 105 7 117 2 2 Unit Ventilator
120 Security Office 214 14 259 5 5 Unit Ventilator
121 Office 0 Yes 400 9 9
201 Classroom 496 33 772 17 17 Unit Ventilator
202 Classroom 325 21 933 21 21 Unit Ventilator
203 Classroom 385 25 838 19 19 Unit Ventilator
204 Classroom 360 24 756 17 17 Unit Ventilator
204A Office 178 11 201 4 4 Unit Ventilator
205 Classroom 334 22 815 18 18 Unit Ventilator
206 Classroom 402 26 815 18 18 Unit Ventilator
207 Classroom 357 23 815 18 18 Unit Ventilator
207A Office 74 4 201 4 4 Unit Ventilator
208 Classroom 388 25 762 17 17 Unit Ventilator
209 Classroom 365 24 811 18 18 Unit Ventilator
210 Classroom 285 19 814 18 18 Unit Ventilator
211 Classroom 430 28 746 16 16 Unit Ventilator
211A Office 161 10 201 4 4 Unit Ventilator
212 Classroom 312 20 810 18 18 Unit Ventilator
213 Classroom 358 23 815 18 18 Unit Ventilator
214 Classroom 376 25 786 17 17 Unit Ventilator
215 Classroom 0 0 Yes 863 19 19 Unit Ventilator Not operating. Facility manager is aware
215A Classroom 131 8 201 4 4 Unit Ventilator
216 Classroom 395 26 855 19 19 Unit Ventilator
217 Classroom 493 32 1259 28 28 Unit Ventilator 2 Units.
218 Classroom 437 29 788 17 17 Unit Ventilator
219 Classroom 76 5 117 2 2 Unit Ventilator
220 Library 1,770 118 2982 67 67 Unit Ventilator 4 Units. 1 unit is a wall unit.  1 unit is a window unit.  1 unit serves 220, but, is in 220B.  1 unit serves 220, but, is in 220C.  This unit needs repair and has 0 CFM of OA.
220A Office 214 14 373 8 8 Unit Ventilator
220B Office 0 0 421 9 0 N/A No ouside air to room.
220C Office 0 0 398 9 0 N/A No ouside air to room.
221 Room 0 0 141 3 0 Unit Ventilator Unit not operating
B01 Classroom 360 24 1859 42 24 Unit Ventilator No return air cover/grille
B02 Classroom 364 24 928 21 21 Unit Ventilator
B03 Classroom 183 12 525 11 11 Unit Ventilator
B04 Classroom 300 20 613 13 13 Unit Ventilator 2 Units.  UV-2 is a window unit.  UV-3 is a wall unit.
- Assistant Principal's Office 40 2 98 2 2 Unit Ventilator
- Auditorium 0 0 7138 162 0 Unit Ventilator 4 units.  UV-1, UV-2, UV-3, and UV-4 are not operating. One fell down.  Facility manager is aware. Might be control issue
- Main Office Conference Room 0 0 181 4 0 Unit Ventilator Measured 0 CFM at all diffusers. No access to unit since Building Engineer does not have key to Server Room.
- Copy room 34 2 179 4 2 Unit Ventilator Measured 0 CFM at all diffusers. No access to unit since Building Engineer does not have key to Server Room.
- Parent Resources Office 0 0 84 1 0 Unit Ventilator Measured 0 CFM at all diffusers. No access to unit since Building Engineer does not have key to Server Room.
- Education Office 57 3 207 4 3 Unit Ventilator
- Gymnasium 3,457 230 4778 108 108 Unit Ventilator 2 Units.
- Ms. Potts' Office 46 3 133 3 3 Unit Ventilator
- Health Office/Nurses Area/Nurse's Suite 480 32 637 14 14 Unit Ventilator
- Cafeteria/Lunchroom  1,731 115 2558 58 58 Unit Ventilator 6 Units.  Univent 6 has a bad motor and 0 CFM of OA.
- Principal's Office 34 2 167 3 2 Unit Ventilator
- Main Office  235 15 Yes 674 15 15 Unit Ventilator
- Teacher's Lounge 0 0 623 14 0 Unit Ventilator Not operating. Facility manager is aware. Might be control issue
- Library (Wall mount unit, south area) 33 2 2775 63 2 Unit Ventilator data is for Wall mount unit, south area.  Unit against window not operating
LSH Building
1 Classroom 829 55 1018 23 23 AHU
2 Classroom 619 41 1018 23 23 AHU
3 Classroom 651 43 1018 23 23 AHU
4 Classroom 486 32 1018 23 23 AHU
5 Classroom 410 27 1018 23 23 AHU
6 Classroom 586 39 1018 23 23 AHU
7 Classroom 379 25 1,018 23 23 AHU
8 Classroom 519 34 1018 23 23 AHU
- Main Office 0 0 295 6 0 AHU Need to confirm with Jason that this reading is for the main office.  Previous note for this line: Broken belt none onsite
- Multi Purpose Room 1,105 73 1995 45 45 AHU
- Teacher's Lounge 0 0 220 5 0 AHU Motor Issue
Sheet Last Modified: 03-12-2021    
School:  Ellwood Elementary School
Vendor: EMCOR Exhaust Retest
  Devine 2nd Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 100 13.0 0 Yes 1465 33 33 Unit Ventilator
100 A Counselor Office 0 Yes 297 6 6
100 B-C Nurse 0 Yes 342 7 7
100 E Main Office 0 Yes 416 9 9
102 102 414.0 27 574 13 13 Unit Ventilator
102 C Principal 0 Yes 400 9 9
103 103 328.0 21 582 13 13 Unit Ventilator
104 104 392.0 26 701 15 15 Unit Ventilator
105 105 457.0 30 1158 26 26 Unit Ventilator
107 107 420.0 28 905 20 20 Unit Ventilator
108 108 443.0 29 906 20 20 Unit Ventilator
109 109 468.0 31 904 20 20 Unit Ventilator
110 110 372.0 24 916 20 20 Unit Ventilator
111 111 260.0 17 448 10 10 Unit Ventilator
201 201 520.0 34 940 21 21 Unit Ventilator
202 202 195.0 13 912 20 13 Unit Ventilator
203 203 640.0 42 903 20 20 Unit Ventilator
204 204 430.0 28 914 20 20 Unit Ventilator
206 206 409.0 27 860 19 19 Unit Ventilator
207 207 423.0 28 912 20 20 Unit Ventilator
208 208 417.0 27 904 20 20 Unit Ventilator
210 210 154.0 10 903 20 10 Unit Ventilator
211 211 511.0 34 912 20 20 Unit Ventilator
212 212 534.0 35 975 22 22 Unit Ventilator
- Auditorium 0.0 0 2900 65 0 AHU
- Gym 2,115.0 141 3922 89 89 AHU
- Library 0.0 0 Yes 2809 63 63 AHU
- Floor 1 East Corridor 0.0 0 0 0 Unit Ventilator
- Floor 1 East Corridor 0.0 0 0 0 Unit Ventilator
Sheet Last Modified: 03-17-2021    
School:  Philadelphia Military Academy At Elverson
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
103 Conference room 788.0 52 690 15 15
104 IMC 973.0 64 690 15 15
105 Conference room 354.0 23 690 15 15
106 Weight room  871.0 58 943 21 21
107 Classroom 1,423.0 94 690 15 15
108 Classroom 787.0 52 690 15 15
111 Classroom 625.0 41 736 16 16
112 Classroom 112.0 7 736 16 7
113 Classroom 728.0 48 736 16 16
114 Classroom 525.0 35 1180 26 26
201 Classroom 1,325.0 88 690 15 15
202 Classroom 180.0 12 690 15 12
203 Classroom 428.0 28 690 15 15
204 Classroom 487.0 32 690 15 15
205 Classroom 73.0 4 805 18 4
206 Classroom 796.0 53 943 21 21
207 Classroom 63.0 4 690 15 4
208 Classroom 445.0 29 690 15 15
211 Classroom 0.0 0 736 16 0
212 Classroom 0.0 0 736 16 0
213 Classroom 670.0 44 736 16 16
214 Classroom 0.0 0 736 16 0
215 Classroom 745.0 49 736 16 16
301 Classroom 142.0 9 690 15 9
302 Classroom 447.0 29 690 15 15
303 Classroom 117.0 7 690 15 7
304 Classroom 147.0 9 690 15 9
305 Classroom 120.0 8 805 18 8
306 Classroom 796.0 53 1048 23 23
307 Classroom 370.0 24 690 15 15
308 Classroom 477.0 31 690 15 15
309 Classroom 115.0 7 690 15 7
311 Classroom 572.0 38 736 16 16
312 Classroom 0.0 0 736 16 0
313 Classroom 697.0 46 736 16 16
314 Classroom 0.0 0 736 16 0
315 Classroom 0.0 0 736 16 0
- Cafeteria / Kitchen  970.0 64 2595 58 58
- Hallway 462.0 30 1400 31 30
- Hallway 0.0 0 1400 31 0
- Hallway 432.0 28 1400 31 28
- main office  1,050.0 70 744 16 16
- Office / storage  735.0 49 720 16 16
Sheet Last Modified: 04-21-2021        
School:  Eleanor Emlen Elementary School House fan Abated  
Vendor: Devine Brothers Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B001 Classroom 736 49 736 16 16 Unit Ventilator
B002 Classroom 0 0 Yes 1,848 42 42 Unit Ventilator
B003 Classroom 994 66 1,032 23 23 Unit Ventilator
B004A Classroom 701 46 768 17 17 Unit Ventilator
B004B Classroom 360 24 816 18 18 Unit Ventilator
B005 Classroom 419 27 546 12 12 Unit Ventilator
101 Classroom 857 57 768 17 17 House Fan
102 Classroom 267 17 690 15 15 House Fan
103 Classroom 517 34 690 15 15 House Fan
104 Office 193 12 88 2 2 House Fan
104D Waiting Room 255 17 90 2 2 House Fan
104D Office 199 13 396 9 9 House Fan
104D Storage 136 9 207 4 4 House Fan
104D Nurse 173 11 144 3 3 House Fan
105 Waiting Room 174 11 248 5 5 House Fan
105A Office 93 6 182 4 4 House Fan
105B Office 85 5 126 2 2 House Fan
105C Office 103 6 126 2 2 House Fan
106 Classroom 378 25 690 15 15 House Fan
107 Classroom 289 19 792 18 18 House Fan
108 Classroom 643 42 690 15 15 House Fan
109 Classroom 782 52 1,050 23 23 House Fan
110 Classroom 485 32 621 14 14 House Fan
200 Classroom 0 0 Yes 528 12 12 House Fan
201 Classroom 531 35 800 18 18 House Fan
202 Classroom 312 20 690 15 15 House Fan
203 Classroom 273 18 690 15 15 House Fan
204 Classroom 97 6 Yes 690 15 15 House Fan
205 Classroom 443 29 690 15 15 House Fan
206 Classroom 267 17 900 20 17 House Fan
207 Classroom 372 24 690 15 15 House Fan
208 Classroom 437 29 805 18 18 House Fan
209 Classroom 504 33 690 15 15 House Fan
210 Classroom 361 24 690 15 15 House Fan
211 Classroom 416 27 690 15 15 House Fan
213 Classroom 0 0 Yes 720 16 16 House Fan
214 Classroom 0 0 Yes 690 15 15 House Fan
215 Classroom 0 0 Yes 744 16 16 House Fan
216 Classroom 0 0 Yes 720 16 16 House Fan
217 Classroom 0 0 Yes 690 15 15 House Fan
218 Classroom 0 0 Yes 720 16 16 House Fan
301 Classroom 0 Yes 1,190 27
302 Classroom 695 46 660 15 15 House Fan
303 Classroom 99 6 Yes 660 15 15 House Fan
304 Classroom 719 47 660 15 15 House Fan
305 Classroom 427 28 616 14 14 House Fan
306 Classroom 259 17 638 14 14 House Fan
307 Classroom 336 22 690 15 15 House Fan
308 Classroom 372 24 660 15 15 House Fan
308A Classroom 0 Yes 220 5
309 Classroom 105 7 Yes 690 15 15 House Fan
310 Classroom 346 23 540 12 12 House Fan
311 Classroom 178 11 690 15 11 House Fan
Portable Building Cafeteria 1 0 1,840 41
Portable Building Cafeteria 2 0 989 22
- Auditorium 0 0 Yes 5,336 121 121 House Fan
- Basement Office/Classroom 617 41 1,088 24 24 House Fan
- Gym 3331 222 5005 113 113 AHU
- Prinicipal Office 0 108 2 0
- Main Office 0 234 5 0
Sheet Last Modified: 04-27-2021    
School:  Louis H. Farrell Elementary School
Vendor: EMCOR Retest
  Devine 2nd Retest Devine 3rd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
A-2 LS 269 17 891 20 17 Unit Ventilator
A-3 LS 319 21 891 20 20 Unit Ventilator
A-4 LS 259 17 540 12 12 Unit Ventilator
A-6 LS 274 18 891 20 18 Unit Ventilator
A-10 A-10 290 19 1130 25 19 RTU
A-11 A-11 276 18 800 18 18 RTU
A-12 A-12 296 19 800 18 18 RTU
A-13 A-13 306 20 800 18 18 RTU
A-14 A-14 293 19 800 18 18 RTU
A-15 A-15 331 22 800 18 18 RTU
A-16 A-16 303 20 800 18 18 RTU
A-21 A-21 314 20 800 18 18 RTU
A-22 A-22 285 19 800 18 18 RTU
A-23 A-23 293 19 800 18 18 RTU
A-24 A-24 293 19 800 18 18 RTU
A-25 A-25 333 22 800 18 18 RTU
A-26 A-26 316 21 800 18 18 RTU
100 LS 328 21 1813 41 21 Unit Ventilator
101 LS 326 21 1813 41 21 Unit Ventilator
103 LS 406 27 925 21 21 Unit Ventilator
105 AS 318 21 672 15 15 Unit Ventilator
108 Yes 350 N/A
111 AS 241 16 950 21 16 Unit Ventilator
112 ? 282 18 950 21 18 Unit Ventilator
113 ? 222 14 950 21 14 Unit Ventilator
200 LIT/SS 318 21 950 21 21 Unit Ventilator
201 M/SC 278 18 950 21 18 Unit Ventilator
202 LS 297 19 950 21 19 Unit Ventilator
203 RELA/LS/EL PI 297 19 950 21 19 Unit Ventilator
204 Classroom 0 Yes 288 6 6 Unit Ventilator
205 M/SC/SS 345 23 950 21 21 Unit Ventilator
206 RELA 327 21 950 21 21 Unit Ventilator
207 ESOL 372 24 950 21 21 Unit Ventilator
208 MATH 308 20 950 21 20 Unit Ventilator
209 M/SC/SS 294 19 950 21 19 Unit Ventilator
209A Yes 310 N/A
210 RELA/SS 203 13 950 21 13 Unit Ventilator
211 MATH/SC 245 16 950 21 16 Unit Ventilator
212 RELA 293 19 950 21 19 Unit Ventilator
213 SC/SS 283 18 950 21 18 Unit Ventilator
300 RELA / SS 265 17 950 21 17 Unit Ventilator
301 CSC 277 18 950 21 18 Unit Ventilator
302 MATH 254 16 950 21 16 Unit Ventilator
303 SC/SS 224 14 950 21 14 Unit Ventilator
304 Room 0 Yes 192 4 4
305 SC/MATH 287 19 950 21 19 Unit Ventilator
306 MATH 300 20 950 21 20 Unit Ventilator
307 SS/RELA 226 15 950 21 15 Unit Ventilator
308 RELA/EL B 277 18 950 21 18 Unit Ventilator
309 SC/SS 277 18 1175 26 18 Unit Ventilator
310 MATH 346 23 950 21 21 Unit Ventilator
311 RELA EL PI 232 15 950 21 15 Unit Ventilator
312 SS/RELA ALG 203 13 950 21 13 Unit Ventilator
313 SC/MATH 223 14 950 21 14 Unit Ventilator
- Lunchroom 815 54 2604 59 54 Unit Ventilator
Gymnasium Gymnasium 0 Yes 3940 89 89
Gymnasium Office 0 Yes 247 5 5
- Auditorium 72 4 3808 86 4 Unit Ventilator
- Main Office 0 Yes 279 6 6 N/A
- Principal Office 0 288 6 0 N/A
Vice Principal Office 0 Yes 96 2 2
- Counselor Office 0 Yes 288 6 6 N/A
Building Engineer Office 0 Yes 275 6 6
- IMC 0 Yes 1485 33 33 N/A
- Nurse 0 Yes 234 5 5 N/A
Sheet Last Modified: 03-23-2021        
School:  D. Newlin Fell Elementary-Middle School House fan Abated  
Vendor: Devine Brothers    
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
2 Music Room 519 34 418 9 9 House Fan
100 Classroom 677 45 704 16 16 House Fan
101 Classroom 791 52 308 7 7 House Fan
102 Classroom 653 43 704 16 16 House Fan
103 Classroom 588 39 660 15 15 House Fan
104 Classroom 604 40 660 15 15 House Fan
105 Classroom 960 64 660 15 15 House Fan
106 Classroom 560 37 660 15 15 House Fan
107 Classroom 760 50 682 15 15 House Fan
108 Classroom 550 36 638 14 14 House Fan
109 Classroom 491 32 687 15 15 House Fan
200 Classroom 362 24 682 15 15 House Fan
201 Classroom 750 50 638 14 14 House Fan
202 Classroom 840 56 682 15 15 House Fan
203 Classroom 411 27 660 15 15 House Fan
204 Classroom 952 63 660 15 15 House Fan
205 Library 670 44 638 14 14 House Fan
206 Library 668 44 638 14 14 House Fan
207 Classroom 512 34 682 15 15 House Fan
208 Classroom 765 51 638 14 14 House Fan
209 Classroom 478 31 682 15 15 House Fan
300 Classroom 500 33 704 16 16 House Fan
301 Classroom 406 27 638 14 14 House Fan
302 Classroom 110 7 682 15 7 House Fan
303 Classroom 426 28 660 15 15 House Fan
304 Classroom 630 42 660 15 15 House Fan
305 Classroom 888 59 660 15 15 House Fan
306 Classroom 791 52 660 15 15 House Fan
307 Classroom 407 27 682 15 15 House Fan
308 Classroom 641 42 638 14 14 House Fan
309 Classroom 645 43 704 16 16 House Fan
309A Classroom 0 Yes 275 6 6 N/A
310 Classroom 310 20 275 6 6 House Fan
- Auditrium 3031 202 3055 69 69 House Fan
- Boys Bathroom 300 20 114 2 2 N/A
- Cafeteria 375 25 990 22 22 House Fan
- Girls Bathroom 421 28 96 2 2 N/A
- Gym 0 0 Yes 3219 73 73 N/A
- Main Office 0 0 Yes 330 7 7 House Fan
- Principal Office 0 Yes 288 6 6 N/A
- Nurse Office 0 0 Yes 220 5 5 House Fan
- PTA Room 900 60 1540 35 35 House Fan
- Speech Room 438 29 506 11 11 House Fan
- Teachers Lounge 0 0 330 7 0 House Fan
Sheet Last Modified: 04-30-2021    
School:  Samuel Fels High School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
A100 Classroom 69 4 290 6 4
A103 Classroom 125 8 870 19 8
A105 Classroom 148 9 870 19 9
A106 Classroom 147 9 870 19 9
A107 Classroom 135 9 870 19 9
A108 Classroom 39 2 870 19 2
A109 Classroom 162 10 870 19 10
A110 Classroom 162 10 870 19 10
A111 Classroom 167 11 870 19 11
A113 Classroom 161 10 870 19 10
A114 Classroom 0 0 930 21 0
A120 Office 125 8 144 3 3
A123 Classroom 298 19 900 20 19
A124 Classroom 345 23 900 20 20
A125 Classroom 376 25 900 20 20
A126 Classroom 266 17 900 20 17
A130 Classroom 697 46 900 20 20
A131 Classroom 155 10 900 20 10
A132 Classroom 291 19 960 21 19
A135 Classroom 645 43 960 21 21
A136 Classroom 162 10 960 21 10
A137 Classroom 229 15 1320 30 15
A138 Classroom 963 64 1376 31 31
A139 Classroom 161 10 1376 31 10
A140 Classroom 1027 68 1376 31 31
A142 Classroom 1338 89 1271 28 28
A143 Classroom 964 64 1505 34 34
A144 Classroom 937 62 1394 31 31
A148 Hallway 193 12 0 0
A150 Hallway 255 17 0 0
A152 Hallway 180 12 0 0
A200 Classroom 451 30 290 6 6
A203 Classroom 252 16 870 19 16
A205 Classroom 332 22 870 19 19
A206 Classroom 911 60 870 19 19
A207 Classroom 536 35 870 19 19
A208 Classroom 1475 98 870 19 19
A209 Classroom 620 41 870 19 19
A210 Classroom 1060 70 870 19 19
A211 Classroom 1246 83 870 19 19
A212 Classroom 1262 84 1271 28 28
A213 Classroom 879 58 961 21 21
A214 Classroom 667 44 961 21 21
A220 Office 7 0 144 3 0
A223 Classroom 486 32 1860 42 32
A225 Classroom 90 6 160 3 3
A226 Classroom 323 21 900 20 20
A227 Classroom 830 55 960 21 21
A231 Classroom 260 17 1320 30 17
A236 Classroom 8 0 120 2 0
A237 Classroom 9 0 104 2 0
A238 Classroom 207 13 1680 38 13
A239 Classroom 1272 84 1376 31 31
A240 Classroom 249 16 224 5 5
A241 Classroom 1797 119 1364 31 31
A242 Classroom 1960 130 1320 30 30
A243 Classroom 960 64 1320 30 30
A244 Classroom 1222 81 1505 34 34
A245 Classroom 695 46 1394 31 31
A248 Hallway 0 0 0 0
A250 Hallway 297 19 0 0
A252 Hallway 566 37 0 0
A255 Classroom 0 0 120 2 0
B100 Classroom 0 0 930 21 0
B102 Classroom 0 0 961 21 0
B103 Classroom 0 0 1023 23 0
B105 Classroom 0 0 1311 29 0
B106 Classroom 0 0 280 6 0
B107 Classroom 0 0 1265 28 0
B108 Classroom 0 0 961 21 0
B109 Classroom 0 0 961 21 0
B117 Classroom 0 0 576 13 0
B118 Classroom 0 0 961 21 0
B120 Classroom 0 0 208 4 0
B123 Classroom 0 0 990 22 0
B124 Classroom 0 0 990 22 0
B125 Hallway 0 0 0 0
B126 Hallway 0 0 0 0
B127 Hallway 0 0 0 0
B128 Hallway 0 0 0 0
B200 Classroom 0 0 930 21 0
B201 Classroom 0 0 1316 29 0
B201B Classroom 0 0 224 5 0
B202 Classroom 0 0 961 21 0
B203 Classroom 0 0 1023 23 0
B204 Classroom 0 0 1311 29 0
B205 Classroom 0 0 1265 28 0
B208 Classroom 0 0 961 21 0
B209 Classroom 0 0 961 21 0
B210 Classroom 0 0 144 3 0
B218 Classroom 0 0 990 22 0
B219 Classroom 0 0 990 22 0
B222 Hallway 0 0 0 0
B223 Hallway 0 0 0 0
B224 Hallway 0 0 0 0
B225 Hallway 0 0 0 0
C101 Front of house 160 10 384 8 8
C103 Auditorium 12689 845 9310 211 211
C105 Stage 770 51 3400 77 51
C106 Classroom 0 0 1302 29 0
C107 Backstage 59 3 870 19 3
C108 Classroom 39 2 870 19 2
C109 Classroom 77 5 870 19 5
C110 Classroom 89 5 870 19 5
C111 Classroom 576 38 870 19 19
C112 Classroom 112 7 870 19 7
C113 Classroom 1414 94 2016 45 45
C114 Classroom 20 1 870 19 1
C115 Classroom 18 1 840 19 1
C116 Classroom 20 1 840 19 1
C117 Classroom 18 1 840 19 1
C118 Classroom 210 14 840 19 14
C119 Classroom 168 11 840 19 11
C121 Classroom 0 0 840 19 0
D104 Locker room 4 0 1680 38 0
D105 Locker room 5 0 1680 38 0
D106 Office 25 1 120 2 1
D109 Locker room 12 0 522 11 0
D111 Locker room 8 0 522 11 0
D112 Office 22 1 240 5 1
D113 Office 26 1 240 5 1
D114 Locker room 39 2 720 16 2
D115 Office 0 0 260 5 0
D116 Weight room 181 12 1392 31 12
D119 Classroom 91 6 1240 28 6
D126 Vestibule 42 2 0 0
D128 Hallway 249 16 0 0
E100A Library 274 18 9200 209 18
E100B Office 28 1 225 5 1
E101 Classroom 17 1 992 22 1
E102 Office 12 0 225 5 0
E103 Office 14 0 225 5 0
E104 Office 0 0 150 3 0
E105A Storage 6 0 0 0
E105B Storage 8 0 0 0
E107 Office 52 3 286 6 3
E111 Office 0 0 368 8 0
E112 Hallway 0 0 0 0
E113 Office 0 0 132 3 0
E114 Office 0 0 84 1 0
E115 Office 0 0 180 4 0
E116 Office 0 0 72 1 0
E117 Office 0 0 120 2 0
E118 Hallway 0 0 0 0
E119 Office 0 0 400 9 0
E120 Office 0 0 180 4 0
E121 Office 0 0 180 4 0
E123 Office 0 0 220 5 0
E124 Office 0 0 220 5 0
E125 Office 0 0 150 3 0
E126 Office 0 0 216 4 0
E127 Office 0 0 90 2 0
E128 Office 0 0 150 3 0
E129 Office 0 0 216 4 0
E130 Office 0 0 285 6 0
E131 Office 0 0 195 4 0
E132 Office 0 0 195 4 0
E133 Office 0 0 315 7 0
E134 Office 0 0 315 7 0
E137 Office 0 0 420 9 0
E139 Office 0 0 264 6 0
E144 Server room 0 0 368 8 0
E146 Hallway 0 0 0 0
E147 Hallway 0 0 0 0
E148 Hallway 0 0 0 0
E149 Vestibule 0 0 0 0
E150 Vestibule 0 0 0 0
E151 Hallway 0 0 0 0
E152 Hallway 0 0 0 0
E157 Hallway 0 0 0 0
E201 Office 0 0 126 2 0
E202 Office 0 0 126 2 0
E203B Office 0 0 266 6 0
E204 Office 0 0 126 2 0
E205 Office 0 0 126 2 0
E209 Office 0 0 1040 23 0
E210 Hallway 0 0 0 0
F100 Cafeteria 8136 542 8448 192 192
F101 Kitchen 1521 101 1636 37 37
F104 Kitchen 81 5 230 5 5
F106 Kitchen 99 6 306 6 6
F107 Kitchen 0 0 401 9 0
F108 Kitchen 199 13 836 19 13
F109 Maintenance 59 3 686 15 3
F110 Maintenance 40 2 256 5 2
F111 Maintenance 69 4 162 3 3
F112 Maintenance 89 5 340 7 5
F116 Kitchen 0 0 1636 37 0
F119 Engineer's office 135 9 176 4 4
F120 Hallway 149 9 0 0
F121 Hallway 1306 87 0 0
- Gym 2098 139 13184 299 139
- Office 0 0 120 2 0
- Storage 0 0 0 0
- Pool 5277 351 6426 146 146
- Principal Office 0 0 288 6 0
- Stage 3751 250 3400 77 77
Sheet Last Modified: 04-06-2021    
School:  Feltonville Arts & Sciences Middle School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
104 Classroom 256 17 775 17 17
105 Classroom 614 40 810 18 18
106 Classroom 599 39 802 18 18
107 Classroom 428 28 804 18 18
108 Classroom 352 23 802 18 18
109 Classroom 699 46 791 17 17
110 Classroom 311 20 838 19 19
111 Classroom 232 15 953 21 15
112 Classroom 311 20 633 14 14
205 Classroom 455 30 774 17 17
206 Classroom 398 26 759 17 17
207 Classroom 352 23 749 17 17
208 Classroom 313 20 812 18 18
210 Classroom 0 0 Yes 808 18 18
211 Classroom 650 43 765 17 17
212 Classroom 283 18 802 18 18
214 Classroom 605 40 632 14 14
301 Classroom 288 19 776 17 17
302 Classroom 297 19 760 17 17
303 Classroom 305 20 817 18 18
304 Classroom 700 46 811 18 18
305 Classroom 357 23 808 18 18
306 Classroom 490 32 783 17 17
307 Classroom 309 20 803 18 18
308 Classroom 211 14 Yes 809 18 18
309 Classroom 1419 94 2223 50 50
- Basement 4061 270 4615 104 104
- Cafeteria, Kitchen, Faculty Room 761 50 5110 116 50
- Classroom above 214 403 26 631 14 14
- Classroom Art Lab Computer Lab 315 21 Yes 1017 23 23
- Classroom Science Lab 1 345 23 993 22 22
- Classroom Science Lab 2 3rd Floor 344 22 989 22 22
- Classroom Science Lab 2 Right 455 30 989 22 22
- Classroom Science Lab STEM Lab Left 740 49 1631 37 37
- Dean's Office 1st Floor 31 2 Yes 170 3 3
- Dean's Office 2nd Floor 18 1 Yes 170 3 3
- Dean's Office 3rd Floor 38 2 Yes 168 3 3
- Drama Room 747 49 3095 70 49
- First Floor 5315 354 6974 158 158
- First Floor Multi-Purpose Room 572 38 3095 70 38
- Gym 1186 79 5237 119 79
- Health Room 0 0 Yes 594 13 13
- Second Floor 1094 72 4743 107 72
Sheet Last Modified: 04-29-2021    
School:  Feltonville Intermediate Elementary School
Vendor: EMCOR Exhaust Report
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 - 0 Yes 462 10 10
101 - 0 948 21 0
101A - 0 127 2 0
102 - 0 Yes 243 5 5
103 - 0 101 2 0
103A - 0 125 2 0
104 - 0 Yes 967 21 21
106 - 0 Yes 1120 25 25
107 - 0 213 4 0
108 Room 0 Yes 1436 32 32
109 Room 0 0 Yes 893 20 20
110 Room 647 43 1479 33 33
112 Room 0 Yes 1415 32 32
112A - 0 129 2 0
113 Room 0 1200 27 0
114 - 0 Yes 976 22 22
116 - 0 1064 24 0
118 Gym Office 0 0 1027 23 0
153A Small Office Inside M/O 0 108 2 0
156B Counselor #2 0 182 4 0
157 - 0 108 2 0
200 - 0 478 10 0
201 - 0 Yes 1071 24 24
202 - 0 578 13 0
202A - 0 179 4 0
203 - 0 Yes 677 15 15
203A - 0 436 9 0
204 - 0 Yes 574 13 13
205 - 0 829 18 0
206 - 0 Yes 629 14 14
206A - 0 220 5 0
207 - 0 Yes 818 18 18
207A - 0 126 2 0
208 - 0 Yes 752 17 17
208A - 0 113 2 0
209 - 0 Yes 788 17 17
210 - 225 15 Yes 740 16 16
300 - 0 Yes 858 19 19
301 - 0 Yes 491 11 11
302 - 0 Yes 765 17 17
303 - 0 Yes 667 15 15
304 - 0 505 11 0
305 - 0 Yes 626 14 14
306 - 0 Yes 769 17 17
307 - 0 Yes 1108 25 25
307A - 0 73 1 0
307B - 0 127 2 0
309 - 0 488 11 0
309A - 0 135 3 0
311 - 0 Yes 842 19 19
313 - 0 Yes 662 15 15
315 - 0 Yes 735 16 16
- Bradham Office 0 141 3 0
- Cafeteria (2nd Floor) 0 5423 123 0
- Confrence Room 0 216 4 0
- Counselor 0 132 3 0
- Custodial Staff Room 0 118 2 0
- Food Service Locker Room 0 83 1 0
- Food Service Manager's Office 0 56 1 0
- Gymnasium 0 4006 91 0
- Kitchen 0 954 21 0
- Main Office 0 505 11 0
- MPR / Auditorium 0 Yes 2669 60 60
- Nurse 0 191 4 0
- Nurse Waiting Area 0 159 3 0
- Principal's Office 0 351 7 0
- Psychologist's Office 0 66 1 0
- Storage 0 107 2 0
- Storage Room #2 0 99 2 0
- Supply Closet 0 126 2 0
- Teacher's Lounge 0 226 5 0
- 1st Floor Lunchroom 0 0 2677 60 0
- Closet 34 2 40 0 0
- 3rd Floor Lunchroom 0 4452 101 0
- Cafeteria Manager's Office 75 5 55 1 1
Sheet Last Modified: 02-23-2021      
School:  Feltonville Headstart House Fan Abated
Vendor: N/A
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Sheet Last Modified: 03-24-2021          
School:  Thomas Finletter Academics Plus Elementary School House fan Abated
Vendor: Devine   Devine Brothers Retest
School:  Finletter LSH
Vendor: Chadwick
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Finletter Main Building
101 Classroom 535 35 1056 24 24 House Fan
102 Classroom 458 30 1056 24 24 House Fan
103 Classroom 621 41 1056 24 24 House Fan
104 Classroom 595 39 870 19 19 House Fan
105 Classroom 554 36 870 19 19 House Fan
106 Classroom 1,227 81 870 19 19 House Fan
107 Classroom 980 65 870 19 19 House Fan
108 Classroom 817 54 899 20 20 House Fan
109 Classroom 876 58 899 20 20 House Fan
110 Classroom 535 35 928 21 21 House Fan
201 Classroom 477 31 1056 24 24 House Fan
202 Classroom 334 22 1056 24 22 House Fan
203 Classroom 411 27 1056 24 24 House Fan
204 Classroom 916 61 870 19 19 House Fan
205 Classroom 1,018 67 870 19 19 House Fan
206 Classroom 1,222 81 870 19 19 House Fan
207 Classroom 1,203 80 870 19 19 House Fan
208 Classroom 450 30 899 20 20 House Fan
209 Classroom 363 24 899 20 20 House Fan
210 Classroom 434 28 928 21 21 House Fan
211 Classroom 0 0 195 4 0 N/A
212 Classroom 0 0 384 8 0 N/A
301 Classroom 278 18 1056 24 18 House Fan
302 Classroom 458 30 1056 24 24 House Fan
303 Classroom 125 8 1056 24 8 House Fan
304 Classroom 288 19 870 19 19 House Fan
305 Classroom 645 43 870 19 19 House Fan
306 Classroom 289 19 870 19 19 House Fan
307 Classroom 654 43 870 19 19 House Fan
308 Classroom 345 23 899 20 20 House Fan
309 Classroom 319 21 899 20 20 House Fan
310 Classroom 675 45 928 21 21 House Fan
311 Classroom 705 47 667 15 15 House Fan
312 Classroom 0 0 275 6 0 N/A
402 Health 335 22 588 13 13 House Fan
403 Music Room 491 32 990 22 22 House Fan
- Annex Classroom 65 4 960 21 4 House Fan
- Art 882 58 1421 32 32 House Fan
- Auditorium 3,675 245 3431 77 77 House Fan
- Health Classroom 0 0 250 5 0 House Fan
- Gym/Cafe 0 Yes 3432 78 78
- Main office 0 0 Yes 322 7 7 N/A
Finletter LSH
105 Womens Staff Bathroom 0 96 2 0 AHU
105 Mens Staff Bathroom 0 77 1 0 AHU
106 Custodial 57 3 36 0 0 AHU
111 Lobby 0 187 4 0 AHU
112 Office 118 7 110 2 2 AHU
113 Office 118 7 110 2 2 AHU
114 General Storage 216 14 54 1 1 AHU
115 Multipurpose Room 2,476 165 2166 49 49 AHU
116 Corridor #2 0 120 2 0 AHU
123 Custodial Storage 76 5 54 1 1 AHU
125 Academic Storage 66 4 18 0 0 AHU
A Classroom 341 22 986 22 22 AHU
B Classroom 332 22 986 22 22 AHU
C Classroom 341 22 986 22 22 AHU
D Classroom 332 22 986 22 22 AHU
E Classroom 327 21 986 22 21 AHU
F Classroom 327 21 986 22 21 AHU
G Classroom 327 21 986 22 21 AHU
H Classroom 327 21 986 22 21 AHU
I Classroom 293 19 986 22 19 AHU
J Classroom 359 23 986 22 22 AHU
K Classroom 293 19 986 22 19 AHU
L Classroom 359 23 986 22 22 AHU
- Custodial Office 0 Yes 0 0 AHU
- Teachers Lounge 0 No 288 6 0 AHU
Sheet Last Modified: 03-22-2021    
School:  Fitler Academic Plus Elementary School
Vendor: Devine Meehan Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
105 Classroom 707 47 1024 23 23 House Fan
106 Classroom 796 53 720 16 16 House Fan
107 Classroom 0 0 Yes 720 16 16 House Fan
201 Classroom 834 55 1024 23 23 House Fan
202 Classroom 879 58 1024 23 23 House Fan
203 Classroom 510 34 1024 23 23 House Fan
204 Classroom 951 63 1024 23 23 House Fan
205 Classroom 716 47 1024 23 23 House Fan
206 Classroom 668 44 720 16 16 House Fan
207 Classroom 78 5 Yes 720 16 16 House Fan
301 Classroom 860 57 720 16 16 House Fan
302 Classroom 550 36 1024 23 23 House Fan
303 Classroom 538 35 1024 23 23 House Fan
304 Classroom 957 63 1024 23 23 House Fan
305 Classroom 746 49 1024 23 23 House Fan
306 Classroom 637 42 720 16 16 House Fan
307 Classroom 364 24 Yes 720 16 16 House Fan
- Combo room 883 58 1024 23 23 House Fan
- Gym 1325 88 1344 30 30 House Fan
- Library 1641 109 2400 54 54 House Fan
- Main office 850 56 1156 26 26 House Fan
- Restroom 781 52 660 15 15 House Fan
- Counselors Office 1062 70 175 3 3 ERU
- Cafeteria 0.0 0 1944 44 0 NA
- Nurses Office 0 Yes 75 1 1
Sheet Last Modified: 03-12-2021    
School:  Aloysius L. Fitzpatrick Elementary School
Vendor: Devine Brothers Part 2 Part 3
School:  Aloysius L. Fitzpatrick Elementary School Annex
Vendor: Devine Brothers Part 2 Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
B-10 Classroom 313 20 704 16 16 Unit Ventilator
100 Classroom 298 19 660 15 15 Unit Ventilator
101 Classroom 281 18 744 16 16 Unit Ventilator
102 Classroom 315 21 840 19 19 Unit Ventilator
103 Classroom 289 19 840 19 19 Unit Ventilator
104 Classroom 337 22 805 18 18 Unit Ventilator
105 Classroom 306 20 840 19 19 Unit Ventilator
106 Classroom 293 19 840 19 19 Unit Ventilator
107 Classroom 287 19 576 13 13 Unit Ventilator
108 Classroom 409 27 828 18 18 Unit Ventilator
109 Classroom 26 1 Yes 600 13 13 Unit Ventilator
110 Classroom 340 22 840 19 19 Unit Ventilator
112 Classroom 341 22 828 18 18 Unit Ventilator
200 Classroom 319 21 840 19 19 Unit Ventilator
201 Classroom 275 18 840 19 18 Unit Ventilator
202 Classroom 300 20 840 19 19 Unit Ventilator
203 Classroom 309 20 840 19 19 Unit Ventilator
204 Classroom 290 19 840 19 19 Unit Ventilator
205 Classroom 314 20 840 19 19 Unit Ventilator
206 Library 656 43 1680 38 38 Unit Ventilator
207 Classroom 326 21 425 9 9 Unit Ventilator
210 Classroom 293 19 840 19 19 Unit Ventilator
212 Classroom 334 22 840 19 19 Unit Ventilator
214 Classroom 304 20 840 19 19 Unit Ventilator
216 Classroom 325 21 840 19 19 Unit Ventilator
218 Classroom 307 20 840 19 19 Unit Ventilator
300 Classroom 289 19 864 19 19 Unit Ventilator
301 Classroom 305 20 840 19 19 Unit Ventilator
302 Classroom 281 18 840 19 18 Unit Ventilator
303 Classroom 299 19 840 19 19 Unit Ventilator
304 Classroom 329 21 840 19 19 Unit Ventilator
305 Classroom 294 19 840 19 19 Unit Ventilator
306 Classroom 607 40 1704 38 38 Unit Ventilator
307 Classroom 340 22 425 9 9 Unit Ventilator
310 Classroom 299 19 840 19 19 Unit Ventilator
312 Classroom 326 21 840 19 19 Unit Ventilator
314 Classroom 304 20 840 19 19 Unit Ventilator
316 Classroom 329 21 840 19 19 Unit Ventilator
318 Classroom 337 22 840 19 19 Unit Ventilator
- Auditorium 92 6 1825 41 6 AHU
B-1 Classroom 466 31 966 21 21 Unit Ventilator
B-2 Classroom 287 19 966 21 19 Unit Ventilator
B-4 Classroom 236 15 704 16 15 Unit Ventilator
B-8 Classroom 269 17 792 18 17 Unit Ventilator
- Cafeteria 72 4 2835 64 4 Unit Ventilator
- Gymnasium 72 4 Yes 3922 89 89 AHU
- Main Office 284 18 1000 22 18 Unit Ventilator
- Music 29 1 768 17 1 Unit Ventilator
Annex Building
9 Classroom 165 11 Yes 1040 23 23 Unit Ventilator
10 Classroom 310 20 864 19 19 Unit Ventilator
11 Classroom 311 20 962 21 20 Unit Ventilator
12 Classroom 291 19 1040 23 19 Unit Ventilator
Sheet Last Modified: 04-14-2021    
School:  Edwin Forrest Elementary School
Vendor: Devine Brothers
School:  Edwin Forrest Elementary School- Little School House
Vendor: Devine Brothers Devine Brothers Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Edwin Forrest Elementary School Main Building
- Auditorium 955 63 3,552 80 63 Unit Ventilator
- PreK 281 18 1,084 24 18 Unit Ventilator
101 admin 0 Yes 920 20 20 House Fan
102 2nd 0 Yes 690 15 15 House Fan
103 admin 0 Yes 736 16 16 House Fan
104 Specialist K-6 0 Yes 690 15 15 House Fan
105 2nd grade 0 Yes 690 15 15 House Fan
106 2nd 0 Yes 690 15 15 House Fan
107 4th  0 Yes 690 15 15 House Fan
108 2nd 0 Yes 736 16 16 House Fan
109 2nd 0 Yes 690 15 15 House Fan
- Main Office 0 Yes 336 7 7 House Fan
110 2nd 0 Yes 736 16 16 House Fan
- Principal Office 0 Yes 210 4 4 House Fan
- Nurses Office 0 Yes 264 6 6 House Fan
201 4th 0 Yes 736 16 16 House Fan
202 4th 0 Yes 690 15 15 House Fan
203 4th 0 Yes 736 16 16 House Fan
204 4th 0 Yes 690 15 15 House Fan
205 3rd 0 Yes 690 15 15 House Fan
206 3rd 0 Yes 690 15 15 House Fan
207 3rd 0 Yes 690 15 15 House Fan
208 3rd 0 Yes 736 16 16 House Fan
209 3rd 0 Yes 690 15 15 House Fan
210 3rd 0 Yes 736 16 16 House Fan
211 small group instruction  0 Yes 192 4 4 House Fan
212 counselor office 0 Yes 108 2 2 House Fan
- Teachers Lounge 0 Yes 253 5 5 House Fan
301 6th 0 Yes 736 16 16 House Fan
302 6th 0 Yes 690 15 15 House Fan
303 6th 0 Yes 736 16 16 House Fan
304 5th 0 Yes 690 15 15 House Fan
305 5th 0 Yes 690 15 15 House Fan
306 6th 0 Yes 690 15 15 House Fan
307 6th 0 Yes 690 15 15 House Fan
308 5th 0 Yes 736 16 16 House Fan
309 5th 0 Yes 690 15 15 House Fan
310 5th 0 Yes 736 16 16 House Fan
311 3rd fl computer room 0 Yes 720 16 16 House Fan
312 Small group instruction  0 Yes 192 4 4 House Fan
314 Yes 180 House Fan
- Speech Room 0 Yes 180 4 4 House Fan
b1 music room 0 Yes 736 16 16 House Fan
b2a Small group instruction  0 Yes 352 8 8 House Fan
b2 Small group instruction 0 Yes 352 8 8 House Fan
b3 Small group instruction 0 Yes 506 11 11 House Fan
B4 Computer Lab 0 Yes 968 22 22 House Fan
- Gym/caf 0 Yes 3,432 78 78 N/A
- Kitchen 0 Yes 609 13 13 House Fan
- 2nd Flr Counselor Office 0 Yes 195 4 4 House Fan
- 3rd Flr Counselor Office 0 Yes 108 2 2 House Fan
Edwin Forrest Elementary School- Little School House
P1 - 348 23 986 22 22 Unit Ventilator
P2 - 303 20 986 22 20 Unit Ventilator
P3 - 362 24 986 22 22 Unit Ventilator
P4 - 327 21 986 22 21 Unit Ventilator
P5 - 304 20 986 22 20 Unit Ventilator
P6 - 390 26 812 18 18 Unit Ventilator
P7 - 308 20 812 18 18 Unit Ventilator
P8 - 308 20 812 18 18 Unit Ventilator
P9 - 382 25 812 18 18 Unit Ventilator
P10 - 312 20 812 18 18 Unit Ventilator
P11 - 311 20 812 18 18 Unit Ventilator
P12 - 316 21 812 18 18 Unit Ventilator
P13 - 327 21 812 18 18 Unit Ventilator
- Administration and Corridors 727 48 576 13 13 AHU
- Cafeteria 78 5 Yes 2,014 45 45 AHU
- Faculty Break Room 312 20 210 4 4 Unit Ventilator
Sheet Last Modified: 04-08-2021    
School:  Fox Chase Elementary School
  Fox Chase Farm
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Fox Chase Main Building
101 Classroom 338 22 840 19 19 Unit Ventilator
102 Classroom 316 21 1104 25 21 Unit Ventilator
103 Classroom 291 19 989 22 19 Unit Ventilator
104 Classroom 302 20 960 21 20 Unit Ventilator
105 Classroom 312 20 984 22 20 Unit Ventilator
105A Office 0 0 Yes 216 4 4 Unit Ventilator
107 Examing Room 0 Yes 234 5 5 N/A
107A Office 0 0 Yes 225 5 5 N/A
108 Classroom 0 Yes 216 4 4
109 Classroom 315 21 1035 23 21 Unit Ventilator
110 Classroom 300 20 1032 23 20 Unit Ventilator
111 Classroom 155 10 Yes 1012 23 23 Unit Ventilator
112 Classroom 161 10 Yes 1081 24 24 Unit Ventilator
201 Classroom 341 22 943 21 21 Unit Ventilator
202 Classroom 382 25 897 20 20 Unit Ventilator
203 Classroom 382 25 897 20 20 Unit Ventilator
204 Classroom 237 15 462 10 10 Unit Ventilator
205 Classroom 192 12 Yes 936 21 21 Unit Ventilator
206 Classroom 391 26 912 20 20 Unit Ventilator
207 Classroom 0 0 Yes 943 21 21 Unit Ventilator
208 Classroom 71 4 Yes 960 21 21 Unit Ventilator
3340 Ag Room 0 Yes 1283 29 29 Unit Ventilator
- 1st Floor Teacher's Lounge 0 0 336 7 0 N/A
A-1 Classroom 281 18 836 19 18 Unit Ventilator
A-2 Classroom 283 18 836 19 18 Unit Ventilator
A-3 Classroom 319 21 836 19 19 Unit Ventilator
A-4 Classroom 252 16 836 19 16 Unit Ventilator
A-5 Classroom 241 16 836 19 16 Unit Ventilator
A-6 Classroom 295 19 836 19 19 Unit Ventilator
C-1 Classroom 0 Yes 1560 35 35 N/A
C-4 Classroom 0 Yes 380 8 8 N/A
- Annex 0 0 1283 29 0 Unit Ventilator
- Auditorium 0 0 4420 100 0 AHU
Instrument Room Stage Area 0 Yes 228 5 5
- Cafeteria 704 46 2340 53 46 Unit Ventilator
- Counselor 0 0 230 5 0 N/A
- Dental Office 0 0 Yes 208 4 4 N/A
- Examining Room 0 0 234 5 0 N/A
- Gym 0 0 5429 123 0 AHU
- Kitchen Storage 296 19 260 5 5 Unit Ventilator
- Main Office 0 0 Yes 226 5 5 N/A
- Music Room 581 38 1,400 31 31 Unit Ventilator
- Nurse 0.0 0 Yes 234 5 5 N/A
- Principal 0 0 Yes 234 5 5 N/A
Fox Chase Farm
- Data Closet 14.0 0 30 0 0 AC
- Kitchen 190.0 12 156 3 3 AC
- Men's Bathroom 56.0 3 225 5 3 AC
- Teaching Area Classroom 658.0 43 1692 38 38 AC
- Women's Bathroom 55.0 3 225 5 3 AC
Sheet Last Modified: 04-23-2021      
School:  Anne Frank Elementary School
Vendor: Devine Brothers Devine Retest  
School:  Anne Frank Elementary School- Little School House
Vendor: Devine Brothers Devine Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Frank Main Building
100 Classroom 283 18 Yes 864 19 19 Unit Ventilator
101 Classroom 284 18 Yes 864 19 19 Unit Ventilator
102 Classroom 236 15 Yes 864 19 19 Unit Ventilator
103 Classroom 260 17 Yes 864 19 19 Unit Ventilator
104 Classroom 56 3 Yes 864 19 19 Unit Ventilator
106 Classroom 0 0 240 5 0 Unit Ventilator UV does not work.
108 Classroom 191 12 Yes 456 10 10 Unit Ventilator Unit low on OA
109 Classroom 0 0 Yes 456 10 10 Unit Ventilator Unit not running
110 Classroom 305 20 Yes 1,032 23 23 Unit Ventilator
125 Classroom 348 23 672 15 15 Unit Ventilator
- Admin Office 0 0 135 3 0 Unit Ventilator Unit not running
200 Classroom 283 18 Yes 864 19 19 Unit Ventilator
201 Library 60 4 Yes 875 19 19 Unit Ventilator Fan going backwards
202 Classroom 293 19 864 19 19 Unit Ventilator
203 Classroom 304 20 864 19 19 Unit Ventilator
204 Classroom 322 21 864 19 19 Unit Ventilator
205 Classroom 215 14 Yes 864 19 19 Unit Ventilator
206 Classroom 205 13 240 5 5 Unit Ventilator
207 Classroom 257 17 Yes 864 19 19 Unit Ventilator
208 Classroom 299 19 864 19 19 Unit Ventilator
209 Classroom 203 13 Yes 864 19 19 Unit Ventilator
210 Classroom 225 15 Yes 864 19 19 Unit Ventilator
211 Classroom 333 22 864 19 19 Unit Ventilator
212 Classroom 153 10 Yes 864 19 19 Unit Ventilator
213 Classroom 226 15 Yes 864 19 19 Unit Ventilator
214 Classroom 0 Yes 864 19 19
215 Classroom 284 18 Yes 864 19 19 Unit Ventilator
- Library 0 0 Yes 864 19 19 Unit Ventilator Unit not running
300 Classroom 241 16 Yes 864 19 19 Unit Ventilator
301 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
302 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
303 Classroom 185 12 Yes 864 19 19 Unit Ventilator
304 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
305 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
306 Classroom 0 0 Yes 240 5 5 Unit Ventilator Unit not running
307 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
308 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
309 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
310 Classroom 127 8 Yes 864 19 19 Unit Ventilator
311 Classroom 42 2 Yes 864 19 19 Unit Ventilator
312 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
313 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
315 Classroom 0 0 Yes 864 19 19 Unit Ventilator Unit not running
Auditorium 0 0 3,180 72 0
Cafeteria 0 0 Yes 2,720 61 61 Hyrdroxyl
Gymnasium 0 0 Yes 3,657 83 83 Hydroxyl
Gymnasium Office 0 165 3 0
- Counselor Office 0 0 Yes 132 3 3 NA
- Main Office 60 4 Yes 951 21 21 Unit Ventilator Fan going backwards
- Nurses Office 0 0 Yes 304 6 6 NA
- Principals Office 0 0 Yes 210 4 4 NA
- Vice Principals Office 0 0 Yes 72 1 1 NA
Frank LSH
1 Classroom 931.0 62 928 21 21 BCU 90% OA damper 70% RA Damper. OA & RA dampers need to be realigned
2 Classroom 595.0 39 928 21 21 BCU 95% OA damper 70% RA Damper. OA & RA dampers need to be realigned
3 Classroom 945.0 63 928 21 21 BCU 90% OA damper 70% RA Damper. OA & RA dampers need to be realigned
4 Classroom 610.0 40 928 21 21 BCU 95% OA damper 70% RA Damper. OA & RA dampers need to be realigned
5 Classroom 322.0 21 928 21 21 BCU Damper at 35%
6 Classroom 307.0 20 Yes 928 21 21 BCU
7 Classroom 310.0 20 Yes 928 21 21 BCU
8 Classroom 305.0 20 Yes 928 21 21 BCU
9 Classroom 370.0 24 928 21 21 BCU Damper at 35%
10 Classroom 329.0 21 928 21 21 BCU Damper at 35%
11 Classroom 396.0 26 928 21 21 BCU
12 Classroom 319.0 21 928 21 21 BCU
- Bathrooms, Corridor and Main Entrance 284.0 18 225 5 5 FCU OA damper 5%
- Corner Facilities/Guidance Office 0.0 0 196 4 0 FCU Not running
- Counselor Office 0 0 Yes 100 2 2 FCU Unit not running.
- Janitor Close and Storage Rooms 262.0 17 24 0 0 FCU OA damper 10%
- Main Office 587.0 39 315 7 7 FCU OA damper 0%. BC filter cover plate & filter not installed. Air from boiler room space entering unit. BC coil is very dirty and needs to be cleaned.
- Cafeteria 922 61 1,696 38 38 BCU Damper at 30%
- Art Teacher Office 102 6 100 2 2 BCU
- ESL Teacher Office 110 7 100 2 2 BCU
- ESL Room 241 16 80 1 1 BCU Damper at 50%
Frank Annex
7 Classroom 36 2 Yes 1,080 24 24 Unit Ventilator Unit needs repairs.
8 Classroom 235 15 Yes 1,080 24 24 Unit Ventilator
- gang girlsnboys 0 480 10 0 N/A
Sheet Last Modified: 03-17-2021    
School:  Frankford High School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
9 Classroom 122 8 1836 41 8 Unit Ventilator
11 Classroom 0 0 2011 45 0 Unit Ventilator
12 Classroom 0 0 2011 45 0 Unit Ventilator
14 Classroom 167 11 812 18 11 Unit Ventilator
15-14 Classroom 0 0 N/A 0 0 Unit Ventilator
15A Classroom 107 7 812 18 7 Unit Ventilator
16 Classroom 0 0 476 10 0 Unit Ventilator
17 Classroom 0 0 952 21 0 Unit Ventilator
18 Classroom 76 5 884 20 5 Unit Ventilator
19 Classroom 55 3 576 13 3 Unit Ventilator
20 Classroom 0 0 1023 23 0 Unit Ventilator
124 Classroom 210 14 1702 38 14 Unit Ventilator
222 Classroom 80 5 889 20 5 Unit Ventilator
223 Classroom 163 10 991 22 10 Unit Ventilator
224 Classroom 80 5 991 22 5 Unit Ventilator
225 Classroom 50 3 1,005 22 3 Unit Ventilator
226 Classroom 149 9 991 22 9 Unit Ventilator
227 Classroom 128 8 864 19 8 Unit Ventilator
228 Classroom 255 17 899 20 17 Unit Ventilator
229 Classroom 0 0 462 10 0 Unit Ventilator
230 Classroom 181 12 1,001 22 12 Unit Ventilator
231A Classroom 286 19 986 22 19 Unit Ventilator
232A Classroom 80 5 1,048 23 5 Unit Ventilator
233 Classroom 40 2 1120 25 2 Unit Ventilator
326 Classroom 91 6 775 17 6 Unit Ventilator
327 Classroom 48 3 775 17 3 Unit Ventilator
330-331 Classroom 166 11 969 22 11 Unit Ventilator
332 Classroom 84 5 1505 34 5 Unit Ventilator
333 Classroom 0 0 1505 34 0 Unit Ventilator
335 Classroom 0 0 1120 25 0 Unit Ventilator
- IMC 264 17 5398 122 17 Unit Ventilator
Sheet Last Modified: 04-21-2021    
School:  Benjamin Franklin Elementary School
Vendor: Devine Devine 2nd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Basement Boy's Restroom 0 0 234 5 0 AHU
- Basement Girl's Restroom 0 0 234 5 0 AHU
- 1st Floor Boy's Restroom 27 1 234 5 1 AHU
- 1st Floor Girl's Restroom 40 2 234 5 2 AHU
- 2nd Floor Girl's Restroom 28 1 234 5 1 AHU
- 2nd Floor Boy's Restroom 40 2 234 5 2 AHU
1 Classroom 0 Yes 304 6 6 Unit Ventilator
1B Classroom 0 Yes 667 15
6 Classroom 350 23 780 17 17 Unit Ventilator
7 Cafeteria 1,972 131 2800 63 63 AHU
8 Classroom 299 19 780 17 17 Unit Ventilator
- Kitchen 1,585 105 1023 23 23 AHU
- Kitchen Office 225 15 80 1 1 AHU
101 Classroom 0 Yes 720 16 16 House Fan
102 Classroom 0 Yes 720 16 16 House Fan
103 Classroom 0 Yes 720 16 16 House Fan
104 Classroom 0 Yes 650 14 14 House Fan
105 Classroom 0 Yes 650 14 14 House Fan
106 Classroom 0 Yes 650 14 14
107 Classroom 0 720 16 0 House Fan
110 Classroom 352 23 780 17 17 House Fan
111 Classroom 321 21 780 17 17 Unit Ventilator
112 Classroom 300 20 780 17 17 Unit Ventilator
113 Classroom 312 20 780 17 17 Unit Ventilator
114 Classroom 410 27 780 17 17 Unit Ventilator
115 Classroom 346 23 780 17 17 Unit Ventilator
116 Asst Principals Office 352 23 207 4 4 Unit Ventilator
117 Classroom 332 22 609 13 13 Unit Ventilator
201 Classroom 0 Yes 720 16 16 House Fan
202 Classroom 0 Yes 720 16 16 House Fan
203 Classroom 0 Yes 720 16 16 House Fan
204 Classroom 0 Yes 650 14 14 House Fan
205 Classroom 0 Yes 650 14 14 House Fan
206 Classroom 0 Yes 650 14 14 House Fan
207 Classroom 0 Yes 650 14 14 House Fan
208 Classroom 0 Yes 720 16 16 House Fan
209 Library 568 37 Yes 1600 36 36 Unit Ventilator
210 Trs Lounge 330 22 380 8 8 Unit Ventilator
212 TECH LAB 487 32 1600 36 32 Unit Ventilator
214 Classroom 305 20 780 17 17 Unit Ventilator
215 Classroom 325 21 780 17 17 Unit Ventilator
216 Classroom 325 21 780 17 17 Unit Ventilator
217 Classroom 287 19 780 17 17 Unit Ventilator
218 Classroom 323 21 780 17 17 Unit Ventilator
219 Classroom 291 19 780 17 17 Unit Ventilator
220 Counselor's Office 287 19 207 4 4 Unit Ventilator
221 Classroom 314 20 605 13 13 Unit Ventilator
- Faculty Lounge 0 0 160 3 0 Unit Ventilator
- Nurses Office 0 Yes 132 3 3
- Psychology Office 33 2 90 2 2 Unit Ventilator
- Main Office 0 Yes 220 5 5
 
 
 
Sheet Last Modified: 04-19-2021    
School:  Benjamin Franklin High School
Vendor: Devine Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Weight room 63 4 713 16 4 HV+ AHU
2 Weight room 0 0 775 17 0 HV
3 Weight room 0 0 1632 37 0 HV
4 Welding 9254 616 2176 49 49 MUA
4A Classroom 280 18 640 14 14 AC
6 Classroom 0 0 Yes 2655 60 60 AHU
7 Classroom 0 0 216 4 0 AHU
8 Classroom 0 0 588 13 0 AHU
9 Classroom 0 0 621 14 0 AHU
10 Machine Shop 810 54 2961 67 54 HV
11 Classroom 176 11 1740 39 11 AC
12 Classroom 842 56 1581 35 35 HV
13 Classroom 175 11 1239 28 11 AC
13A Classroom 93 6 552 12 6 AC
14 Classroom 136 9 756 17 9 AC
15 Classroom 155 10 912 20 10 AC
15A Practice Room 77 5 77 1 1 HV
15B Practice Room 188 12 77 1 1 HV
15C Practice Room 143 9 77 1 1 HV
15D Music Office 142 9 180 4 4 HV
16 Lecture Hall 2049 136 2068 47 47 HV
17 Lecture Hall 387 25 2280 51 25 HV
18 Classroom 803 53 1080 24 24 AC
19 Classroom 781 52 1344 30 30 AC
20 Classroom 635 42 828 18 18 AC
100 Classroom 280 18 775 17 17 UV
102 Classroom 382 25 961 21 21 UV
110 Room 0 0 195 4 0 FC
111A Room 0 0 104 2 0 FC
113 Room 0 0 315 7 0 FC
115 Room 0 0 352 8 0 FC
116 Room 0 0 196 4 0 FC
150 Kitchen 0 0 1955 44 0 RTU
152 Cafeteria 0 0 3363 76 0 RTU
200 Living Room 140 9 819 18 9 UV
201 Classroom 217 14 792 18 14 UV
202 Office-A 201 13 600 13 13 UV
202 Office-B 171 11 396 9 9 UV
204 Principal Office 41 2 180 4 2 OAS-1A & OAS-1B
206 Co-Principal 40 2 120 2 2 OAS-1A & OAS-1B
207 Classroom 257 17 792 18 17 UV
209 Storage 189 12 165 3 3 UV
209B Office 287 19 180 4 4 UV
211 Classroom 358 23 713 16 16 UV
212 Work Room 49 3 297 6 3 OAS-1A & OAS-1B
214 Office 57 3 121 2 2 OAS-1A & OAS-1B
215 Classroom 295 19 806 18 18 UV
216 Conference 44 2 72 1 1 OAS-1A & OAS-1B
217 Learning Lounge 263 17 572 13 13 UV
218 College Office 50 3 132 3 3 OAS-1A & OAS-1B
220 College 49 3 120 2 2 OAS-1A & OAS-1B
222 Health Suite 45 3 256 5 3 OAS-1A & OAS-1B
222A Nurse Office 50 3 108 2 2 OAS-1A & OAS-1B
222B Exam 48 3 99 2 2 OAS-1A & OAS-1B
223A Dining 856 57 1760 40 40 UV
229 Classroom 0 Yes 589 13 13
231 Office 150 10 210 4 4 UV
232 Health Suite 221 14 464 10 10 OAS-1A & OAS-1B
232B Storage 0 0 45 1 0 OAS-1A & OAS-1B
232C Nurse Health 0 0 99 2 0 AC
232D Nurse Health 0 0 106 2 0 AC
238 Conference 119 7 228 5 5 OAS-1A & OAS-1B
240 Office 131 8 143 3 3 OAS-1A & OAS-1B
242 Storage 146 9 71 1 1 OAS-1A & OAS-1B
244 Office 124 8 143 3 3 OAS-1A & OAS-1B
246 Open Work Area 119 7 252 5 5 OAS-1A & OAS-1B
248 Office 135 9 143 3 3 OAS-1A & OAS-1B
250 Main Office 408 27 675 15 15 UV
300 Collaboration 25 1 264 6 1 OAS-1A & OAS-1B
301 Classroom 192 12 792 18 12 UV
302 Classroom 233 15 900 20 15 UV
304 Classroom 255 17 851 19 17 UV
306 Classroom 218 14 897 20 14 UV
308 Classroom 206 13 759 17 13 UV
309 Classroom 308 20 736 16 16 UV
311 Classroom 301 20 576 13 13 UV
315 Classroom 138 9 759 17 9 UV
316 Classroom 482 32 759 17 17 UV
317 Classroom 182 12 Yes 1173 26 26 UV
318 Classroom 146 9 Yes 713 16 16 UV
319 Classroom 209 13 736 16 13 UV
320 Classroom 165 11 736 16 11 UV
321A Office 96 6 154 3 3 UV
321B Storage 289 19 154 3 3 UV
322 Classroom 154 10 Yes 736 16 16 UV
324 Classroom 0 0 558 12 0 UV
326 Classroom 225 15 900 20 15 UV
327 Office 236 15 240 5 5 UV
328 LSS Community Rm 43 2 288 6 2 OAS-1A & OAS-1B
329 Classroom 224 14 936 21 14 UV
400 Collaboration 0 0 264 6 0 OAS-1A & OAS-1B
401 Classroom 0 0 759 17 0 UV
402 Classroom 264 17 1311 29 17 UV
404 Classroom 250 16 345 7 7 UV
406 Classroom 330 22 1311 29 22 UV
407 Classroom 258 17 736 16 16 UV
409 Classroom 97 6 736 16 6 UV
411 Classroom 648 43 552 12 12 UV
415 Classroom 178 11 759 17 11 UV
416 Classroom 155 10 851 19 10 UV
417 Classroom 3 0 713 16 0 UV
418 Classroom 182 12 851 19 12 UV
419 Classroom 219 14 736 16 14 UV
420 Classroom 162 10 828 18 10 UV
421 Office 86 5 529 12 5 UV
422 Classroom 132 8 828 18 8 UV
424 Office 158 10 99 2 2 UV
426 Classroom 73 4 900 20 4 UV
427 Classroom 339 22 1200 27 22 UV
428 Collaboration 62 4 444 10 4 OAS-1A & OAS-1B
500 Collaboration 22 1 322 7 1 OAS-1A & OAS-1B
501 Classroom 201.0 13 825 18 13 UV
502 Classroom 681.0 45 1380 31 31 UV
504 Storage 216.0 14 352 8 8 UV
506 Classroom 477.0 31 1357 30 30 UV
507 Classroom 155.0 10 851 19 10 UV
509 Classroom 194.0 12 805 18 12 UV
515 Classroom 269.0 17 920 20 17 UV
516 Classroom 162.0 10 1012 23 10 UV
517 Classroom 647.0 43 943 21 21 UV
518 Classroom 73.0 4 851 19 4 UV
519 Classroom 201 13 693 15 13 UV
520 Classroom 515.0 34 858 19 19 UV
522A Office 21 1 100 2 1 OAS-1A & OAS-1B
523 Classroom 950 63 1344 30 30 UV
524 Staff Lounge 527 35 375 8 8 UV
526 Classroom 1235 82 1175 26 26 UV
601 Classroom 231.0 15 936 21 15 UV
602 Classroom 325.0 21 920 20 20 UV
603 Production Studio 25.0 1 160 3 1 OAS-1A & OAS-1B
603A Control Rm 25.0 1 96 2 1 OAS-1A & OAS-1B
604 Classroom 568.0 37 460 10 10 UV
605 Classroom 609.0 40 1152 26 26 UV
606 Classroom 140.0 9 621 14 9 UV
609 Classroom 614.0 40 900 20 20 UV
611 Classroom 256.0 17 900 20 17 UV
612 Classroom 208.0 13 714 16 13 UV
613 Classroom 564.0 37 792 18 18 UV
614 Classroom 290.0 19 756 17 17 UV
615 Storage 261.0 17 336 7 7 UV
616 Classroom 265.0 17 900 20 17 UV
617 Office 92.0 6 300 6 6 UV
620 Classroom 750.0 50 900 20 20 UV
620 Classroom 567.0 37 2304 52 37 UV
- Auditorium 1,102.0 73 8648 196 73 AHU
- Faculty/Office 0.0 0 330 7 0 AC
- Practice Room 1 0 0 77 1 0 HV
- Practice Room 2 0 0 77 1 0 HV
- Practice Room 3 0 0 77 1 0 HV
- Kitchen Office 15 1 99 2 1 RTU
- Weight Room 163 10 1632 37 10 AHU
Sheet Last Modified: 04-27-2021    
School:  Franklin Learning Center
Vendor: Devine
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 318 21 840 19 19
101/102 Classroom 144 9 1426 32 9
103 / 104 Conference 811 54 1612 36 36
105 Classroom 186 12 690 15 12
108 ESOL 0 242 5 0
111 Classroom 44 2 221 5 2
120 Classroom 528 35 625 14 14
121 Classroom 486 32 806 18 18
122 Classroom 640 42 744 16 16
123 Classroom 705 47 660 15 15
124 Classroom 504 33 266 6 6
125 Classroom 615 41 575 13 13
126 Classroom 615 41 275 6 6
129 Classroom 238 15 675 15 15
132 Classroom 264 17 414 9 9
132a Classroom 391 26 690 15 15
133 Classroom 730 48 759 17 17
200 Classroom 447 29 950 21 21
201 Classroom 372 24 713 16 16
202 Classroom 349 23 690 15 15
203 / 204 Classroom 655 43 1426 32 32
205 Classroom 294 19 713 16 16
206 Classroom 0 0 198 4 0
207 Classroom 37 2 925 21 2
208 Classroom 314 20 782 17 17
209 Classroom 638 42 875 19 19
210 Classroom 661 44 782 17 17
212 Classroom 621 41 851 19 19
213 Classroom 0 0 165 3 0
214 Classroom 580 38 625 14 14
215 Classroom 446 29 720 16 16
216 Classroom 486 32 960 21 21
217 Classroom 410 27 960 21 21
218 Classroom 377 25 600 13 13
220 Classroom 174 11 980 22 11
221 IMC/ Library 433 28 1536 34 28
221 Office 210 14 154 3 3
300 Classroom 88 5 900 20 5
301 Classroom 215 14 506 11 11
302 Classroom 403 26 975 22 22
303 Classroom 368 24 936 21 21
304 Classroom 287 19 575 13 13
305 Classroom 392 26 713 16 16
306 Classroom 168 11 297 6 6
307 Classroom 729 48 700 15 15
309 Classroom 443 29 480 10 10
310 Medical Classroom 1312 87 1403 31 31
310 Doctor's Office 3 0 77 1 0
310 Bathroom 12 0 120 2 0
310 Storage 11 0 140 3 0
312 Classroom 538 35 575 13 13
312 Councelor 0 0 950 21 0
315 Classroom 255 17 675 15 15
316 Classroom 353 23 644 14 14
317 Classroom 465 31 950 21 21
318 Classroom 465 31 897 20 20
318 Prep Room / Chemistry 0 156 3 0
318 Secure Closet 0 0 0
319 Classroom 263 17 575 13 13
321 Classroom 506 33 588 13 13
322 Computer 0 0 299 6 0
323 Classroom 374 24 598 13 13
324 Classroom 104 6 552 12 6
325 Classroom 118 7 594 13 7
- Cafeteria 1320 88 2808 63 63
- Gym 0 3649 82 0
- Office 58 3 230 5 3
- Office 223 14 567 12 12
Sheet Last Modified: 04-29-2021    
School:  Horace H. Furness High School
Vendor: Chadwick Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 0 1224 27 0
3 Classroom 0 672 15 0
4 Classroom 0 840 19 0
5 Classroom 0 840 19 0
101 Classroom 306 20 667 15 15
102 Classroom 0 768 17 0
103 classroom 297 19 667 15 15
104 Classroom 0 896 20 0
105 classroom 0 667 15 0
106 classroom 326 21 667 15 15
107 Library 1463 97 2448 55 55
112 Classroom 0 448 10 0
201 classroom 272 18 735 16 16
201A Room 0 448 10 0
202 Classroom 0 1536 34 0
203 classroom 540 36 874 19 19
204 classroom 443 29 814 18 18
205 classroom 392 26 667 15 15
206 classroom 0 667 15 0
207 classroom 0 720 16 0
208 classroom 328 21 660 15 15
209 classroom 0 725 16 0
210 classroom 0 696 15 0
211 classroom 319 21 696 15 15
212 classroom 359 23 696 15 15
213 classroom 316 21 696 15 15
214 classroom 0 696 15 0
215 Classroom 0 576 13 0
218 classroom 367 24 720 16 16
219A classroom 0 783 17 0
219B classroom 275 18 1100 25 18
220 classroom 292 19 690 15 15
221 classroom 490 32 770 17 17
221A classroom 380 25 770 17 17
222 classroom 0 161 3 0
222A Room 0 560 12 0
301A classroom 301 360 24 690 15 15
301B classroom 301 345 23 672 15 15
302A classroom 302 272 18 1056 24 18
302B classroom 302 356 23 624 14 14
303 classroom 438 29 770 17 17
304 classroom 0 690 15 0
305 classroom 0 672 15 0
306 classroom 0 720 16 0
307 classroom 0 720 16 0
308 classroom 246 16 720 16 16
309 classroom 0 720 16 0
310A classroom 0 1008 22 0
310b classroom 0 1344 30 0
311A classroom 201 13 1008 22 13
311B classroom 0 1148 26 0
312A classroom 0 960 21 0
312B classroom 0 400 9 0
313A classroom 175 11 1008 22 11
313B classroom 0 480 10 0
314 Classroom 0 448 10 0
315 Classroom 0 392 8 0
316 classroom 73 4 696 15 4
317A classroom 0 1137 25 0
317B classroom 117 7 1008 22 7
318A classroom 0 1152 26 0
318B classroom 0 720 16 0
319A classroom 392 26 1056 24 24
319B classroom 215 14 320 7 7
320A classroom 0 920 20 0
320B classroom 0 1056 24 0
321A classroom 0 1056 24 0
321B classroom 302 20 1056 24 20
- Cafeteria 153 10 3665 83 10
Main Office Office 0 1248 28 0
Assistant Principal Office 0 360 8 0
Burke Office 0 728 16 0
SSO Office 0 240 5 0
Nurse Suite 0 960 21 0
Sheet Last Modified: 04-23-2021    
School:  Girard Academic Music Program (GAMP) High School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- CAFE 9130 608 977 22 22
- GYM 0 6667 151 0
- GYM OFFICE 0 99 2 0
- LOWER HALF OF AUDITORIUM 13845 923 6498 147 147
- UPPER HALF OF AUDITORIUM 14721 981 3247 73 73
Principal Office 0 0 Yes 363 8 8
Assistant Principal Office 0 0 169 3 0
Main Office Office 0 0 Yes 266 6 6
Counselor 1 Office 0 0 Yes 134 3 3
Counselor 2 Office 0 0 Yes 246 5 5
Nurse Office 0 0 Yes 88 2 2
Lunch Room Lunch Room 0 0 2580 58 0
Orchestra Room Orchestra Room 0 0 Yes 1082 24 24
Orchestra Room Office 0 330 7
Band Room Band Room 0 0 Yes 1221 27 27
102 Classroom 0 0 Yes 685 15 15
103 Classroom 0 0 Yes 722 16 16
104/105 Classroom 0 0 Yes 1063 24 24
107 Classroom 0 0 Yes 735 16 16
108 Classroom 0 0 Yes 695 15 15
109 Classroom 0 0 Yes 685 15 15
201 Classroom 0 0 Yes 679 15 15
202 Classroom 0 0 Yes 679 15 15
203 Classroom 0 0 Yes 715 16 16
204 Classroom 0 0 Yes 683 15 15
205 Classroom 0 0 Yes 680 15 15
206 Classroom 0 0 Yes 711 16 16
207 Classroom 0 0 Yes 734 16 16
208 Classroom 0 0 Yes 634 14 14
209 Classroom 0 0 Yes 686 15 15
211 Classroom 0 0 394 8 0
301 Classroom 0 0 Yes 689 15 15
302 Classroom 0 0 Yes 645 14 14
303 Classroom 0 0 Yes 669 15 15
304 Classroom 0 0 Yes 725 16 16
305 Classroom 0 0 Yes 729 16 16
306 Classroom 0 0 Yes 950 21 21
307A Classroom 0 0 Yes 292 6 6
308 Classroom 0 0 Yes 900 20 20
309 Classroom 0 0 Yes 687 15 15
311 Classroom 0 0 Yes 348 7 7
Sheet Last Modified: 03-12-2021    
School:  Edward Gideon Elementary School
Vendor: Emcor Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 309 20 815 18 18 Unit Ventilator
102 Classroom 380 25 745 16 16 Unit Ventilator
Hallway @ 102 Hallway 0 0 0 0 Unit Ventilator
- Girls Bathroom next to Room 102 0 262 5 0 N/A
- Boys Bathroom next to Room 102 0 294 6 0 N/A
103 Classroom 247 16 0 0 Unit Ventilator
103 A - 0 207 4 0 Unit Ventilator
103 B - 0 175 3 0 Unit Ventilator
104 Classroom 226 15 450 10 10 Unit Ventilator
104 A - 0 97 2 0 Unit Ventilator
104 B - 0 151 3 0 Unit Ventilator
104 C - 0 134 3 0 Unit Ventilator
104 Counselor  0 451 10 0 Unit Ventilator
105 Classroom 323 21 872 19 19 Unit Ventilator
Hallway @ 105 Hallway 325 21 0 0 Unit Ventilator
106A Main Office 0 Yes 394 8 8 Unit Ventilator
106E Principal Office 0 Yes 166 3 3 Unit Ventilator
109 Classroom 351 23 858 19 19 Unit Ventilator
110 Classroom 374 24 811 18 18 Unit Ventilator
111 Classroom 253 16 866 19 16 Unit Ventilator
113 A School police 0 317 7 0 Unit Ventilator
113 b  inner office 0 153 3 0 Unit Ventilator
113 c inner office 0 Yes 164 3 3 Unit Ventilator
201 Classroom 154 10 1019 23 10 Unit Ventilator
Hallway @ 201 Hallway 225 15 0 0 Unit Ventilator
202 Classroom 537 35 924 21 21 Unit Ventilator
203 Classroom 0 0 Yes 938 21 21 Unit Ventilator
204 Classroom 319 21 788 17 17 Unit Ventilator
205 Classroom 296 19 822 18 18 Unit Ventilator
206 Classroom 310 20 822 18 18 Unit Ventilator
Hallway @ 206 Hallway 0 0 0 0 Unit Ventilator
207 Classroom 350 23 822 18 18 Unit Ventilator
- Boys Bathroom outside Room 207  0 164 3 0 N/A
208 Classroom 328 21 825 18 18 Unit Ventilator
- Female Staff Bathroom outside Room 208 0 61 1 0 N/A
- Girls Bathroom outside Room 208 0 127 2 0 N/A
209 Classroom  310 20 822 18 18 Unit Ventilator
210 Classroom  253 16 811 18 16 Unit Ventilator
211 Classroom  262 17 829 18 17 Unit Ventilator
212 Classroom 365 24 825 18 18 Unit Ventilator
Hallway @ 212 Hallway 215 14 0 0 Unit Ventilator
213 Classroom 357 23 426 9 9 Unit Ventilator
301 Classroom 189 12 Yes 829 18 18 Unit Ventilator
302 Classroom 298 19 822 18 18 Unit Ventilator
302 A Bathroom 0 232 5 0 N/A
302 B  Bathroom 0 147 3 0 N/A
303 Classroom 0 0 Yes 894 20 20 Unit Ventilator
304 Classroom 316 21 788 17 17 Unit Ventilator
305 Classroom 422 28 820 18 18 Unit Ventilator
306 Classroom 288 19 822 18 18 Unit Ventilator
Hallway @ 306 Hallway 0 0 0 0 Unit Ventilator
307 Classroom 351 23 822 18 18 Unit Ventilator
308 Classroom 476 31 826 18 18 Unit Ventilator
Hallway @ 308 Hallway 250 16 0 0 Unit Ventilator
309 Classroom 349 23 826 18 18 Unit Ventilator
310 Classroom 321 21 811 18 18 Unit Ventilator
311 Classroom 331 22 829 18 18 Unit Ventilator
312 Classroom 367 24 822 18 18 Unit Ventilator
Hallway @ 312 Hallway 215 14 0 0 Unit Ventilator
- Auditorium 630 42 0 0 AHU
GYM GYM 572 38 0 0 Unit Ventilator
Hallway @ Elevator Hallway 0 0 0 0 Unit Ventilator
Hallway @ Stair D Hallway 231 15 0 0 Unit Ventilator
- Nurse 0 0 0 0 Unit Ventilator
- Teachers Lounge 0 0 0 0 Unit Ventilator
- Auditorium 0 2,998 68 0 AHU
- Auditorium Rear classroom  0 251 5 0 AHU
- Boys bathroom outside main offce 0 303 6 0 N/A
- 3rd floor Boys bathroom 0 220 4 0 N/A
- Building Engineer Office 0 99 2 0 N/A
- 3rd floor Girls bathroom 0 192 4 0 N/A
- Girls bathroom  outside main offce 0 300 6 0 N/A
- 3rd floor Gym Teacher office 0 284 6 0 N/A
- 3rd floor Gym/Lunchroom 0 3,603 81 0 Unit Ventilator
- Kitchen 0 509 11 0 N/A
- Parent & teacher conf rm  0 123 2 0 Unit Ventilator
- Principal Conf rm 0 159 3 0 Unit Ventilator
- Teacher Lounge 0 436 9 0 Unit Ventilator
Sheet Last Modified: 04-29-2021    
School:  Stephen Girard Elementary School
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 100 51 3 Yes 672 15 15 Unit Ventilator
101 101 114 7 Yes 1200 27 27 Unit Ventilator
103 103 27 1 Yes 840 19 19 Unit Ventilator
105 105 62 4 840 19 4 Unit Ventilator
118 Speech Classroom 0 Yes 275 6 6 N/A
200 Classroom 0 Yes 840 19 19 Unit Ventilator
201 Classroom 0 Yes 840 19 19 Unit Ventilator
202 Classroom 0 Yes 840 19 19 Unit Ventilator
203 Classroom 0 Yes 840 19 19 Unit Ventilator
204 Classroom 0 Yes 840 19 19 Unit Ventilator
205 Classroom 0 Yes 840 19 19 Unit Ventilator
206 Classroom 0 Yes 840 19 19 Unit Ventilator
207 Classroom 0 Yes 375 8 8 Unit Ventilator
208 Classroom 0 Yes 840 19 19 Unit Ventilator
209 Classroom 0 Yes 840 19 19 Unit Ventilator
210 Classroom 0 Yes 840 19 19 Unit Ventilator
216 Classroom 0 200 4 0
300 Classroom 0 Yes 840 19 19 Unit Ventilator
301 Classroom 0 840 19 0 Unit Ventilator
302 Classroom 0 Yes 840 19 19 Unit Ventilator
303 Classroom 0 Yes 840 19 19 Unit Ventilator
304 Classroom 0 Yes 840 19 19 Unit Ventilator
305 Classroom 0 Yes 840 19 19 Unit Ventilator
306 Classroom 0 Yes 840 19 19 Unit Ventilator
307 / 309 Classroom 0 Yes 1375 31 31 Unit Ventilator
308 Classroom 0 Yes 840 19 19 Unit Ventilator
308A Classroom 0 364 8 0
310 Classroom 0 Yes 840 19 19 Unit Ventilator
- Auditorium 11,536 769 2600 59 59 AHU
- Gymnasium 1,656 110 3550 80 80 AHU
- IMC 227 15 1846 41 15 Unit Ventilator
- Nurse 0 Yes 170 3 3 N/A
- Principal Office 0 Yes 294 6 6
- Main Office 0 Yes 396 9 9 Unit Ventilator
Sheet Last Modified: 4-27-21    
School:  Philadelphia High School for Girls
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B-12 Showers 2144 142 2,163 49 49 AHU
B-13 Visitors' Lockers 0 0 256 5 0 Unit Ventilator
B-14 Home Lockers 0 0 316 7 0 Unit Ventilator
B-16 Girls' Locker Room 1254 83 4,702 106 83 Unit Ventilator
G-1 Classroom 292 19 1,032 23 19 Unit Ventilator
G-3 Classroom 459 30 1,216 27 27 Unit Ventilator
G-6 - 0 0 734 16 0 Unit Ventilator
G-8 Dance 277 18 1,275 28 18 Unit Ventilator
G-10 Classroom 281 18 741 16 16 Unit Ventilator
G-11 Classroom 274 18 745 16 16 Unit Ventilator
G-12 Classroom 222 14 714 16 14 Unit Ventilator
G-17 Classroom 93 6 748 17 6 Unit Ventilator
G-19 Classroom 277 18 718 16 16 Unit Ventilator
1 Fitness Room 227 15 1,169 26 15 Unit Ventilator
2 Fitness Room 506 33 2,048 46 33 Unit Ventilator
100 Classroom 306 20 756 17 17 Unit Ventilator
101 Classroom 275 18 756 17 17 Unit Ventilator
102 Archives 145 9 689 15 9 Unit Ventilator
104 Classroom 221 14 756 17 14 Unit Ventilator
105 Instruments 612 40 2,376 54 40 Unit Ventilator
106 Roster Office 208 13 778 17 13 Unit Ventilator
107 Office 290 19 799 18 18 Unit Ventilator
108 Office 0 0 769 17 0 Unit Ventilator
109 Office 291 19 790 17 17 Unit Ventilator
110 Office 203 13 768 17 13 Unit Ventilator
111 Poetry 188 12 1,182 26 12 Unit Ventilator
111-A Health Office 0 0 462 10 0 Unit Ventilator
112 Classroom 0 0 767 17 0 Unit Ventilator
113 Classroom 0 0 1,655 37 0 Unit Ventilator
114 Classroom 0 0 769 17 0 Unit Ventilator
115 Classroom 0 0 1,749 39 0 Unit Ventilator
116 Classroom 0 0 749 17 0 Unit Ventilator
118 Classroom 0 0 752 17 0 Unit Ventilator
200 Classroom 0 0 775 17 0 Unit Ventilator
201 Classroom 221 14 763 17 14 Unit Ventilator
202 Classroom 213 14 771 17 14 Unit Ventilator
204 Classroom 0 0 771 17 0 Unit Ventilator
205 Music Office 472 31 2,334 53 31 Unit Ventilator
206 Classroom 0 0 780 17 0 Unit Ventilator
207 Classroom 289 19 768 17 17 Unit Ventilator
208 Classroom 213 14 776 17 14 Unit Ventilator
209 Classroom 251 16 786 17 16 Unit Ventilator
210 Classroom 255 17 781 17 17 Unit Ventilator
211 Classroom 268 17 744 16 16 Unit Ventilator
212 Classroom 388 25 780 17 17 Unit Ventilator
214 Classroom 251 16 776 17 16 Unit Ventilator
215 Classroom 402 26 781 17 17 Unit Ventilator
216 Classroom 244 16 772 17 16 Unit Ventilator
217 Classroom 178 11 787 17 11 Unit Ventilator
218 Classroom 0 0 789 17 0 Unit Ventilator
219 Classroom 54 3 783 17 3 Unit Ventilator
221 Classroom 290 19 841 19 19 Unit Ventilator
223 Classroom 0 0 891 20 0 Unit Ventilator
300 Classroom 270 18 786 17 17 Unit Ventilator
302 Classroom  416 27 996 22 22 Unit Ventilator
303 Classroom  555 37 1,052 23 23 Unit Ventilator
304 Classroom  525 35 1,007 22 22 Unit Ventilator
305 Classroom  279 18 791 17 17 Unit Ventilator
306 Classroom  378 25 1,034 23 23 Unit Ventilator
307 Classroom  0 0 781 17 0 Unit Ventilator
308 Classroom  158 10 1,048 23 10 Unit Ventilator
309 Classroom  188 12 787 17 12 Unit Ventilator
310 Classroom  403 26 1,115 25 25 Unit Ventilator
311 Classroom  186 12 792 18 12 Unit Ventilator
312 Classroom  240 16 1,015 23 16 Unit Ventilator
313 Classroom  202 13 779 17 13 Unit Ventilator
314 Classroom  329 21 1,008 22 21 Unit Ventilator
315 Classroom  289 19 790 17 17 Unit Ventilator
316 Classroom  326 21 788 17 17 Unit Ventilator
317 Classroom  169 11 780 17 11 Unit Ventilator
319 Classroom  351 23 706 16 16 Unit Ventilator
321 Classroom  293 19 716 16 16 Unit Ventilator
- Auditorium 946 63 10,546 239 63 AHU
- Gymnasium 287 19 10,449 237 19 AHU
- Main Cafeteria  2523 168 12,220 277 168 Unit Ventilator
- Faculty Cafeteria 549 36 1,172 26 26 Unit Ventilator
- Main Office 192 12 1,054 23 12 Unit Ventilator
- Library 538 35 5,853 133 35 Unit Ventilator
Sheet Last Modified: 04-23-2021    
School:  Samuel Gompers Elementary-Middle School
Vendor: Capital
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Kindergarten 334 22 2002 45 22 Unit Ventilator
102 Classroom 429 28 1106 25 25 Unit Ventilator
104 Classroom 450 30 1099 24 24 Unit Ventilator
105 Classroom 444 29 1094 24 24 Unit Ventilator
106 Classroom 436 29 1095 24 24 Unit Ventilator
107 Classroom 432 28 1102 25 25 Unit Ventilator
B-107 Library 492 32 1241 28 28 Unit Ventilator
B-107A Workroom 28 1 204 4 1 Unit Ventilator
A-108 Teacher Room 138 9 387 8 8 Unit Ventilator
A-112 Infirmary 21 1 198 4 1 Unit Ventilator
A-113 Waiting 80 5 155 3 3 FCU
A-114 Nurse’s Office 339 22 186 4 4 FCU
A-121 Examination 226 15 310 7 7 FCU
A-122 Office 22 1 133 3 1 Unit Ventilator
A-124 Counselor Office 34 2 178 4 2 Unit Ventilator
A-131 General Office 51 3 488 11 3 Unit Ventilator
A-133 Principal Office 32 2 232 5 2 Unit Ventilator
A-137 Conference 96 6 333 7 6 Unit Ventilator
A-150 Office 117 7 324 7 7 FCU
A-153 Office 122 8 322 7 7 FCU
201 Classroom 429 28 1083 24 24 Unit Ventilator
202 Classroom 431 28 1074 24 24 Unit Ventilator
203 Classroom 432 28 1075 24 24 Unit Ventilator
204 Classroom 265 17 544 12 12 Unit Ventilator
205 Classroom 418 27 1109 25 25 Unit Ventilator
A-205 Teachers Room 156 10 353 8 8 Unit Ventilator
206 Classroom 433 28 1110 25 25 Unit Ventilator
207 Classroom 435 29 1112 25 25 Unit Ventilator
208 Classroom 438 29 1095 24 24 Unit Ventilator
A-208 After School Programs 65 4 441 10 4 Unit Ventilator
B-209 Classroom 262 17 537 12 12 Unit Ventilator
B-210 Classroom 437 29 1093 24 24 Unit Ventilator
B-211 Classroom 435 29 1095 24 24 Unit Ventilator
212 Classroom 419 27 1084 24 24 Unit Ventilator
213 Classroom 454 30 1087 24 24 Unit Ventilator
A-217 Cafeteria 466 31 1943 44 31 AHU
A-218 Gymnasium 1290 86 3950 89 86 AHU
Portable R1 0 Yes 843 19 19
Portable R2 0 Yes 842 19 19
Portable R3 0 Yes 852 19 19
Portable R4 0 Yes 1033 23 23
Portable R5 0 Yes 1022 23 23
Sheet Last Modified: 04-22-2021    
School:  Joseph Greenberg Elementary-Middle School
Vendor: Devine Borthers Devine Brothers Retest
    Devine Brothers 2nd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 325.0 21 828 18 18 Unit Ventilator
101 Classroom 335.0 22 828 18 18 Unit Ventilator
102 Classroom 380.0 25 828 18 18 Unit Ventilator
103 Classroom 288.0 19 828 18 18 Unit Ventilator
104 Classroom 284.0 18 384 8 8 Unit Ventilator
105 Nurse 300.0 20 432 9 9 Unit Ventilator
106 Classroom 530.0 35 1012 23 23 Unit Ventilator
107 Classroom 671.0 44 864 19 19 Unit Ventilator
107A Meeting room 0 Yes 432 9 9 Unit Ventilator
108 Classroom 441.0 29 1012 23 23 Unit Ventilator
109 Classroom 298.0 19 828 18 18 Unit Ventilator
111 Classroom 291.0 19 828 18 18 Unit Ventilator
200 Classroom 308.0 20 828 18 18 Unit Ventilator
201 Classroom 281.0 18 828 18 18 Unit Ventilator
202 Classroom 295.0 19 828 18 18 Unit Ventilator
203 Classroom 351.0 23 828 18 18 Unit Ventilator
204 Classroom 317.0 21 828 18 18 Unit Ventilator
205 Classroom 326.0 21 828 18 18 Unit Ventilator
207 Classroom 320.0 21 828 18 18 Unit Ventilator
209 Classroom 345.0 23 828 18 18 Unit Ventilator
210 Classroom 316.0 21 384 8 8 Unit Ventilator
211 Classroom 281.0 18 368 8 8 Unit Ventilator
211a Classroom 375.0 25 621 14 14 Unit Ventilator
211b Classroom 307.0 20 828 18 18 Unit Ventilator
212 Classroom 351.0 23 828 18 18 Unit Ventilator
213 Classroom 344.0 22 828 18 18 Unit Ventilator
214 Classroom 345.0 23 828 18 18 Unit Ventilator
215 Classroom 375.0 25 828 18 18 Unit Ventilator
216 Classroom 312.0 20 828 18 18 Unit Ventilator
217 Classroom 326.0 21 828 18 18 Unit Ventilator
300 Classroom 325.0 21 828 18 18 Unit Ventilator
301 Classroom 291.0 19 828 18 18 Unit Ventilator
302 Classroom 285.0 19 552 12 12 Unit Ventilator
303 Classroom 330.0 22 828 18 18 Unit Ventilator
304 Classroom 325.0 21 828 18 18 Unit Ventilator
305 Classroom 321.0 21 828 18 18 Unit Ventilator
306 Classroom 289.0 19 384 8 8 Unit Ventilator
307 Classroom 345.0 23 828 18 18 Unit Ventilator
309 Classroom 350.0 23 1242 28 23 Unit Ventilator
313 Classroom 302.0 20 828 18 18 Unit Ventilator
314 Classroom 289.0 19 828 18 18 Unit Ventilator
315 Classroom 321.0 21 828 18 18 Unit Ventilator
316 Classroom 311.0 20 828 18 18 Unit Ventilator
317 Classroom 331.0 22 828 18 18 Unit Ventilator
318 Classroom 314.0 20 828 18 18 Unit Ventilator
319 Classroom 311.0 20 828 18 18 Unit Ventilator
321 Classroom 288.0 19 828 18 18 Unit Ventilator
400 Classroom 375.0 25 864 19 19 Unit Ventilator
401 IMC Classroom 310.0 20 828 18 18 Unit Ventilator
- Auditorium 12,200.0 813 3213 73 73 AHU
- Cafeteria 7,911.0 527 5250 119 119 AHU
- Gym 8,800.0 586 3978 90 90 AHU
- IMC Classroom 220.0 14 828 18 14 Unit Ventilator
- Teacher Lounge 448.0 29 168 3 3 Unit Ventilator
- Main Office 280.0 18 1134 25 18 Unit Ventilator
- Dean's office 0 Yes 135 3 3 Unit Ventilator
- Assistant principal office 0 Yes 135 3 3 Unit Ventilator
- Principal's Office 0 Yes 432 9 9 Unit Ventilator
- Kitchen 0 Yes 864 19 19 N/A
- BE office  275 18 441 10 10 N/A
- Custodial office 95 6 195 4 4 N/A
Sheet Last Modified: 04-26-2021    
School:  Albert M. Greenfield Elementary School
Vendor: Meehan Devine Capital Part I
Vendor: Capital Part II Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B06 Music rm. 329 21 416 9 9 AHU
B17 Storage 229 15 320 7 7 N/A
B36 Music main 452 30 962 21 21 AHU
B37 Music Office 151 10 168 3 3 AHU
B38 Practice rm 44 2 64 1 1 AHU
B40 Music Ensamble 163 10 312 7 7 AHU
101 Reception 121 8 360 8 8 AHU
102 0 Yes 120 N/A
103 Offices 0 0 Yes 120 2 2 AHU
104 Offices 0 0 Yes 120 2 2 AHU
105 Sensory Room 46 3 120 2 2 AHU
106 Office 76 5 231 5 5 AHU
107 Nurse Reception 0 0 Yes 81 1 1 AHU
107A Nurse Office 48 3 Yes 189 4 4 AHU
107B Offices 0 0 Yes 99 2 2 AHU
107C Storage 0 0 110 2 0 N/A
108 Conference 65 4 238 5 4 AHU
109 Admin 0 0 Yes 130 2 2 AHU
110 Classroom 340 22 936 21 21 Unit Ventilator
111 Classroom 491 32 936 21 21 Unit Ventilator
112 Classroom 366 24 936 21 21 Unit Ventilator
113A Classroom 1038 69 676 15 15 Unit Ventilator
126 Lobby 55 3 676 15 3 Unit Ventilator
128 Corridor 60 4 456 10 4 Unit Ventilator
129 Principal Office 94 6 220 5 5 Unit Ventilator
201 Classroom 150 10 260 5 5 Unit Ventilator
202 Classroom 390 26 884 20 20 Unit Ventilator
203 Classroom 302 20 884 20 20 Unit Ventilator
204 Classroom 493 32 725 16 16 Unit Ventilator
205 Classroom 475 31 850 19 19 Unit Ventilator
206 Classroom 488 32 918 20 20 Unit Ventilator
207 Classroom 570 38 990 22 22 Unit Ventilator
208 Classroom 407 27 362 8 8 Unit Ventilator
208A Classroom 74 4 195 4 4 Unit Ventilator
209 Classroom 461 30 672 15 15 Unit Ventilator
210 Classroom 357 23 957 21 21 Unit Ventilator
211 Classroom 545 36 990 22 22 Unit Ventilator
212 Classroom 416 27 812 18 18 Unit Ventilator
213 Classroom 444 29 924 21 21 Unit Ventilator
214 Classroom 430 28 864 19 19 Unit Ventilator
215 Classroom 429 28 952 21 21 Unit Ventilator
216 Classroom 180 12 325 7 7 Unit Ventilator
217 Classroom 206 13 420 9 9 Unit Ventilator
218 Classroom 0 0 0 0 Unit Ventilator
225 Library 1255 83 3628 82 82 Unit Ventilator
301 Classroom 570 38 957 21 21 Unit Ventilator
302 Classroom 289 19 864 19 19 Unit Ventilator
303 Classroom 328 21 957 21 21 Unit Ventilator
304 Classroom 501 33 754 17 17 Unit Ventilator
305 Classroom 336 22 1020 23 22 Unit Ventilator
306 Classroom 545 36 1020 23 23 Unit Ventilator
307 Classroom 374 24 506 11 11 Unit Ventilator
308 Classroom 418 27 460 10 10 Unit Ventilator
309 Classroom 550 36 924 21 21 Unit Ventilator
310 Classroom 441 29 1020 23 23 Unit Ventilator
311 Classroom 439 29 924 21 21 Unit Ventilator
312 Classroom 401 26 696 15 15 Unit Ventilator
313 Classroom 530 35 957 21 21 Unit Ventilator
314 Classroom 325 21 858 19 19 Unit Ventilator
315 Classroom 568 37 1650 37 37 Unit Ventilator
316 Classroom 318 21 1650 37 21 Unit Ventilator
317 Classroom 300 20 1664 37 20 Unit Ventilator
318 Classroom 62 4 0 0 Unit Ventilator
- B.E. Office 139 9 88 2 2 AHU
- GYM 1357 90 6110 138 90 AHU
- Stage/Auditorium/Cafeteria 0 0 4588 104 0 AHU
- Kitchen 47 3 403 9 3 AHU
Sheet Last Modified: 04-07-2021    
School:  Horatio Hackett Elementary School
Vendor: Devine Brothers Part 2 Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
104 Library 501 33 Yes 1920 43 43 Unit Ventilator
106 Gym Mechanical 497 33 624 14 14 AHU
107 Gym Mechanical 959 63 1400 31 31 AHU
108 Lounge 299 19 560 12 12 Unit Ventilator
109 Classroom 394 26 1136 25 25 Unit Ventilator
110 Classroom 323 21 1024 23 21 Unit Ventilator
111 Classroom 284 18 776 17 17 Unit Ventilator
112 Classroom 280 18 720 16 16 Unit Ventilator
201 Classroom 279 18 840 19 18 Unit Ventilator
202 Classroom 658 43 784 17 17 Unit Ventilator
203 Classroom 335 22 784 17 17 Unit Ventilator
204 Classroom 0 0 Yes 840 19 19 Unit Ventilator
205 Classroom 475 31 840 19 19 Unit Ventilator
205A Sm office / Speech Room 223 14 304 6 6 Unit Ventilator
206 Classroom 0 0 Yes 696 15 15 Unit Ventilator
207 Classroom 0 0 Yes 488 11 11 Unit Ventilator
207A Small Office 120 8 248 5 5 Unit Ventilator
208 Classroom 278 18 784 17 17 Unit Ventilator
209 Classroom 362 24 672 15 15 Unit Ventilator
210 Classroom 0 0 Yes 784 17 17 Unit Ventilator
211 Classroom 334 22 784 17 17 Unit Ventilator
212 Classroom 355 23 840 19 19 Unit Ventilator
212A Office/Councelors 0 336 7 0 N/A
214 Classroom 455 30 864 19 19 AHU
215 Classroom 405 27 920 20 20 AHU
216 Classroom 505 33 832 18 18 AHU
217 Classroom 390 26 768 17 17 Unit Ventilator
218 Classroom 311 20 Yes 976 22 22 AHU
219 Classroom 405 27 880 20 20 AHU
219c Classroom 123 8 288 6 6 Unit Ventilator
305 Classroom 400 26 1000 22 22 Unit Ventilator
306 Classroom 0 0 Yes 936 21 21 Unit Ventilator
307 Classroom 315 21 824 18 18 Unit Ventilator
308 Classroom 329 21 824 18 18 Unit Ventilator
308D Councelors 38 2 Yes 384 8 8 Unit Ventilator
309 Classroom 395 26 944 21 21 Unit Ventilator
- Caf/Auditorium 1,435 95 6914 157 95 AHU
- GYM 964 64 4770 108 64 AHU
- Kitchen 413 27 954 21 21 AHU
- Main Office 304 20 832 18 18 Unit Ventilator
- Nurses Office 50 3 Yes 564 12 12 Unit Ventilator
Sheet Last Modified: 04-08-2021    
School:  Andrew Hamilton Elementary School
Vendor: Capital Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
104 Classroom 398 26 598 13 13 Unit Ventilator
106 Classroom 407 27 755 17 17 Unit Ventilator
107 Classroom 376 25 599 13 13 Unit Ventilator
111 Cafeteria 1,724 114 2444 55 55 AHU
112 Auditorium 813 54 3875 88 54 AHU
119 Music 391 26 827 18 18 AHU
121 Gym 1,663 110 4628 105 105 AHU
127 Classroom 595 39 1186 26 26 Unit Ventilator
128 Classroom 628 41 1370 31 31 Unit Ventilator
129 Classroom 565 37 1112 25 25 Unit Ventilator
130 Classroom 608 40 1378 31 31 Unit Ventilator
131 Classroom 575 38 1169 26 26 Unit Ventilator
200 Classroom 415 27 763 17 17 Unit Ventilator
201 Classroom 527 35 776 17 17 Unit Ventilator
202 Teachers Lounge 300 20 469 10 10 Unit Ventilator
205 Team Planning 353 23 431 9 9 Unit Ventilator
206 Classroom 454 30 595 13 13 Unit Ventilator
207 Classroom 454 30 847 19 19 Unit Ventilator
209 General Office 750 50 866 19 19 Unit Ventilator
223 Classroom 432 28 847 19 19 Unit Ventilator
224 Classroom 426 28 837 19 19 Unit Ventilator
225 Classroom 394 26 837 19 19 Unit Ventilator
226 Classroom 393 26 840 19 19 Unit Ventilator
227 Classroom 395 26 832 18 18 Unit Ventilator
228 Classroom 477 31 847 19 19 Unit Ventilator
300 Classroom 400 26 793 18 18 Unit Ventilator
301 Classroom 421 28 791 17 17 Unit Ventilator
302 Classroom 393 26 786 17 17 Unit Ventilator
303 Classroom 365 24 640 14 14 Unit Ventilator
306 Classroom 413 27 793 18 18 Unit Ventilator
307 Classroom 464 30 793 18 18 Unit Ventilator
309 Classroom 306 20 597 13 13 Unit Ventilator
310 Classroom 0 0 Yes 708 16 16
311J Janitors 173 11 59 1 1 Unit Ventilator
314 Office 551 36 214 4 4 Unit Ventilator
315 Office 724 48 214 4 4 Unit Ventilator
318 Classroom 382 25 911 20 20 Unit Ventilator
319 Classroom 0 0 Yes 616 14 14 Unit Ventilator
320 Team Planning 0 0 Yes 235 5 5 Unit Ventilator
321 Team Planning 300 20 243 5 5 Unit Ventilator
322 Classroom 450 30 820 18 18 Unit Ventilator
323 Classroom 0 0 Yes 620 14 14 Unit Ventilator
327 Office 432 28 201 4 4 Unit Ventilator
328 Office 735 49 233 5 5 Unit Ventilator
331 Classroom 0 0 Yes 667 15 15 Unit Ventilator
332 Classroom 339 22 625 14 14 Unit Ventilator
333 Classroom 423 28 894 20 20 Unit Ventilator
334 Classroom 393 26 800 18 18 Unit Ventilator
335 Classroom 838 55 1684 38 38 Unit Ventilator
336 Classroom 375 25 908 20 20 Unit Ventilator
337 Classroom 0 0 Yes 932 21 21 Unit Ventilator
- Library 2,442 162 3672 83 83 Unit Ventilator
Sheet Last Modified: 04-21-2021    
School:  John Hancock Demonstrative Elementary School
Vendor: Devine Brothers Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 127 8 528 12 8 Unit Ventilator
102 Classroom 416 27 750 17 17 Unit Ventilator
103 Classroom 123 8 567 12 8 Unit Ventilator
104 Classroom 283 18 483 10 10 Unit Ventilator
105 Classroom 0 0 Yes 567 12 12 Unit Ventilator
106 Classroom 171 11 756 17 11 Unit Ventilator
107 Classroom 237 15 806 18 15 Unit Ventilator
108 Classroom 0 0 Yes 648 14 14 Unit Ventilator
109 Classroom 173 11 638 14 11 Unit Ventilator
110 Classroom 233 15 812 18 15 Unit Ventilator
111 Classroom 168 11 588 13 11 Unit Ventilator
200 Classroom 323 21 Yes 510 11 11 Unit Ventilator
200A Office 0 Yes 0 0
202 Classroom 432 28 1271 28 28 Unit Ventilator
203 Classroom 299 19 588 13 13 Unit Ventilator
204 Classroom 324 21 575 13 13 Unit Ventilator
205 Classroom 255 17 616 14 14 Unit Ventilator
206 Classroom 324 21 1116 25 21 Unit Ventilator
207 Classroom 310 20 864 19 19 Unit Ventilator
208 Classroom 308 20 837 19 19 Unit Ventilator
209 Classroom 312 20 868 19 19 Unit Ventilator
210 Classroom 303 20 728 16 16 Unit Ventilator
211 Classroom 298 19 754 17 17 Unit Ventilator
212 Classroom 0 Yes 744 16 16 Unit Ventilator
213 Classroom 174 11 Yes 806 18 18 Unit Ventilator
214 Computer Lab 312 20 462 10 10 Unit Ventilator
215 Classroom 0 0 Yes 364 8 8 Unit Ventilator
216 Classroom 0 0 364 8 0 Unit Ventilator
217 Classroom 334 22 875 19 19 Unit Ventilator
219 Classroom 294 19 792 18 18 Unit Ventilator
218 Nurse Office 0 Yes 252 5 5
220 Office 0 0 Yes 126 2 2 Unit Ventilator
B213 Classroom 0 Yes 363 8 8
B3 Faculty Lounge 184 12 Yes 540 12 12 Unit Ventilator
B13 Classroom 0 Yes 0 0
HS215 Classroom 0 Yes 608 13 13
HS216 Classroom 0 Yes 608 13 13
- Classroom Behind kitchen 37 2 224 5 2 Unit Ventilator
- Gym Office 0 0 Yes 100 2 2 Unit Ventilator
- Gym 0 288 6 0 AHU
- Cafeteria 0.0 0 4600 104 0 AHU
- Kitchen 0 0 Yes 448 10 10 Unit Ventilator
- Main Lobby 0 0 720 16 0 Unit Ventilator
- Main Office 201 13 340 7 7 Unit Ventilator
- Main Office Side Office 0 0 104 2 0 Unit Ventilator
- Principals Office 196 13 238 5 5 Unit Ventilator
Assistant Principal Office 0 Yes 0 0
Dean Office 0 Yes 0 0
- Library 692 46 1520 34 34 Unit Ventilator
- Office Across from 210 0.0 0 120 2 0 N/A
- Office across from gym 0.0 0 204 4 0 Unit Ventilator
- Office across from Room 107 76.0 5 140 3 3 Unit Ventilator
- Office across from room 110 115.0 7 140 3 3 Unit Ventilator
- Office Next to gym 0.0 0 80 1 0 Unit Ventilator
Sheet Last Modified: 5-3-21    
School:  Warren G. Harding Middle School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 - 0 288 6 0
101a - 0 288 6 0
102 - 0 Yes 1,128 25 25
102a - 0 100 2 0
103 - 0 720 16 0
104 - 0 Yes 888 20 20
104a - 0 110 2 0
105 - 0 648 14 0
105b - 0 770 17 0
106c - 0 248 5 0
107 - 0 936 21 0
107a - 0 248 5 0
107b - 0 50 1 0
107c - 0 25 0 0
108 - 0 Yes 886 20 20
108a - 0 130 2 0
108b - 0 25 0 0
108c - 0 50 1 0
109 - 0 576 13 0
109a - 0 135 3 0
110 - 0 912 20 0
110a - 0 40 0 0
111 - 0 624 14 0
112 - 0 576 13 0
112a - 0 308 7 0
113 - 0 360 8 0
113a - 0 242 5 0
113b - 0 352 8 0
114 - 0 Yes 204 4 4
116 - 0 2,120 48 0
116a - 0 416 9 0
117 - 0 2,700 61 0
201 - 0 Yes 360 8 8
201a - 0 432 9 0
202 - 0 Yes 768 17 17
203 - 0 288 6 0
203B - 0 Yes 200 4 4
204 - 0 Yes 720 16 16
205 - 0 Yes 768 17 17
206 - 0 319 7 0
206a - 0 224 5 0
206b - 0 112 2 0
208 - 0 Yes 792 18 18
209 IMC 0 Yes 2,160 49 49
211 - 0 936 21 0
212 - 0 888 20 0
213 - 0 336 7 0
214 - 0 696 15 0
215 - 0 Yes 648 14 14
216 - 0 744 16 0
217 - 0 638 14 0
218 - 0 792 18 0
219 - 0 768 17 0
220 - 0 744 16 0
221 - 0 744 16 0
222 - 0 Yes 768 17 17
223 - 0 Yes 816 18 18
224 - 0 Yes 638 14 14
225 - 0 144 3 0
301 - 0 648 14 0
302 - 0 768 17 0
303 - 0 Yes 390 8 8
304 - 0 720 16 0
305 - 0 768 17 0
306 - 0 966 21 0
307a - 0 360 8 0
307b - 0 600 13 0
308a - 0 480 10 0
308b - 0 336 7 0
309 - 0 816 18 0
310 - 0 1,056 24 0
311 - 0 960 21 0
311a - 0 143 3 0
312 - 0 Yes 936 21 21
313 - 0 984 22 0
314 - 0 768 17 0
315 - 0 360 8 0
316 - 0 720 16 0
317 - 0 Yes 720 16 16
318 - 0 744 16 0
320 - 0 816 18 0
321 - 0 768 17 0
322 - 0 768 17 0
323 - 0 768 17 0
324 - 0 Yes 768 17 17
325 - 0 816 18 0
326 - 0 638 14 0
- Main Office 0 Yes 468 10 10
- Nurse Office 0 Yes 144 3 3
- Auditorium 0 1944 44 0
- Girls Lunchroom 0 2173 49 0
- Girls Gym 0 1419 32 0
- Boy's Lunchroom 0 2173 49 0
- Boy's Gym 0 1419 32 0
Sheet Last Modified: 04-21-2021    
School:  Avery D. Harrington Elementary-Middle School
Vendor: EMCOR Fluidics Devine Retest
  EMCOR Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B1 Classroom 0 0 Yes 805 18 18 House Fan
B2 Classroom 0 0 Yes 594 13 13 House Fan
B3 Classroom 530 35 1122 25 25 Unit Ventilator
B4 B4 295 19 1064 24 19 Unit Ventilator
B5 Classroom 299 19 910 20 19 Unit Ventilator
B6 - 363 24 812 18 18 Unit Ventilator
B8 Classroom 0 0 Yes 651 14 0 House Fan
B9 - 0 Yes 600 13 13
10A Classroom 0 Yes 253 5
101 Classroom 0 0 Yes 968 22 22 House Fan
102 Teachers Lounge 0 216 4 0 House Fan
103 Classroom 0 Yes 667 15 15 House Fan
104 Classroom 0 Yes 840 19 19 House Fan
106 Classroom 0 720 16 0 House Fan
107 Classroom 0 0 Yes 725 16 16 House Fan
108 Classroom 0 0 Yes 750 17 17 House Fan
109 Classroom 651 43 1120 25 25 Unit Ventilator
109A Classroom 0 Yes 168 3
109B Classroom 0 Yes 170 3
201 Classroom 0 Yes 775 17 17 House Fan
202 Classroom 0 Yes 750 17 17 House Fan
203 Classroom 0 Yes 644 14 14 House Fan
203a Asst Princ Office 0 Yes 403 9 9 House Fan
204 Classroom 0 Yes 900 20 20 House Fan
205 Classroom 0 Yes 864 19 19 House Fan
206 Classroom 0 Yes 840 19 19 House Fan
207 Classroom 0 Yes 720 16 16 House Fan
208 Classroom 0 Yes 696 15 15 House Fan
301 Classroom 0 Yes 900 20 20 House Fan
302 Classroom 0 Yes 780 17 17 House Fan
303 Classroom 0 Yes 644 14 14 House Fan
303a Counselor Office 0 Yes 403 9 9 House Fan
304 Classroom 0 Yes 930 21 21 House Fan
305 Classroom 0 Yes 810 18 18 House Fan
306 Classroom 0 Yes 870 19 19 House Fan
307 Classroom 0 Yes 725 16 16 House Fan
308 Classroom 0 Yes 754 17 17 House Fan
- Library 1,190 79 3822 86 79 Unit Ventilator
- Auditorium 130.0 8 90 2 2 AHU
- Gym 0 2760 62 0
- Gym / Storeroom 0.0 0 513 11 0 AHU
Kitchen 0 Yes 120 2
- Nurse Office 0 Yes 190 4 4 House Fan
- Main Office 0 Yes 420 9 9 House Fan
- Principal Office 0 Yes 377 8 8 House Fan
Sheet Last Modified: 04-06-2021    
School:  John F. Hartranft Elementary-Middle School
Vendor: Devine Brothers Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 560 37 1519 34 34 Unit Ventilator
100A Office 0 0 108 2 0 AHU
100C Office 0 Yes 144 3 3
100E Office 0 0 304 6 0 AHU
100G Office 0 Yes 304 6 6 AHU
100J Office 0 0 Yes 77 1 1 AHU
101 Classroom 310 20 840 19 19 Unit Ventilator
102 Classroom 309 20 Yes 1302 29 29 Unit Ventilator
103 Classroom 344 22 Yes 1302 29 29 Unit Ventilator
104 Classroom 440 29 1178 26 26 Unit Ventilator
105 Classroom 348 23 1178 26 23 Unit Ventilator
106 Classroom 258 17 Yes 1302 29 29 Unit Ventilator
107 Classroom 488 32 1302 29 29 Unit Ventilator
108 Classroom 346 23 1178 26 23 Unit Ventilator
109 Classroom 226 15 Yes 1178 26 26 Unit Ventilator
110 Classroom 277 18 Yes 1302 29 29 Unit Ventilator
111 Classroom 519 34 966 21 21 Unit Ventilator
112 Classroom 500 33 1302 29 29 Unit Ventilator
113 Classroom 485 32 874 19 19 Unit Ventilator
114 Classroom 407 27 950 21 21 Unit Ventilator
115 Classroom 316 21 Yes 1305 29 29 Unit Ventilator
116 Classroom 261 17 Yes 1305 29 29 Unit Ventilator
117 Classroom 313 20 Yes 1305 29 29 Unit Ventilator
118 Classroom 473 31 1305 29 29 Unit Ventilator
118A Classroom 12 0 Yes 680 15 15 AHU
121 Classroom 55 3 Yes 792 18 18 AHU
121 Backroom 59 3 310 7 3 AHU
200 Classroom 368 24 Yes 1462 33 33 Unit Ventilator
201 Classroom 647 43 1178 26 26 Unit Ventilator
202 Classroom 454 30 1302 29 29 Unit Ventilator
203 Classroom 355 23 Yes 1302 29 29 Unit Ventilator
204 Classroom 258 17 Yes 1178 26 26 Unit Ventilator
205 Classroom 491 32 1178 26 26 Unit Ventilator
206 Classroom 282 18 Yes 1302 29 29 Unit Ventilator
207 Classroom 225 15 Yes 1302 29 29 Unit Ventilator
208 Classroom 247 16 Yes 1179 26 26 Unit Ventilator
209 Classroom 274 18 Yes 1179 26 26 Unit Ventilator
210 Classroom 485 32 1302 29 29 Unit Ventilator
211 Classroom 519 34 1302 29 29 Unit Ventilator
212 Classroom 309 20 Yes 1178 26 26 Unit Ventilator
214 Classroom 325 21 782 17 17 Unit Ventilator
- Cafeteria 2300 153 1593 36 36 AHU
- Cafeteria Entrance Hallway 0 0 730 16 0 AHU
- Conference/Office 0 0 304 6 0 AHU
- Engineer Office 0 0 112 2 0 AHU
- Engineer Breakroom 0 0 99 2 0 AHU
- Gym 3499 233 6160 140 140 AHU
- Kitchen 0 0 864 19 0 AHU
- Main Office 0 0 Yes 1056 24 24 AHU
- Nurse Office 0 0 Yes 425 9 9 AHU
- Principal Office 0 0 Yes 228 5 5 AHU
- Rear Entrance Hallway 0 0 736 16 0 AHU
- Teacher Office 0 0 77 1 0 AHU
Sheet Last Modified: 04-23-2021    
School:  Haverford Child Development Center
Vendor: Devine Brothers Devine Brothers Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
2 Classroom 291.0 19 Yes 1058 24 24 RTU
3 Classroom 323.0 21 Yes 1058 24 24 RTU
4 Classroom 277.0 18 Yes 1058 24 24 RTU
5 Classroom 374.0 24 1058 24 24 RTU
5A Office 15.0 1 170 3 1 RTU
6 Conference 418.0 27 621 14 14 RTU
7 Conference 415.0 27 621 14 14 RTU
8 Classroom 287.0 19 560 12 12 RTU
8A Office 336.0 22 210 4 4 RTU
9 Classroom 723.0 48 962 21 21 RTU
10A Lounge 34.0 2 216 4 2 RTU
10B Book Storage 11.0 0 288 6 0 RTU
- Gym 1,065.0 71 2204 50 50 RTU
- Lobby 18.0 1 608 13 1 RTU
- Storage 89.0 5 572 13 5 RTU
- BE Office 18.0 1 128 2 1 RTU
 
 
 
 
 
 
 
 
Sheet Last Modified: 04-05-2021      
School:  Charles W. Henry Elementary School
Vendor: Devine Devine Part 2 Devine Part 3 Devine Part 4
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 0 Yes 650 14 14 Unit Ventilator
102 Classroom 443 29 837 19 19 Unit Ventilator
103 Classroom 371 24 817 18 18 Unit Ventilator
104 Classroom 374 24 818 18 18 Unit Ventilator
104A Office 0 0 Yes 57 1 1
105 Classroom 397 26 951 21 21 Unit Ventilator
106 Classroom 308 20 815 18 18 Unit Ventilator
108 Classroom 481 32 650 14 14 Unit Ventilator
109 Classroom 763 50 712 16 16 Unit Ventilator
110 Classroom 756 50 650 14 14 Unit Ventilator
110A Office 0 0 Yes 98 2 2
114 Classroom 773 51 749 17 17
201 Classroom 289 19 775 17 17 Unit Ventilator
202 Classroom 314 20 765 17 17 Unit Ventilator
203 Classroom 282 18 781 17 17 Unit Ventilator
203A Office 0 0 Yes 115 2 2
204 Classroom 262 17 Yes 847 19 19 Unit Ventilator
206 Classroom 285 19 546 12 12 Unit Ventilator
207 Classroom 273 18 815 18 18 Unit Ventilator
208 Classroom 265 17 787 17 17 Unit Ventilator
208A Office 0 0 Yes 170 3 3
209 Classroom 0 0 Yes 800 18 18 Unit Ventilator
210 Classroom 398 26 946 21 21 Unit Ventilator
214 Classroom 282 18 Yes 1736 39 39 Unit Ventilator
215 Classroom 387 25 1128 25 25 Unit Ventilator
216 Classroom 284 18 546 12 12 Unit Ventilator
217 Classroom 393 26 544 12 12 Unit Ventilator
218 Classroom 307 20 Yes 1023 23 23 Unit Ventilator
- Art Classroom 249 16 778 17 16 Unit Ventilator
- Auditorium 1908 127 2417 54 54 Unit Ventilator
- Cafe 0 0 Yes 2104 47 47 Unit Ventilator
- Gym 1076 71 Yes 3199 72 72 Unit Ventilator
- Janitor Office 0 0 0 0 N/A
- Music Classroom 292 19 833 18 18 Unit Ventilator
- Sensory Classroom 0 0 Yes 377 8 8 Unit Ventilator
- Counselor's Office 0 0 299 6 0
- Nurse's Office 0 0 Yes 263 5 5
- Medical Waiting Room 0 0 Yes 177 4 4
- Principal's Office 0 0 Yes 307 6 6
Sheet Last Modified: 04-16-2021    
School:  Edward Heston Elementary School
Vendor: Devine Brothers Devine Brothers 2nd Retest
  Devine Brothers 3rd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 148 9 440 10 9 AHU
102 Office 44 2 180 4 2 AHU
103 Classroom 70 4 308 7 4 AHU
103B Office 53 3 418 9 3 AHU
104 Vestible 25 1 220 5 1 Unit Ventilator
104A Office 36 2 102 2 2 AHU
104B Security Office 56 3 123 2 2 AHU
104C Office 27 1 99 2 1 AHU
106 Classroom 328 21 Yes 1540 35 35 Unit Ventilator
107 Classroom 35 2 Yes 440 10 10 AHU
107A Office 74 4 840 19 4 AHU
107B Storage 17 1 196 4 1 AHU
108 Classroom 296 19 Yes 1540 35 35 Unit Ventilator
109 Classroom 275 18 440 10 10 AHU
110 Classroom 322 21 Yes 1056 24 24 Unit Ventilator
112 Classroom 312 20 836 19 19 Unit Ventilator
114 Classroom 276 18 1012 23 18 Unit Ventilator
116 Classroom 279 18 Yes 968 22 22 Unit Ventilator
127 Kitchen 169 11 972 22 11 AHU
200 Classroom 296 19 264 6 6 Unit Ventilator
202 Classroom 276 18 704 16 16 Unit Ventilator
204 Classroom 316 21 396 9 9 Unit Ventilator
206 Classroom 317 21 704 16 16 Unit Ventilator
208 Classroom 281 18 748 17 17 Unit Ventilator
210 Classroom 318 21 528 12 12 Unit Ventilator
212 Classroom 329 21 748 17 17 Unit Ventilator
214 Classroom 318 21 748 17 17 Unit Ventilator
216 Classroom 270 18 748 17 17 Unit Ventilator
218 Classroom 291 19 748 17 17 Unit Ventilator
220 Classroom 424 28 748 17 17 AHU
222 Classroom 289 19 748 17 17 Unit Ventilator
224 Classroom 284 18 792 18 18 Unit Ventilator
228 Room 55.0 3 Yes 264 6 6 Unit Ventilator
232 Classroom 285 19 264 6 6 Unit Ventilator
300 Lounge 347 23 264 6 6 Unit Ventilator
301 Classroom 175 11 Yes 1568 35 35 AHU
302 Classroom 291 19 704 16 16 Unit Ventilator
304 Classroom 284 18 748 17 17 Unit Ventilator
306 Classroom 327 21 748 17 17 Unit Ventilator
308 Classroom 321 21 704 16 16 Unit Ventilator
310 Room 0.0 0 Yes 748 17 17 Unit Ventilator
312 Classroom 289 19 748 17 17 Unit Ventilator
314 Room 53.0 3 Yes 792 18 18 Unit Ventilator
316 Classroom 290 19 792 18 18 Unit Ventilator
318 Room 0.0 0 Yes 748 17 17 Unit Ventilator
320 Classroom 303 20 748 17 17 Unit Ventilator
322 Room 249.0 16 748 17 16 Unit Ventilator
324 Classroom 302 20 748 17 17 Unit Ventilator
328 Classroom 298 19 264 6 6 Unit Ventilator
- Copy Room 38 2 44 1 1 Unit Ventilator
- Main office 78 5 Yes 484 11 11 Unit Ventilator
- Nurse 30 2 176 4 2 Unit Ventilator
- Nurse Examination 76 5 88 2 2 Unit Ventilator
- Principal 43 2 176 4 2 Unit Ventilator
- Cafeteria/Aud 4,461 297 4268 97 97 AHU
- Gym 2,645 176 4620 105 105 AHU
- IMC 1,002 66 2948 67 66 AHU
- IMC/Classrooms 58 3 176 4 3 AHU
- Teachers Lounge 52 3 Yes 296 6 6 AHU
- Dean's Office 31 2 117 2 2 AHU
Sheet Last Modified: 04-23-2021    
School:  Hill-Freedman World Academy at Leeds Campus
Vendor: Goldner
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Room 0 775 17 0
2 Room 0 1008 22 0
3 Room 0 0 832 18 0
4 Room 0 784 17 0
5 Office 0 240 5 0
5 Room 0 1300 29 0
6 Office 0 64 1 0
6 Room 0 0 300 6 0
7 Room 0 0 672 15 0
8 Room 0 500 11 0
9 Room 0 1300 29 0
10 Room 0 840 19 0
119 Classroom 0 Yes 504 11 11
121 Classroom 0 Yes 525 11 11
124 Classroom 0 Yes 616 14 14
131 Classroom 0 Yes 735 16 16
134 Classroom 0 Yes 1224 27 27
- Auditorium 0 8760 199 0
Main Office Office 0 588 13 0
Principal Office 0 154 3 0
Nurse Office Suite 0 Yes 892 20 20
- Boys Gym 1,074 71 5760 130 71
- Boys Locker Room 0 3420 77 0
- Cafeteria 0 11360 258 0
- Conference Room 0 390 8 0
- Girls Gym 0 5760 130 0
- Girls Locker Room 0 3420 77 0
Sheet Last Modified: 04-28-2021    
School:  Thomas Holme Elementary School
Vendor: Devine Brothers Part 2 Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 619 41 989 22 22 Unit Ventilator
2 Classroom 524 34 989 22 22 Unit Ventilator
3 Classroom 285 19 920 20 19 Unit Ventilator
4 Classroom 576 38 1,058 24 24 Unit Ventilator
5 Classroom 550 36 1,058 24 24 Unit Ventilator
61 Classroom 214 14 Yes 1,040 23 23 Unit Ventilator
62 Truancy Court 207 13 Yes 520 11 11 Unit Ventilator
63 Classroom 312 20 Yes 1,040 23 23 Unit Ventilator
64 Classroom 527 35 1,040 23 23 Unit Ventilator
65 Classroom 300 20 Yes 1,040 23 23 Unit Ventilator
66 Classroom 423 28 1,040 23 23 Unit Ventilator
101 Classroom 679 45 920 20 20 Unit Ventilator
102 Classroom 626 41 920 20 20 Unit Ventilator
103 Classroom 500 33 920 20 20 Unit Ventilator
104 Classroom 615 41 920 20 20 Unit Ventilator
105 Classroom 628 41 920 20 20 Unit Ventilator
106 Classroom 697 46 690 15 15 Unit Ventilator
107 Classroom 321 21 960 21 21 Unit Ventilator
108 Classroom 0 Yes 108 2 2
109 Classroom 503 33 920 20 20 Unit Ventilator
110 Classroom 483 32 920 20 20 Unit Ventilator
111 Classroom 553 36 920 20 20 Unit Ventilator
112 Classroom 568 37 920 20 20 Unit Ventilator
113 Classroom 622 41 920 20 20 Unit Ventilator
201 Classroom 649 43 920 20 20 Unit Ventilator
202 Classroom 320 21 920 20 20 Unit Ventilator
203 Classroom 261 17 920 20 17 Unit Ventilator
204 Classroom 469 31 920 20 20 Unit Ventilator
205 Classroom 658 43 920 20 20 Unit Ventilator
206 Classroom 624 41 920 20 20 Unit Ventilator
207 Classroom 607 40 920 20 20 Unit Ventilator
208 Classroom 626 41 920 20 20 Unit Ventilator
209 Classroom 764 50 920 20 20 Unit Ventilator
210 Classroom 589 39 920 20 20 Unit Ventilator
211 Classroom 279 18 920 20 18 Unit Ventilator
212 Classroom 597 39 920 20 20 Unit Ventilator
213 Classroom 664 44 920 20 20 Unit Ventilator
214 Classroom 681 45 920 20 20 Unit Ventilator
215 Classroom 0 Yes 936 21 21 Unit Ventilator
216 Classroom 0 Yes 936 21 21 Unit Ventilator
- Auditorium 0 0 2,880 65 0 AHU
- Cafeteria 127 8 2,250 51 8 Unit Ventilator
- Kitchen 0 Yes 475 10 10
- Main Office 0 Yes 231 5 5 Purifier
- Principal Office 0 Yes 150 3 3
- Vice Principal Office 0 Yes 84 1 1
- Nurse Office 0 Yes 204 4 4
- Counselor Office 0 Yes 135 3 3
- Admin Office 0 Yes 156 3 3
- Dean Office 0 Yes 140 3 3
- School Police Office 0 Yes 99 2 2
- Gym 189 12 Yes 3,950 89 89 Unit Ventilator
- Music 0 0 2,340 53 0 AHU
Sheet Last Modified: 04-23-2021      
School:  Francis Hopkinson Elementary School  
Vendor: Devine Brothers Main Building Retest  
School:  Francis Hopkinson Elementary School- Little School House
Vendor: Devine Brothers      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
101 Classrooms 1,030 68 687 15 15 House Fan
102 Classrooms 873 58 627 14 14 House Fan
103 Classrooms 276 18 696 15 15 House Fan
104 Classrooms 1,044 69 643 14 14 House Fan
105 Classrooms 562 37 638 14 14 House Fan
106 Classroom 953 63 648 14 14 House Fan
107 Classroom 1,035 69 638 14 14 House Fan
108 Classrooms 432 28 675 15 15 House Fan
109 Classrooms 635 42 631 14 14 House Fan
110 Classroom 322 21 695 15 15 House Fan
201 Classrooms 707 47 696 15 15 House Fan
202 Classroom 767 51 656 14 14 House Fan
203 Classrooms 734 48 693 15 15 House Fan
204 Classrooms 787 52 647 14 14 House Fan
205 Classroom 737 49 674 15 15 House Fan
206 Classroom 792 52 657 14 14 House Fan
207 Classrooms 618 41 679 15 15 House Fan
208 Classroom 702 46 686 15 15 House Fan
209 Classroom 892 59 667 15 15 House Fan
210 Classroom 386 25 687 15 15 House Fan
300 Office 0 Yes 275 6 6 House Fan
301 Classrooms 425 28 677 15 15 House Fan
302 Classroom 0 0 Yes 668 15 15 House Fan
303 Classrooms 263 17 694 15 15 House Fan
304 Classrooms 612 40 614 13 13 House Fan
305 Classroom 437 29 672 15 15 House Fan
306 Classroom 497 33 696 15 15 House Fan
307 Classrooms 1,017 67 661 15 15 House Fan
308 Classroom 604 40 664 15 15 House Fan
309 Classroom 702 46 673 15 15 House Fan
310 Classroom 321 21 668 15 15 House Fan
311 Classrooms 393 26 638 14 14 House Fan
- Auditorium 1,307 87 3184 72 72 House Fan
- B Art Room 242 16 570 12 12 House Fan
- B Café / Gym 0 0 Yes 3572 81 81 N/A
- B ESOL Room 269 17 683 15 15 House Fan
- B Music Room 603 40 688 15 15 House Fan
- B Science Room 864 57 704 16 16 House Fan
- Main Office 0 Yes 345 7 7
- Vice Principal's Office 0 Yes 126 2 2
- Nurse Office 0 Yes 275 6 6
P1 Classroom 198 13 Yes 1184 26 26 Unit Ventilator
P2 Classroom 348 23 747 16 16 Unit Ventilator
Hopkinson LSH
1 Room 308 20 877 19 19 AHU
2 Room 323 21 900 20 20 AHU
3 Room 318 21 885 20 20 AHU
4 Room 349 23 908 20 20 AHU
5 Room 308 20 863 19 19 AHU
6 Room 256 17 Yes 876 19 19 AHU
- Corridor and Bathrooms 46 3 0 0 AHU
- Multi-Purpose Room 626 41 2003 45 41 AHU
- Office Area 204 13 352 8 8 AHU
Sheet Last Modified: 04-01-2021    
School:  Henry H. Houston Elementary School
Vendor: EMCOR Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 Yes 784 17 17 House Fan
102 Classroom 0 Yes 651 14 14 House Fan
103 Classroom 0 Yes 664 15 15 House Fan
103A Classroom 0 157 3 0 House Fan
104 Classroom 0 Yes 675 15 15 House Fan
105 Office/Principal 0 354 8 0 House Fan
106 Classroom 0 Yes 651 14 14 House Fan
107 Classroom 0 Yes 459 10 10 House Fan
108 Classroom 0 Yes 681 15 15 House Fan
109 Classroom 0 Yes 950 21 21 House Fan
111 Classroom 276 18 375 8 8 House Fan and Univent
112 Classroom 350 23 312 7 7 House Fan and Univent
201 Classroom 0 561 12 0 House Fan
202 Classroom 0 701 15 0 House Fan
203 Classroom 0 207 4 0 House Fan
204 Classroom 0 710 16 0 House Fan
205 Classroom 0 653 14 0 House Fan
206 Classroom 0 660 15 0 House Fan
207 Classroom 0 769 17 0 House Fan
208 Classroom 0 750 17 0 House Fan
209 Classroom 0 693 15 0 House Fan
210 Classroom 0 437 9 0 N/A
211 Classroom 329 21 795 18 18 Unit Ventilator
212 Classroom 309 20 396 9 9 Unit Ventilator
213 Classroom 274 18 0 0 Unit Ventilator
301 Classroom 0 667 15 0 House Fan
302 Classroom 0 Yes 661 15 15 House Fan
303 Classroom 0 664 15 0 House Fan
304 Classroom 0 729 16 0 House Fan
305 Classroom 0 674 15 0 House Fan
306 Classroom 0 670 15 0 House Fan
307 Classroom 0 758 17 0 House Fan
308 Classroom 0 716 16 0 House Fan
309 Classroom 0 613 13 0 House Fan
309A Small Office 0 201 4 0 House Fan
- Kitchen 0 0 638 14 0 N/A
- Auditorium 1853 123 1500 34 34 AHU 1 and 2
- Library 0 0 1404 31 0 RTU
- Gym  0 Yes 2,232 50 50 N/A
- Old Art Room 0 631 14 0 N/A
- Cafeteria 0 0 4500 102 0 Nesbitt Unit Ventilator
- Old School Store A 230 15 863 19 15 Nesbitt Unit Ventilator
- Old School Store B 345 23 311 7 7 Nesbitt Unit Ventilator
- New School Store 347 23 291 6 6 Nesbitt Unit Ventilator
- Medical Suite Large 0 242 5
- Medical Suite Small 0 126 2
- Medical Suite Medium 0 238 5 0 House Fan
Sheet Last Modified: 4-21-21    
School:  Julia Ward Howe Academics Plus Elementary School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B-1 Art 751 50 754 17 17 House Fan
1 Classroom 1269 84 690 15 15 House Fan
2 Classroom 1240 82 690 15 15 House Fan
3 Classroom 344 22 690 15 15 House Fan
4 Classroom 455 30 690 15 15 House Fan
5 Classroom 1500 100 196 4 4 House Fan
6 Classroom 479 31 713 16 16 House Fan
7 Classroom 1470 98 690 15 15 House Fan
8 Classroom 1454 96 690 15 15 House Fan
9 Classroom 564 37 720 16 16 House Fan
10 Classroom 1739 115 690 15 15 House Fan
11 Classroom 628 41 690 15 15 House Fan
12 Classroom 829 55 720 16 16 House Fan
13 Library 0 0 720 16 0 House Fan
14 Classroom 1302 86 690 15 15 House Fan
15 Classroom 1044 69 690 15 15 House Fan
16 Computer Lab 0 0 690 15 0 House Fan
17 Classroom 548 36 690 15 15 House Fan
18 Classroom 824 54 690 15 15 House Fan
19 Classroom 869 57 690 15 15 House Fan
20 Classroom 0 0 690 15 0 House Fan
21 Classroom 149 9 Yes 690 15 15 House Fan
22 Classroom 898 59 690 15 15 House Fan
23 Classroom 210 14 690 15 14 House Fan
23A - 0 Yes 91 2 2 House Fan
24 Classroom 0 0 350 7 0 House Fan
- Cafeteria 0.0 0 Yes 1,566 35 35 House Fan
- Gym 0 Yes 1,060 24 24 House Fan
- Jugg Room 0 195 4 0 House Fan
- Main Office 0 238 5 0 House Fan
- Principals Office 0 Yes 180 4 4 House Fan
- Counselors Office 0 162 3 0 House Fan
- Psychologists Office 0 Yes 99 2 2 House Fan
- Lounge 0 266 6 0 House Fan
- Security 0 Yes 91 2 2 House Fan
Sheet Last Modified: 4-6-21    
School:  New William H. Hunter Elementary School
Vendor: Devine Brothers Devine Retest
  Devine 2nd Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Office 40 2 149 3 2 AHU-3
2 Office 33 2 143 3 2 AHU-3
3 Office 24 1 72 1 1 AHU-3
4 Office 48 3 92 2 2 AHU-3
101A Classroom 363 24 695 15 15 AHU-1
101B Classroom 378 25 695 15 15 AHU-1 + UV
101C Classroom 358 23 650 14 14 AHU-1
101D Classroom 551 36 650 14 14 AHU-1 + UV
101E Classroom 351 23 610 13 13 AHU-1
101F Classroom 393 26 650 14 14 AHU-1 + UV
102 Classroom 375 25 410 9 9 AHU-1 and UV
107 Main Office Entry 103 6 350 7 6 AHU-3
107 Main Office 195 13 Yes 1125 25 25 AHU-3
108 Classroom 666 44 715 16 16 AHU-5 + UV
109 Classroom 497 33 695 15 15 AHU-5 + UV
110 Classroom 477 31 695 15 15 AHU-5 + UV
111 Classroom 632 42 695 15 15 AHU-5 + UV
112 Classroom 496 33 695 15 15 AHU-5 + UV
113 Music Room 456 30 1430 32 30 AHU-7
113 Practice Rm 1 23 1 72 1 1 AHU-7
113 Practice Rm 2 27 1 78 1 1 AHU-7
201 IMC 1373 91 2995 68 68 AHU-10 + UV
202 Classroom 467 31 1125 25 25 Unit Ventilator and AHU
202 Media 0 0 Yes 385 8 8 Unit Ventilator and AHU
BAS 205 IMC - Reading Small Classroom 303 20 102 2 2 Tightened damper Actuator to the shaft
BAS 206 IMC - Reading Small Classroom 317 21 859 19 19 Tightened damper Actuator to the shaft
206 Classroom 464 30 842 19 19 AHU-1 + UV
207 Classroom 610 40 1325 30 30 Unit Ventilator and AHU
208 Classroom 318 21 Yes 1395 31 31 Unit Ventilator and AHU
208 Computer Lab 81 5 1210 27 5
209 Classroom 293 19 750 17 17 AHU-1 + UV
210 Classroom 526 35 754 17 17 Unit Ventilator and AHU
211 Classroom 551 36 754 17 17 Unit Ventilator and AHU
212 Classroom 426 28 753 17 17 Unit Ventilator and AHU
213 Classroom 497 33 753 17 17 Unit Ventilator and AHU
214 Classroom 478 31 724 16 16 Unit Ventilator and AHU
215 Art Room 367 24 Yes 1324 30 30 AHU-12
304 Classroom 367 24 725 16 16 Unit Ventilator and AHU
305 Classroom 431 28 754 17 17 Unit Ventilator and AHU
306 Classroom 395 26 754 17 17 Unit Ventilator and AHU
307 Classroom 315 21 753 17 17 Unit Ventilator and AHU
308 Classroom 350 23 753 17 17 Unit Ventilator and AHU
309 Classroom 340 22 754 17 17 Unit Ventilator and AHU
310 Classroom 361 24 754 17 17 Unit Ventilator and AHU
311 Classroom 317 21 753 17 17 Unit Ventilator and AHU
312 Classroom 427 28 753 17 17 Unit Ventilator and AHU
313 Classroom 387 25 754 17 17 Unit Ventilator and AHU
314 Classroom 411 27 715 16 16 Unit Ventilator and AHU
315 Classroom 363 24 810 18 18 Unit Ventilator and AHU
- Auditorium 2966 197 2910 66 66 AHU-6
- Cafeteria 2006 133 3590 81 81 AHU
- Kitchen 35 2 Yes 1116 25 25 AHU-3
- Nurses Office 98 6 105 2 2 FC 5-1
- Nurse Exam Room 110 7 94 2 2 FC 5-1
- Nurses Waiting Room 108 7 130 2 2 FC 5-1
- Principal Office 74 4 Yes 322 7 7 AHU-3
- Conference Room 147 9 429 9 9 AHU-3
- Gym 1430 95 4969 112 95 AHU-8 + AHU-9
Sheet Last Modified: 04-13-2021      
School:  Andrew Jackson Elementary School House fan Abated
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B1 Music Room 324 21 1036 23 21 AHU
101 Classroom 536 35 1190 27 27 AHU
102 Classroom 436 29 638 14 14 AHU
103 Classroom 567 37 805 18 18 AHU
104 Classroom 363 24 840 19 19 AHU
105 Classroom 398 26 828 18 18 AHU
106 Classroom 740 49 748 17 17 AHU
107 Classroom 567 37 736 16 16 AHU
107B - 0 Yes 132 3 3 N/A
107C - 0 Yes 220 5 5 N/A
108 Classroom 396 26 841 19 19 AHU
109 Classroom 669 44 1218 27 27 AHU
110 Classroom 482 32 848 19 19 AHU
201 Classroom 581 38 1225 27 27 AHU
202 Classroom 346 23 726 16 16 AHU
203 Classroom 384 25 864 19 19 AHU
204 Classroom 453 30 850 19 19 AHU
204A Office 0 0 Yes 468 10 10
205 Classroom 304 20 840 19 19 AHU
206 Classroom 531 35 864 19 19 AHU
207 Classroom 614 40 805 18 18 AHU
208 Classroom 367 24 850 19 19 AHU
209/210 Classroom 1387 92 1680 38 38 AHU
211 Classroom 490 32 840 19 19 AHU
301 Classroom 530 35 980 22 22 AHU
302 Classroom 303 20 816 18 18 AHU
303 Classroom 88 5 Yes 828 18 18
304 Classroom 427 28 805 18 18 AHU
304A Office 0 0 Yes 442 10 10
305 Classroom 619 41 840 19 19 AHU
306 Classroom 528 35 840 19 19 AHU
307 Classroom 375 25 782 17 17 AHU
308 Classroom 417 27 816 18 18 AHU
- Gym/Cafeteria 2408 160 3005 68 68 AHU
- Library 740 49 2320 52 49 AHU
- I.M.C. Office 160 10 400 9 9 AHU
- Main Office 0 0 Yes 484 11 11
- Princpal's Office 0 Yes 308 7 7 N/A
- Nurse's Office 0 Yes 264 6 6 N/A
Sheet Last Modified: 04-26-2021    
School:  James Martin- Alternative Middle Years (Middle School)
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 0 Yes 696 15 15
106 Classroom 280 18 720 16 16
107 Classroom 313 20 720 16 16
108 Classroom 0 0 Yes 696 15 15
109 Classroom 0 0 Yes 672 15 15
201 Classroom 0 0 Yes 720 16 16
202 Classroom 0 0 Yes 750 17 17
203 Classroom 306 20 750 17 17
204 Lounge 371 24 480 10 10
205 Classroom 345 23 912 20 20
206 School Store 291 19 384 8 8
207 Classroom 309 20 750 17 17
208 Classroom 331 22 720 16 16
209 Classroom 303 20 667 15 15
210 Classroom 292 19 667 15 15
211 Classroom 0 0 Yes 672 15 15
214 Security Office 0 0 Yes 256 5 5
301 Classroom 0 0 Yes 696 15 15
302 Classroom 0 0 Yes 696 15 15
303 Classroom 301 20 720 16 16
304 Classroom 275 18 720 16 16
305 Classroom 297 19 696 15 15
306 Classroom 284 18 720 16 16
307 Classroom 297 19 768 17 17
308 Classroom 317 21 696 15 15
309 Classroom 272 18 696 15 15
310 Classroom 293 19 720 16 16
311 Art Room 0 0 Yes 928 21 21
314 Office 0 0 Yes 256 5 5
- Boys Cafeteria 0 0 Yes 851 19 19
- Counselors Office 0 0 Yes 160 3 3
- Girls Cafeteria 0 0 Yes 1728 39 39
- Gym 0 0 1760 40 0
- IMC-A 270 18 720 16 16
- IMC-B 292 19 720 16 16
- IMC-C 283 18 720 16 16
- Main Office 0 0 Yes 360 8 8
- Nurses Office 0 0 Yes 256 5 5
- Teachers Lounge 0 0 480 10 0
Sheet Last Modified: 04-26-2021        
School:  Abraham S. Jenks Elementary School House fan Abated
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
14 Classroom 422 28 638 14 14 House Fan
15 Cafeteria 221 14 638 14 14 House Fan
101 Classroom 459 30 660 15 15 House Fan
102 Classroom 1235 82 660 15 15 House Fan
103 Classroom 1253 83 660 15 15 House Fan
104 Classroom 919 61 660 15 15 House Fan
105 Classroom 632 42 660 15 15 House Fan
106 Classroom 748 49 660 15 15 House Fan
201 Classroom 1277 85 690 15 15 House Fan
202 Classroom 522 34 690 15 15 House Fan
203 Classroom 1094 72 690 15 15 House Fan
204 Classroom 803 53 690 15 15 House Fan
205 Classroom 749 49 690 15 15 House Fan
206 Classroom 1198 79 690 15 15 House Fan
207 Classroom 1279 85 744 16 16 House Fan
- Principals Office 0 Yes 165 3 3
- Main Office 0 Yes 195 4 4
- Teacher Lounge 0 165 3 0
- Nurses Office 0 Yes 190 4 4
- Library 176 11 638 14 11 House Fan
- Auditorium 217 14 1540 35 14 UV
- Cafeteria 362 24 638 14 14 House Fan
- North Trailer Classroom 227 15 N/A 0 0 N/A used for storage
- South Trailer Classroom 261 17 638 14 14 AHU
- Gym 0 Yes 1700 38 38 N/A
Sheet Last Modified: 04-28-2021          
School:   John S. Jenks Elementary-Middle School      
         
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
322 Classroom 0 Yes 658 14 14 House Fan
321 Classroom 0 Yes 692 15 15 House Fan
320 Classroom 0 Yes 685 15 15 House Fan
319B - 0 Yes 658 14 14 House Fan
319A - 0 Yes 305 6 6 House Fan
318 Classroom 0 Yes 654 14 14 House Fan
317 Classroom 0 Yes 674 15 15 House Fan
316 Classroom 0 Yes 693 15 15 House Fan
315 Classroom 0 Yes 654 14 14 House Fan
214 Classroom 0 Yes 671 15 15 House Fan
213 Classroom 0 Yes 689 15 15 House Fan
212 Classroom 0 Yes 683 15 15 House Fan
211 Classroom 0 Yes 673 15 15 House Fan
210 Classroom 0 Yes 671 15 15 House Fan
209 Classroom 0 Yes 680 15 15 House Fan
208 Classroom 0 Yes 695 15 15 House Fan
207 Classroom 0 Yes 636 14 14 House Fan
110 - 0 Yes 336 7 7 House Fan
109 - 0 Yes 156 3 3 house Fan
106 IMC 0 Yes 671 15 15 House Fan
105 Classroom 0 Yes 640 14 14 House Fan
104 Classroom 0 Yes 627 14 14 House Fan
103 Classroom 0 Yes 666 15 15 House Fan
102 Classroom 0 Yes 668 15 15 House Fan
101 Classroom 0 Yes 602 13 13 House Fan
100 Classroom 0 Yes 1053 23 23 House Fan
- Kindergarten Classroom 0 Yes 1512 34 34 House Fan
- Gym 0 Yes 4500 102 102
- Main Office 0 Yes 385 8 8
- Principal Office 0 Yes 112 2 2
- Library 0 Yes 616 13 13
- Teachers Lounge 0 Yes 402 9 9
- Spo 0 Yes 180 4 4
- Counselor Office 0 Yes 165 3 3
- Nurse Office 0 Yes 263 5 5
- Speech Room 0 Yes 103 2 2
- Auditorium 0 3463 78 0
- Copy Room 0 166 3 0
- Art Room 0 Yes 1085 24 24
- Lego Room 0 Yes 165 3 3
- Kitchen 0 Yes 578 13 13
- Gym Office 0 588 13 0
- Home & school 0 364 8 0
- Boys Room 0 144 3 0
- Girls Room 0 144 3 0
- Boys room by gym 0 614 13 0
- Girls room by gym 0 614 13 0
Sheet Last Modified: 04-06-2021    
School:  Juniata Park Academy Elementary-Middle School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 1020 68 1100 25 25 RTU/UV
2 Classroom 897 59 1108 25 25 RTU/UV
3 Classroom 1328 88 1108 25 25 RTU/UV
4 Classroom 1321 88 1093 24 24 RTU/UV
5 Classroom 975 65 1123 25 25 RTU/UV
6 Classroom 874 58 1125 25 25 RTU/UV
100 Classroom 750 50 660 15 15 RTU/UV
101 Classroom 969 64 660 15 15 RTU/UV
102 Classroom 836 55 952 21 21 RTU/UV
103 Classroom 1212 80 792 18 18 RTU/UV
104 Classroom 1119 74 792 18 18 RTU/UV
105 Classroom 2327 155 794 18 18 RTU/UV
106 Classroom 1053 70 794 18 18 RTU/UV
107 Classroom 789 52 794 18 18 RTU/UV
108 Classroom 952 63 794 18 18 RTU/UV
109 Classroom 910 60 794 18 18 RTU/UV
110 Classroom 817 54 794 18 18 RTU/UV
111 Classroom 1240 82 794 18 18 RTU/UV
112 Classroom 1129 75 794 18 18 RTU/UV
113 Classroom 967 64 794 18 18 RTU/UV
114 Classroom 906 60 794 18 18 RTU/UV
115 Classroom 1064 70 792 18 18 RTU/UV
117 Girls' Toilet Room 115 7 140 3 3 RTU/UV
116 Classroom 853 56 792 18 18 RTU/UV
117 Classroom 636 42 672 15 15 RTU/UV
120 Boys' Toilet Room 120 8 200 4 4 RTU/UV
200 Classroom 661 44 609 13 13 RTU/UV
201 Classroom 638 42 772 17 17 RTU/UV
202 Classroom 449 29 721 16 16 RTU/UV
203 Classroom 691 46 673 15 15 RTU/UV
204 Classroom 534 35 794 18 18 RTU/UV
205 Classroom 627 41 794 18 18 RTU/UV
205 Girls' Toilet Room 22 1 182 4 1 RTU/UV
206 Classroom 530 35 794 18 18 RTU/UV
207 Classroom 539 35 794 18 18 RTU/UV
208 Classroom 665 44 794 18 18 RTU/UV
208 Boys' Toilet Room 24 1 195 4 1 RTU/UV
209 Classroom 509 33 794 18 18 RTU/UV
210 Classroom 310 20 794 18 18 RTU/UV
211 Classroom 418 27 794 18 18 RTU/UV
212 Classroom 487 32 794 18 18 RTU/UV
213 Classroom 539 35 794 18 18 RTU/UV
215 Classroom 538 35 794 18 18 RTU/UV
217 Classroom 683 45 793 18 18 RTU/UV
229 Girls' Toilet Room 330 22 195 4 4 RTU/UV
235 Boys' Toilet Room 140 9 200 4 4 RTU/UV
- Main Office 740 49 500 11 11 RTU/UV
- Confrence Room 475 31 203 4 4 RTU/UV
- Main Office 4 255 17 153 3 3 RTU/UV
- Main Office 3 255 17 120 2 2 RTU/UV
- Main Office 2 260 17 120 2 2 RTU/UV
- Main Office 1 310 20 162 3 3 RTU/UV
- Main Office Work Room 245 16 165 3 3 RTU/UV
- Principals Office 365 24 201 4 4 RTU/UV
- Principal Bathroom 52 3 77 1 1 RTU/UV
-  IMC Workroom 79 5 347 7 5 RTU/UV
- IMC Conference Rm 128 8 360 8 8 RTU/UV
- IMC Reference 62 4 260 5 4 RTU/UV
- IMC Main Area North 320 21 1432 32 21 RTU/UV
- IMC Main Area South 217 14 1432 32 14 RTU/UV
- Library 710 47 2864 65 47 RTU/UV
- Art Room 701 46 1202 27 27 RTU/UV
- Music Classroom 738 49 1248 28 28 RTU/UV
- Cafeteria 9,535 635 4250 96 96 RTU/UV
- Food Service 135 9 Yes 1600 36 36 RTU/UV
- Computer Lab 1,062 70 1000 22 22 RTU/UV
- Science Lab 1,041 69 1436 32 32 RTU/UV
- Tech Ed 1,222 81 1415 32 32 RTU/UV
- Health Suite 575 38 250 5 5 RTU/UV
- Conference Rm 37 2 99 2 2 RTU/UV
- Corridor 405 27 0 0 RTU/UV
- Lounge 220 14 418 9 9 RTU/UV
- Refrence Rm 165 11 120 2 2 RTU/UV
- Boys' Toilet Room 327 21 200 4 4 RTU/UV
- Girls' Toilet Room 227 15 140 3 3 RTU/UV
- Storage 190 12 156 3 3 RTU/UV
- Trash Rm 160 10 213 4 4 RTU/UV
- Work Room 160 10 152 3 3 RTU/UV
- Workshop 210 14 153 3 3 RTU/UV
- Bldg Engineer 160 10 150 3 3 RTU/UV
- Gym 0 6809 154 0 AHU
Sheet Last Modified: 04-13-2021    
School:  General Philip Kearny Elementary School
Vendor: Chadwick Exhaust Report Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 0 0 780 17 0 UV
2 classroom 900 60 780 17 17 UV
3 classroom 1,129 75 780 17 17 UV
4 classroom 1,177 78 780 17 17 UV
100 classroom 1,118 74 750 17 17 House Fan
101 classroom 1,353 90 700 15 15 House Fan
103 classroom 1,342 89 945 21 21 House Fan
105 classroom 1,642 109 696 15 15 House Fan
107 classroom 314 20 744 16 16 House Fan
200 classroom 1,129 75 696 15 15 House Fan
201 classroom 1,048 69 696 15 15 House Fan
202 classroom 1,034 68 783 17 17 House Fan
203 classroom 1,345 89 810 18 18 House Fan
204 classroom 1,224 81 324 7 7 House Fan
207 classroom 1,653 110 768 17 17 House Fan
300 classroom 1,129 75 672 15 15 House Fan
301 classroom 990 66 725 16 16 House Fan
302 classroom 623 41 783 17 17 House Fan
303 classroom 986 65 810 18 18 House Fan
305 classroom 1,268 84 720 16 16 House Fan
306 classroom 1,338 89 414 9 9 House Fan
307 classroom 1,067 71 768 17 17 House Fan
308 classroom 931 62 675 15 15 House Fan
309 classroom 1,059 70 675 15 15 House Fan
310 classroom 1,114 74 675 15 15 House Fan
311 classroom 1,191 79 675 15 15 House Fan
312 classroom 924 61 414 9 9 House Fan
312 classroom 1,529 101 414 9 9 House Fan
315 classroom 1,386 92 702 15 15 House Fan
- Gym 9,069 604 6100 138 138 RTU
- Main office 0 Yes 340 7 7 House Fan
- Principal office 0 Yes 320 7 7 House Fan
Cafeteria 0 Yes 3240 73 73
- Auditorium 0 3240 73 0 House Fan
- Faculty 0 336 7 0
- Kitchen 0 700 15 0 House Fan
- Nurse 0 Yes 171 3 3 House Fan
- Lunchroom 0 Yes 3078 69 69 House Fan
Sheet Last Modified: 04-22-2021    
School:  William D. Kelley Elementary School
Vendor: Devine Brothers Devine Part 2
  Devine Part 3 Devine Part 4
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 315 21 1,053 23 21 UV
102 Classroom 322 21 880 20 20 UV
103 Classroom 319 21 735 16 16 UV
104 Classroom 318 21 805 18 18 UV
104B Classroom 301 20 870 19 19 UV
105 Classroom 357 23 735 16 16 UV
106 Classroom 395 26 735 16 16 UV
108 Classroom 376 25 735 16 16 UV
109 Classroom 302 20 735 16 16 UV
110 Classroom 321 21 442 10 10 UV
111 Classroom 339 22 735 16 16 UV
200 Classroom 357 23 700 15 15 UV
201 Classroom 302 20 720 16 16 UV
202 Classroom 330 22 770 17 17 UV
203 Classroom 314 20 735 16 16 UV
204 Classroom 355 23 735 16 16 UV
205 Classroom 344 22 735 16 16 UV
206 Classroom 284 18 406 9 9 UV
207 Classroom 332 22 735 16 16 UV
208 IMC 302 20 1,540 35 20 UV
209 Classroom 341 22 770 17 17 UV
210 IMC 323 21 1,540 35 21 UV
211 Classroom 307 20 735 16 16 UV
212 Classroom 305 20 510 11 11 UV
214 Classroom 339 22 735 16 16 UV
216 Classroom 330 22 735 16 16 UV
218 Classroom 180 12 143 3 3 UV
300 Classroom 311 20 700 15 15 UV
301 Classroom 320 21 720 16 16 UV
302 Classroom 416 27 770 17 17 UV
303 Classroom 380 25 735 16 16 UV
304 Classroom 305 20 735 16 16 UV
306 Classroom 281 18 406 9 9 UV
307 Classroom 292 19 735 16 16 UV
308 Classroom 385 25 735 16 16 UV
309 Classroom 318 21 735 16 16 UV
310 Classroom 163 10 Yes 735 16 16 UV
311 Classroom 334 22 735 16 16 UV
312 Classroom 275 18 510 11 11 UV
314 Classroom 325 21 735 16 16 UV
316 Classroom 302 20 735 16 16 UV
318 Classroom 181 12 143 3 3 UV
- Auditorium 1,841 122 4,278 97 97 AHU
- Gymnasium 899 59 3,588 81 59 AHU
- Library 625 41 1,540 35 35 UV
- Main Office 101 6 Yes 483 10 10 AHU
- Nurse Office 84 5 Yes 368 8 8
- Admin Asst. Office 38 2 99 2 2
- Principal's Office 41 2 315 7 2
- Conference/Office 90 6 384 8 6
- Counselor's Office 0 0 442 10 0
Sheet Last Modified: 04-30-2021    
School:  John B. Kelly Elementary School
Vendor: Capital
Vendor: Devine Brothers Retest 2nd Retest
  Devine 3rd Retest Devine 4th Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Teachers Dining 340 22 868 19 19 UV
102 Classroom 497 33 850 19 19 UV
102A Classroom 155 10 550 12 10 UV
103 Classroom 673 44 850 19 19 UV
103A Classroom 216 14 550 12 12 UV
104 Classroom 607 40 850 19 19 UV
105 Classroom 592 39 850 19 19 UV
106 Classroom 576 38 850 19 19 UV
107 Classroom 572 38 850 19 19 UV
108 Classroom 576 38 850 19 19 UV
109 Classroom 539 35 850 19 19 UV
110 Classroom 434 28 850 19 19 UV
111 Classroom 336 22 850 19 19 UV
112 Classroom 627 41 850 19 19 UV
113 Classroom 320 21 850 19 19 UV
114 Classroom 534 35 850 19 19 UV
160 Classroom 305 20 942 21 20 UV
160 Main Office 182 12 232 5 5 UV
201 Classroom 370 24 850 19 19 UV
202 Classroom 494 32 850 19 19 UV
202A Office 33 2 140 3 2 UV
203 Classroom 744 49 1088 24 24 UV
204 Classroom 609 40 850 19 19 UV
204A Classroom 282 18 550 12 12 UV
205 Classroom 327 21 850 19 19 UV
205A Classroom 293 19 550 12 12 UV
206 Classroom 284 18 1088 24 18 UV
207 Classroom 468 31 850 19 19 UV
208 Classroom 586 39 850 19 19 UV
209 Classroom 381 25 850 19 19 UV
210 Classroom 341 22 1088 24 22 UV
210A Office 188 12 136 3 3 UV
211 Classroom 530 35 850 19 19 UV
212 Classroom 729 48 850 19 19 UV
212A Classroom 289 19 550 12 12 UV
213 Classroom 661 44 850 19 19 UV
213A Classroom 233 15 550 12 12 UV
214 Classroom 588 39 1088 24 24 UV
215 Classroom 341 22 676 15 15 UV
216 Classroom 425 28 850 19 19 UV
217 East Classroom 294 19 1006 22 19 UV
217 North Classroom 227 15 1093 24 15 UV
217 South Center Classroom 382 25 1069 24 24 UV
217 West Center Classroom 285 19 1093 24 19 UV
- Admin/Asst. Office 66 4 179 4 4 UV
- Administration Offices 1305 87 535 12 12 UV
ART Art Classroom 731 48 1350 30 30 UV
ART -A Art Classroom 401 26 0 0 UV
ART -B Art Classroom 557 37 0 0 UV
ART -C Art Classroom 111 7 0 0 UV
ART -D Art Classroom 318 21 0 0 UV
- Auditorium 1721 114 6080 138 114 UV
- 1st Flr A-Wing Left Boys Bathroom 53 3 88 2 2 AHU
- 2nd Flr A-Wing Left Boys Bathroom 101 6 96 2 2 AHU
- 2nd Flr A-Wing Right Boys Bathroom 43 2 103 2 2 AHU
- Conference Room 139 9 211 4 4 AHU
- Copy/Storage Room 110 7 165 3 3 AHU
- Corridor 41 2 0 0 AHU
- Counselor Office 58 3 123 2 2 AHU
- Dressing - A Backstage 307 20 232 5 5 UV
- Dressing - B Backstage 461 30 196 4 4 UV
- Dressing - C Backstage 493 32 190 4 4 UV
- Dressing - D Backstage 275 18 199 4 4 UV
- 1st Flr A-Wing Left Girls Bathroom 41 2 109 2 2 AHU
- 2nd Flr A-Wing Left Girls Bathroom 78 5 106 2 2 AHU
- 2nd Flr A-Wing Right Girls Bathroom 54 3 103 2 2 AHU
- IMC 0 0 8471 192 0 AHU
- IMC North Side 947 63 480 10 10 AHU
- IMC South Side 822 54 480 10 10 AHU
- IMC Entry from Office 0 0 0 0 AHU
- IMC Entry to Hall 0 0 0 0 AHU
- IMC-1 Office 80 5 293 6 5 AHU
- IMC-2 Storage 151 10 330 7 7 AHU
- IMC-4 Storage 175 11 372 8 8 AHU
- IMC-5 Data/Storage 68 4 277 6 4 AHU
- Cafeteria 0 0 1195 27 0 AHU
- Cafeteria 1928 128 4807 109 109 AHU
- Gym 2934 195 387 8 8 AHU
- Music Classroom A 326 21 0 0 UV
- Music Classroom B 555 37 0 0 UV
- Music Classroom C 152 10 0 0 UV
- Music Classroom D 106 7 0 0 UV
- Main Music Classroom 463 30 380 8 8 UV
- Music Office 136 9 355 8 8 AHU
- Nurse Exam Room 0 0 209 4 0 AHU
- Nurse Exam Room 43 2 0 0 AHU
- Nurses Office 0 0 0 0 AHU
- Nurses Rest 68 4 0 0 AHU
- Nurses Suite 411 27 0 0 UV
- Aud & Dental 31 2 270 6 2 AHU
- Principals Office 98 6 270 6 6 AHU
- Speech/Com 388 25 736 16 16 UV
- Server Room 55 3 121 2 2 Split System
- Storage 247 16 809 18 16 AHU
- Office / Waiting Room 277 18 0 0 AHU
K - 1 Kindergarten 452 30 1488 33 30 UV
K - 2 Kindergarten 490 32 1488 33 32 UV
K - 3 Kindergarten 498 33 1488 33 33 UV
K - 4 Kindergarten 635 42 1488 33 33 UV
K - 5 Kindergarten 280 18 1488 33 18 UV
K - 6 Kindergarten 300 20 1488 33 20 UV
Sheet Last Modified: 04-23-2021    
School:  Kenderton Elementary School
Vendor: Chadwick Part 2 Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 229 15 1,012 23 15 UV
101 Classroom 451.0 30 1680 38 30 UV
102 Classroom 458.0 30 1652 37 30 UV
103 Classroom 331.0 22 Yes 1344 30 30 UV
104 Nurse 0 Yes 275 6 6
200A Classroom 198.0 13 442 10 10 UV
200 Classroom 0.0 0 891 20 0 UV
201 Classroom 278.0 18 Yes 891 20 20 UV
202 Classroom 331.0 22 918 20 20 UV
203 Classroom 297 19 980 22 19 UV
204 Classroom 302 20 918 20 20 UV
205 Classroom 198 13 918 20 13 UV
206 Classroom 273 18 616 14 14 UV
207 Classroom 273 18 918 20 18 UV
208 Classroom 191 12 Yes 120 2 2 UV
209 Classroom 283 18 918 20 18 UV
211 Classroom 276 18 286 6 6 UV
213 Classroom 271 18 918 20 18 UV
300 Classroom 278 18 Yes 918 20 20 UV
301 Classroom 271 18 918 20 18 UV
302 Classroom 272 18 Yes 918 20 20 UV
303 Classroom 296 19 980 22 19 UV
304 Classroom 276 18 864 19 18 UV
306 Classroom 316 21 918 20 20 UV
307 Classroom 281 18 Yes 924 21 21 UV
308 Classroom 0 0 Yes 924 21 21 UV
309 Classroom 0 0 980 22 0 UV
310 Classroom 0 0 Yes 616 14 14 UV
311 Classroom 0 0 Yes 918 20 20 UV
312 Computer Room 0 Yes 860 19 19
313 Classroom 0 0 Yes 918 20 20 UV
314 Classroom 0 0 280 6 0 UV
315 Classroom 0 0 Yes 918 20 20 UV
316 Classroom 0 0 Yes 840 19 19 UV
319 Classroom 0 0 918 20 0 UV
400 Classroom 286 19 2660 60 19 UV
401 Classroom 279 18 918 20 18 UV
402 Classroom 313 20 918 20 20 UV
403 Classroom 340 22 918 20 20 UV
404 Classroom 0 0 868 19 0 UV
406 Classroom 291 19 918 20 19 UV
407 Classroom 0 0 Yes 924 21 21 UV
408 Classroom 0 0 Yes 918 20 20 UV
409 Classroom 0 0 Yes 980 22 22 UV
410 Classroom 335 22 Yes 644 14 14 UV
411 Classroom 0 0 918 20 0 UV
412 Classroom 276 18 308 7 7 UV
413 Classroom 0 0 Yes 840 19 19 UV
414 Classroom 0 0 Yes 270 6 6 UV
415 Classroom 0 0 918 20 0 UV
- Parent Resource 0 0 2 0 0 UV
- Main Office 42 2 406 9 2 UV
- Principal's Office 0 320 7 0
- Asist Prince 172 11 11 0 0 UV
Sheet Last Modified: 04-19-2021      
School:  Kensington High School House fan Abated
     
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 - 0 675 15 0
2 - 0 1,014 23 0
3 - 0 728 16 0
4 - 0 364 8 0
5 - 0 850 19 0
100 Main Office 0 1,014 23 0
102 - 0 Yes 800 18 18
103 IMC 0 1,690 38 0
104 - 0 728 16 0
105 - 0 728 16 0
107 - 0 728 16 0
108 - 0 962 21 0
109 - 0 728 16 0
111 - 0 910 20 0
114 - 0 Yes 728 16 16
115 - 0 728 16 0
116 - 0 702 15 0
117 - 0 728 16 0
118 - 0 Yes 728 16 16
120 - 0 845 19 0
125 - 0 1,020 23 0
200 - 0 728 16 0
201 - 0 962 21 0
202 - 0 910 20 0
203 - 0 728 16 0
204 - 0 702 15 0
205 - 0 728 16 0
207 - 0 728 16 0
208 - 0 884 20 0
209 - 0 546 12 0
210 - 0 546 12 0
211 - 0 884 20 0
214 - 0 728 16 0
215 - 0 728 16 0
217 - 0 728 16 0
218 - 0 728 16 0
221 - 0 1,037 23 0
300 - 0 728 16 0
301 - 0 910 20 0
302 - 0 910 20 0
303 - 0 702 15 0
304 - 0 728 16 0
305 - 0 702 15 0
307 - 0 728 16 0
308 - 0 910 20 0
309 - 0 546 12 0
310 - 0 546 12 0
311 - 0 884 20 0
314 - 0 728 16 0
315 - 0 728 16 0
316 - 0 728 16 0
317 - 0 728 16 0
318 - 0 728 16 0
322 Gym 0 6,360 144 0
Sheet Last Modified: 04-22-2021      
School:  Kensington Creative and Performing Arts (CAPA) High School
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Auditorium 0 5100 115 0
- Gymnasium 0 8400 190 0
101b - 0 450 10 0
101 - 0 400 9 0
103 - 0 1200 27 0
106 - 0 1200 27 0
118 - 0 900 20 0
119 - 0 900 20 0
121 - 0 900 20 0
122 - 0 900 20 0
123 - 0 900 20 0
131 - 0 1150 26 0
134 - 0 Yes 700 15 15
135 - 0 750 17 0
201 - 0 1200 27 0
209 - 0 900 20 0
210 - 0 900 20 0
212 - 0 900 20 0
213 - 0 900 20 0
214 - 0 900 20 0
216 - 0 Yes 1400 31 31
217 - 0 1400 31 0
218 - 0 1200 27 0
220 - 0 1200 27 0
221 - 0 1200 27 0
224 - 0 900 20 0
225 - 0 900 20 0
- Cafe 0 2400 54 0
Sheet Last Modified: 04-23-2021    
School: Kensington Health Sciences Academy High School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Room 247 16 857 19 16
102 Room 338 22 792 18 18
103 Room 206 13 854 19 13
104 Room 248 16 834 18 16
105 Room 212 14 854 19 14
106 Room 548 36 834 18 18
107 & 107A Room 613 40 783 17 17
110 Room 184 12 793 18 12
114 Nurse 0 114 2 0
115 Room 191 12 337 7 7
116 Room 171 11 848 19 11
201 Room 506 33 919 20 20
203 Room 0 0 795 18 0
208 2nd Floor Bed and Dental Area 1803 120 943 21 21
211 Room 273 18 860 19 18
212 Room 77 5 456 10 5
213 Room 250 16 681 15 15
214 Dental Classroom 171 11 794 18 11
215 Room 204 13 689 15 13
216 Room 191 12 756 17 12
217 Room 222 14 681 15 14
218 Room 276 18 599 13 13
- Cafeteria 586 39 1697 38 38
Sheet Last Modified: 03-30-2021      
School:  Francis Scott Key Elementary School
Vendor:  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Gym 0 Yes 704 16 16 House Fan
102 Classroom 0 Yes 713 16 16 House Fan
103 Classroom 0 Yes 713 16 16 House Fan
104 Classroom 0 Yes 736 16 16 House Fan
105 Classroom 0 Yes 704 16 16 House Fan
106 Classroom 0 Yes 704 16 16 House Fan
107 Classroom 0 437 9 0 House Fan
108 Classroom 0 667 15 0 House Fan
109 Classroom 0 667 15 0 House Fan
110 Classroom 0 Yes 667 15 15 House Fan
111 Classroom 0 Yes 667 15 15 House Fan
212 Classroom 0 Yes 713 16 16 House Fan
213 Classroom 0 Yes 837 19 19 House Fan
215 IMC 0 Yes 1,536 34 34 House Fan
216 Classroom 0 Yes 736 16 16 House Fan
217 Classroom 0 Yes 736 16 16 House Fan
218 Classroom 0 Yes 713 16 16 House Fan
219 Classroom 0 696 15 0 House Fan
220 Classroom 0 696 15 0 House Fan
221 Classroom 0 696 15 0 House Fan
222 Computer Lab 0 720 16 0 House Fan
323 Classroom  0 713 16 0 House Fan
324 Classroom 0 713 16 0 House Fan
325 Classroom 0 713 16 0 House Fan
326 Classroom 0 736 16 0 House Fan
327 Classroom 0 713 16 0 House Fan
328 Classroom 0 768 17 0 House Fan
329 Classroom  0 696 15 0 House Fan
330 Classroom 0 696 15 0 House Fan
331 Classroom 0 720 16 0 House Fan
332 Classroom 0 720 16 0 House Fan
333 Classroom 0 696 15 0 House Fan
- Boy's Gang Bathrrom 0 620 14 0 N/A
- Caferteria 0 Yes 2,240 50 50 House Fan
- Counselor's Office 0 180 4 0 House Fan
- Girls Gang Bathrrom 0 620 14 0 N/A
- Main Office 0 Yes 361 8 8 House Fan
- Nurse 0 Yes 391 8 8 House Fan
- Principle's Office 0 276 6 0 House Fan
- Teachers' Lounge 0 391 8 0 House Fan
Sheet Last Modified: 03-24-2021        
School:  Eliza B. Kirkbride Elementary-Middle    
       
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 - 0 Yes 805 18 18 House Fan
102 - 0 690 15 0 House Fan
103 - 0 Yes 704 16 16 House Fan
104 - 0 Yes 690 15 15 House Fan
106 - 0 Yes 690 15 15 House Fan
107 - 0 Yes 660 15 15 House Fan
108 - 0 Yes 660 15 15 House Fan
109 - 0 Yes 690 15 15 House Fan
110 - 0 Yes 841 19 19 House Fan
201 - 0 Yes 814 18 18 House Fan
202 - 0 660 15 0 House Fan
203 - 0 Yes 704 16 16 House Fan
204 - 0 660 15 0 House Fan
205 - 0 Yes 660 15 15 House Fan
208 - 0 Yes 638 14 14 House Fan
209 - 0 638 14 0 House Fan
210 - 0 Yes 841 19 19 House Fan
211 - 0 Yes 660 15 15 House Fan
212 - 0 638 14 0 House Fan
301 - 0 851 19 0 House Fan
302 - 0 660 15 0 House Fan
303 - 0 704 16 0 House Fan
304 - 0 690 15 0 House Fan
305/306 - 0 1,357 30 0 House Fan
307 - 0 690 15 0 House Fan
308 - 0 690 15 0 House Fan
309 - 0 690 15 0 House Fan
310 - 0 841 19 0 House Fan
311 - 0 660 15 0 House Fan
312 - 0 690 15 0 House Fan
- Art  0 696 15 0 House Fan
- Counselor Suite 0 Yes 660 15 15 House Fan
- Gym 0 Yes 3,680 83 83 House Fan
- Library 0 Yes 1,380 31 31 House Fan
- Lunchroom1 0 Yes 690 15 15 House Fan
- Lunchroom2 0 Yes 1,100 25 25 House Fan
- Main Office 0 Yes 322 7 7 House Fan
- Nurse Office 0 Yes 96 2 2 House Fan
- Principal Office 0 Yes 240 5 5 House Fan
- Teacher Lounge/BE office 0 Yes 960 21 21 House Fan
Sheet Last Modified: 04-20-2021          
School:  John Hancock Demonstration Middle School @ General J Harry LaBrum Campus
  LaBrum Building LaBrum Retest        
Vendor: Devine Brothers        
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
102 Classroom 391 26 875 19 19 UV
102A Classroom 230 15 578 13 13 UV
103 Classroom 0 0 Yes 910 20 20 UV
104 Classroom 622 41 612 13 13 UV
105 Classroom 150 10 Yes 1152 26 26 UV
106 Classroom 320 21 342 7 7 UV
107 Classroom 221 14 Yes 1044 23 23 UV
201 Classroom 362 24 864 19 19 UV
202 Classroom 267 17 782 17 17 UV
203 Classroom 245 16 Yes 884 20 20 UV
204 Classroom 240 16 Yes 1116 25 25 UV
205 Classroom 311 20 900 20 20 UV
206 Classroom 583 38 858 19 19 UV
207 Classroom 340 22 840 19 19 UV
208 Classroom 462 30 816 18 18 UV
209 Classroom 410 27 720 16 16 UV
210 Classroom 327 21 888 20 20 UV
212 Classroom 390 26 875 19 19 UV
213 Classroom 336 22 864 19 19 UV
214 Classroom 366 24 828 18 18 UV
- Admin   0 0 Yes 286 6 6 UV
- Cafeteria 450 30 2765 62 30 UV
- Gym 0 0 5248 119 0
- Library 538 35 2016 45 35 UV
- Nurse's Room 0 0 Yes 550 12 12 UV
Sheet Last Modified: 04-27-2021      
School:  Robert E. Lamberton Elementary School                
School:  Robert E. Lamberton Elementary- Little School House
School:  Robert E. Lamberton Elementary- Little School House- Part 2
Vendor: Devine Brothers  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
1A Music Room 261.0 17 506 11 11 UV
1B Classroom 0 0 Yes 720 16 16 UV
2A Classroom 264.0 17 504 11 11 UV
4 Classroom 159.0 10 Yes 2024 46 46 UV
5A Classroom 0.0 0 Yes 600 13 13 UV
6 Classroom 0.0 0 Yes 625 14 14 UV
7 Classroom 0 Yes 1206 27 27 UV
101 Classroom 457.0 30 506 11 11 UV
102 Classroom 348 23 1012 23 23 UV
103 Classroom 466 31 989 22 22 UV
104 Classroom 335 22 Yes 1012 23 23 UV
105 Classroom 277 18 Yes 989 22 22 UV
106 Classroom 198 13 Yes 1012 23 23 UV
107 Classroom 406 27 1012 23 23 UV
108 Classroom 271 18 667 15 15 UV
109 Classroom 351 23 1012 23 23 UV
110 Classroom 420 28 989 22 22 UV
111 Classroom 338 22 989 22 22 UV
112 Classroom 0 0 Yes 989 22 22 UV
113 Classroom 280 18 575 13 13 UV
114 Classroom 271 18 Yes 874 19 19 UV
115 Classroom 278 18 Yes 874 19 19 UV
116 Classroom 387 25 874 19 19 UV
117 Classroom 176 11 Yes 874 19 19 UV
118 Classroom 243 16 Yes 1012 23 23 UV
119 Assitant Principal 0 Yes 361 8 8
120A Tescher's Lounge 0 Yes 377 8 8
120 Nurse 0 501 11 0
121 Special Education 0 Yes 531 12 12
201 Classroom 320 21 Yes 989 22 22 UV
202 Classroom 0 0 Yes 667 15 15 UV
203 Classroom 418 27 989 22 22 UV
204 Classroom 511 34 1012 23 23 UV
205 Classroom 560 37 1012 23 23 UV
206 Classroom 770 51 1012 23 23 UV
207 Classroom 0 0 Yes 1012 23 23 UV
208 Classroom 246 16 Yes 989 22 22 UV
209 Classroom 446 29 1012 23 23 UV
210A Classroom 233 15 504 11 11 UV
210B Classroom 0 0 Yes 504 11 11 UV
215 Classroom 0 0 Yes 874 19 19 UV
216 Classroom 0 0 Yes 874 19 19 UV
217 Classroom 220 14 Yes 874 19 19 UV
218 Classroom 359 23 874 19 19 UV
220 Classroom 232 15 Yes 1012 23 23 UV
221 Classroom 441 29 1058 24 24 UV
- Principal 0 Yes 387 8 8
- Main Office 0 Yes 784 17 17
- Auditorium 4,864.00 324 5832 132 132 AHU
Lamberton LSH
15 Classroom 313.0 20 Yes 928 21 21 AHU
16 Classroom 299.0 19 Yes 928 21 21 AHU
17 Classroom 317.0 21 928 21 21 AHU
18 Classroom 329.0 21 928 21 21 AHU
19 Classroom 291.0 19 Yes 928 21 21 AHU
20 Classroom 295.0 19 Yes 928 21 21 AHU
21 Classroom 316.0 21 928 21 21 AHU
22 Classroom 324.0 21 928 21 21 AHU
23 Classroom 314.0 20 Yes 928 21 21 AHU
24 Classroom 327.0 21 928 21 21 AHU
25 Classroom 287.0 19 Yes 928 21 21 AHU
26 Classroom 303.0 20 Yes 928 21 21 AHU
- Main Office 4.0 0 Yes 300 6 6 AHU
- Multi Purpose 1,539.0 102 1749 39 39 AHU
- Janitor 0.0 0 80 1 0 AHU
Sheet Last Modified: 04-16-2021    
School:  Lankenau Environmental Science High School
Vendor: Goldner
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
201 Classroom 407 27 585 13 13
205 Classroom 242 16 534 12 12
206 Classroom 183 12 529 12 12
207 Classroom 182 12 529 12 12
208 Classroom 178 11 522 11 11
210 Classroom 117 7 493 11 7
211 Classroom 120 8 475 10 8
212 Classroom 63 4 507 11 4
213 Classroom 63 4 531 12 4
214 Classroom 67 4 603 13 4
302 Classroom 84 5 586 13 5
303 Classroom 87.00 5 589 13 5
304 Classroom 85 5 573 13 5
305 Classroom 73 4 613 13 4
307 Classroom 517 34 1146 26 26
308 308 412 27 879 19 19
308B 308B 38 2 350 7 2
309 Classroom 611 40 1120 25 25
- Auditorium storage 1 23 1 67 1 1
- Auditorium storage 2 22 1 109 2 1
- Botany / Storage area 198 13 3264 74 13
- Cafeteria 706 47 1326 30 30
- Cafeteria 2 (Small) 158 10 518 11 10
- Cafeteria 3 (Main) 662 44 1536 34 34
- Conference Room 55 3 254 5 3
- Counselors Office 241 16 700 15 15
- Dean's Office 54 3 280 6 3
- Gym 606 40 2089 47 40
- Lounge 141 9 409 9 9
- Main Office 166 11 605 13 11
- Music Assembly 1,020.00 68 2424 55 55
- Nurse's Office 44 2 247 5 2
- Principal's office 109 7 280 6 6
- Science Storage 60 4 355 8 4
202 - 0 585 13 13
203 - 0 527 11 11
204 - 0 535 12 13
209 - 0 535 12 13
- Roster Chair 0 156 3 3
306 - 0 900 20 20
Sheet Last Modified: 03-18-2021    
School:  Henry W. Lawton Elementary School
Vendor: Devine Brothers Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 956.0 63 990 22 22 UV
102 Classroom 407.0 27 990 22 22 UV
103 Classroom 547.0 36 730 16 16 UV
104 Classroom 327.0 21 796 18 18 UV
105 Classroom 464.0 30 730 16 16 UV
106 Classroom 432.0 28 796 18 18 UV
107 Classroom 376.0 25 730 16 16 UV
108 Classroom 641.0 42 676 15 15 UV
109 Classroom 519.0 34 730 16 16 UV
110 Classroom 699.0 46 676 15 15 UV
111 Classroom 685.0 45 720 16 16 UV
112 Classroom 929.0 61 930 21 21 UV
113 Classroom 742.0 49 720 16 16 UV
114 Classroom 705.0 47 930 21 21 UV
115 Classroom 712.0 47 720 16 16 UV
117 Classroom 671.0 44 720 16 16 UV
119 Classroom 713.0 47 720 16 16 UV
121 Classroom 571.0 38 720 16 16 UV
123 Classroom 400.0 26 720 16 16 UV
201 Classroom 411.0 27 816 18 18 UV
202 Classroom 658.0 43 816 18 18 UV
203 Classroom 455.0 30 816 18 18 UV
204 Classroom 790.0 52 816 18 18 UV
205 Classroom 802.0 53 816 18 18 UV
206 Classroom 611.0 40 816 18 18 UV
207 Classroom 814.0 54 720 16 16 UV
208 Classroom 320.0 21 816 18 18 UV
209 Classroom 653.0 43 720 16 16 UV
211 Classroom 707.0 47 720 16 16 UV
213 Classroom 649.0 43 720 16 16 UV
214 Classroom 289.0 19 540 12 12 UV
215 Classroom 730.0 48 720 16 16 UV
216 Classroom 332.0 22 768 17 17 UV
217 Classroom 364.0 24 720 16 16 UV
218 Classroom 716.0 47 676 15 15 UV
219 Classroom 672.0 44 720 16 16 UV
220 Classroom 639.0 42 676 15 15 UV
222 Classroom 683.0 45 540 12 12 UV
224 Classroom 633.0 42 720 16 16 UV
226 Classroom 1,102.0 73 540 12 12 UV
- Art (Large) 477.0 31 1258 28 28 UV
- Cafeteria 632.0 42 2310 52 42 AHU
- Computer 886.0 59 1440 32 32 UV
- IMC 426.0 28 2620 59 28 UV
- Main Office 232.0 15 275 6 6 UV
- Nurse's Office 283.0 18 363 8 8 UV
- Science (Large) 375.0 25 1088 24 24 UV
Sheet Last Modified: 04-26-2021    
School:  Henry C. Lea Elementary School
Vendor: Devine Chadwick Devine Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
L1 Classroom 166 11 696 15 11 UV
L3 Classroom 0 0 624 14 0 UV
L4 Classroom 191 12 696 15 12 UV
L5 Classroom 208 13 864 19 13 UV
L7 Classroom 247 16 768 17 16 UV
B2 Classroom 0 Yes 1457 33 33
101 Classroom 312 20 1225 27 20 UV
102 Classroom 319 21 1295 29 21 UV
103 Classroom 284 18 810 18 18 AHU
105 Classroom 287 19 840 19 19 AHU
106 Classroom 0 0 Yes 840 19 19 AHU
107 Classroom 289 19 840 19 19 AHU
108 Classroom 301 20 840 19 19 AHU
109 Classroom 295 19 840 19 19 AHU
110 Classroom 298 19 840 19 19 AHU
111 Classroom 289 19 840 19 19 AHU
125 Counselor's Office 0 Yes 126 2 2
127 Classroom 0 Yes 126 2 2
201 Classroom 0 0 Yes 1015 23 23 UV
202 Classroom 0 0 Yes 980 22 22 UV
203 Classroom 0 Yes 840 19 19 AHU
204 Classroom 0 Yes 840 19 19
204a Classroom 0 0 Yes 252 5 5 AHU
205 Classroom 0 0 Yes 810 18 18 AHU
206 Classroom 0 0 Yes 870 19 19 AHU
207 Classroom 0 0 Yes 840 19 19 AHU
208 Classroom 0 0 Yes 840 19 19 AHU
209 Classroom 0 0 Yes 840 19 19 AHU
210 Classroom 0 0 Yes 840 19 19 AHU
211 Classroom 0 0 Yes 840 19 19 AHU
212 Classroom 0 0 Yes 212 4 4 AHU
301/302 Library 380 25 Yes 5400 122 122 UV
303 Classroom 0 0 Yes 840 19 19 AHU
304 Classroom 0 0 Yes 690 15 15 AHU
304A Room 0 Yes 266 6 6
306 Classroom 0 0 Yes 840 19 19 AHU
307 Classroom 0 0 Yes 840 19 19 AHU
308 Classroom 0 0 Yes 840 19 19 AHU
309 Classroom 0 0 Yes 840 19 19 AHU
310 Classroom 0 0 Yes 840 19 19 AHU
311 Classroom 0 0 Yes 840 19 19 AHU
312 Classroom 0 0 Yes 840 19 19 AHU
313 Classroom 0 0 840 19 0 AHU
- Auditorium 0 0 2296 52 0 AHU
- Side Cafeteria 490 32 Yes 1800 40 40 AHU
- Front Cafeteria 352 23 Yes 1560 35 35 AHU
- Computer Lab 276 18 1456 33 18 AHU
- Corridor 156 10 650 14 10 UV
- Gym 0 0 Yes 3950 89 89 AHU
- Main Office 212 14 460 10 10 AHU
- Nurse's Bathroom 0 0 28 0 0 AHU
- Nurse's Office 0 Yes 168 3 3 AHU
- Nurse's Exam Room 0 88 2 0 AHU
- Office Bathroom 0 0 25 0 0 AHU
- Principal's Office 0 0 Yes 160 3 3 UV
Sheet Last Modified: 04-22-2021          
School:  Amy Northwest @ Levering Middle School      
         
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 750 17 0
103 Classroom 0 Yes 725 16 16
106 Nurse Office 0 Yes 668 15 15
107 Classroom 0 666 15 0
109 IMC 0 Yes 1,457 33 33
203 Classroom 0 Yes 675 15 15
204 Classroom 0 Yes 683 15 15
205 Classroom 0 Yes 663 15 15
206 Classroom 0 691 15 0
207 Classroom 0 672 15 0
209 Classroom 0 Yes 685 15 15
210 Classroom 0 677 15 0
303/304 Classroom 0 Yes 1,253 28 28
305 Classroom 0 Yes 675 15 15
306 Classroom 0 Yes 692 15 15
307 Classroom 0 Yes 670 15 15
310 Classroom 0 1,065 24 0
Annex 1 Classroom 0 Yes 733 16 16
Annex 2 Classroom 0 Yes 709 16 16
Annex 3 Classroom 0 730 16 0
Annex 4 Classroom 0 Yes 707 16 16
Annex 5 Classroom 0 Yes 723 16 16
Sheet Last Modified: 04-01-2021    
School:  Abraham Lincoln High School
Vendor: Devine Brothers EMCOR Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
2 Room 2 Office 93.0 6 576 13 6 AHU #7
3 Room 3 Storage 99.0 6 576 13 6 AHU #8
4 Room 4 Electrical 103.0 6 576 13 6 AHU #9
5 Room 5 Kitchen 461.0 30 576 13 13 AHU #10
6 Child Care 1116 74 576 13 13 AHU #11
8 Child Care 2029 135 1665 37 37 AHU #12
100 Classroom 760 50 363 8 8 UV1+UV2+AHU-2
100A Classroom 615 41 0 0 UV+AHU-2
101 Classroom 1715 114 1247 28 28 UV1+UV2+AHU-2
102 Classroom 1244 82 130 2 2 UV+AHU-2
102A Office 25 1 140 3 1 AHU-2
102B Office 35 2 107 2 2 AHU-2
103 Classroom 1636 109 1410 32 32 UV1+UV2+AHU-2
104 Classroom 1067 71 806 18 18 UV1+UV2+AHU-2
105 Classroom 1322 88 1140 25 25 UV1+UV2+AHU-2
106 Classroom 1182 78 957 21 21 UV1+UV2+AHU-2
107 Classroom 1894 126 1426 32 32 UV1+UV2+AHU-2
107A Storage Room 300 20 0 0 AHU-1
108 Classroom 1212 80 899 20 20 UV1+UV2+AHU-2
109 109 OFFICE 144 9 99 2 2 AHU-2 / FC
110 Classroom 1159 77 868 19 19 UV1+UV2+AHU-1
111 Classroom 1827 121 1426 32 32 UV1+UV2+AHU-1
112 Classroom 990 66 868 19 19 UV1+UV2+AHU-1
114 Classroom 1114 74 837 19 19 UV1+UV2+AHU-1
116 Classroom 663 44 896 20 20 UV1+UV2+AHU-1
118 Classroom 932 62 1748 39 39 UV1+UV2+AHU-1
120 Classroom 1141 76 864 19 19 UV1+UV2+AHU-1
121 Classroom 1025 68 945 21 21 UV1+UV2+AHU-1
122 Classroom 941 62 837 19 19 UV1+UV2+AHU-1
123 Classroom 1848 123 2208 50 50 UV1+UV2+UV1+UV2+AHU-1
124 Classroom 865 57 837 19 19 UV1+UV2+AHU-1
125 Classroom 984 65 888 20 20 UV1+UV2+AHU-1
126 Classroom 843 56 837 19 19 UV1+UV2+AHU-1
128 Classroom 598 39 837 19 19 UV1+UV2+AHU-1
129 Classroom 740 49 890 20 20 UV1+UV2+AHU-1
130 Security 0 0 108 2 0 AHU-4
131 Police 0 0 180 4 0 AHU-4
132 Classroom 728 48 0 0 UV1+UV2+UV3+UV4
133a book room 0 0 0 0 AHU-4
135 Classroom 0 0 840 19 0 UV1+UV2
136 office 0 0 140 3 0 AHU-4
136a storage 0 0 0 0 AHU-4
137 storage 0 0 0 0 AHU-4
137a storage 0 0 0 0 AHU-4
139 office 0 0 74.75 1 0 AHU-4
140 Main Office and waiting 0 0 338 7 0 AHU-4
141 Office 0 0 0 0 AHU-4
142 Office 0 0 0 0 AHU-4
143 Office 0 0 99 2 0 AHU-4
144 Office 0 0 105 2 0 AHU-4
145 Office 0 0 110 2 0 AHU-4
146 Work Room 0 0 636 14 0 AHU-4
147 Conference 0 0 192 4 0 AHU-4
147A records 0 0 300 6 0 AHU-4
149 Health Suite 0 0 495 11 0 AHU-4
149a Exam 0 0 188 4 0 AHU-4
149b Exam 0 0 197 4 0 AHU-4
149c Office 0 0 197 4 0 AHU-4
149D Office 0 0 109 2 0 AHU-4
149E Meditation 0 0 209 4 0 AHU-4
150 office 0 0 117 2 0 AHU-4
151 copy center 0 0 418 9 0 AHU-4
154 office 0 0 117 2 0 AHU-4
155 office 0 0 121 2 0 AHU-4
156 work room 0 0 875 19 0 AHU-4
157 Records 0 0 96 2 0 AHU-4
158 Roster Room 0 0 143 3 0 AHU-4
159 Office 0 0 96 2 0 AHU-4
160 Classroom 1346 89 1428 32 32 UV1+UV2+AHU-3
160's Men's Staff Restroom 740 49 0 0 AHU-3
160's Women's Staff Restroom 685 45 0 0 AHU-3
160A Science Prep 423 28 891 20 20 AHU-3
161 Classroom 829 55 891 20 20 UV1+UV2+AHU-3
162 Classroom 1327 88 688 15 15 UV1+UV2+AHU-3
163 Classroom 895 59 868 19 19 UV1+UV2+AHU-3
164 Classroom 1334 88 1419 32 32 UV1+UV2+AHU-3
164a Science Prep 44 2 0 0 AHU-3
165 Classroom 942 62 868 19 19 UV1+UV2+AHU-3
166 Classroom 1071 71 1155 26 26 UV1+UV2+AHU-3
167 Classroom 458 30 918 20 20 UV1+UV2+AHU-3
168 Classroom 1150 76 868 19 19 UV1+UV2+AHU-3
169 Classroom 684 45 952 21 21 UV1+UV2+AHU-3
170 Classroom 787 52 891 20 20 UV+UV+AHU-3
171 Classroom 1006 67 918 20 20 UV1+UV2+AHU-3
172 Classroom 994 66 891 20 20 UV1+UV2+AHU-3
173 Classroom 565 37 891 20 20 AHU-3
174 Classroom 736 49 896 20 20 UV1+UV2+AHU-3
175 Classroom 1415 94 891 20 20 UV1+UV2+AHU-3
176 Classroom 903 60 800 18 18 UV1+UV2+AHU-3
177 Classroom 867 57 918 20 20 UV1+UV2+AHU-3
190 Music Classroom 1656 110 1395 31 31 AHU-8
190 Office 82 5 225 5 5 AHU-8
190 Storage 52 3 1716 39 3 AHU-8
190A Classroom 315 21 90 2 2 AHU-8
190D Classroom 166 11 623 14 11 AHU-8
190E Classroom 191 12 336 7 7 AHU-8
191 Music Classroom 1393 92 2100 47 47 AHU-8
191A Classroom 68 4 56 1 1 AHU-8
191B Classroom 72 4 90 2 2 AHU-8
191C Classroom 83 5 90 2 2 AHU-8
192 Classroom 998 66 1189 27 27 AHU-8
200 Classroom 1117 74 1240 28 28 UV1+UV2+AHU-2
201 Classroom 1325 88 1485 33 33 UV1+UV2+AHU-2
201A Science Prep 255 17 1486 33 17 AHU-2
202 Classroom 1325 88 2270 51 51 UV1+UV2+UV3+AHU-2
202A Office 44 2 99 2 2 AHU-2
203 Classroom 1339 89 1575 35 35 UV1+UV2+AHU-2
204 Classroom 403 26 806 18 18 UV1+UV2+AHU-2
205 Classroom 652 43 1395 31 31 UV1+UV2+AHU-2
206 Office Suite toilet 0 1254 28 0 AHU-2
207 Classroom 1006 67 891 20 20 UV1+UV2+AHU-2
208 Classroom 759 50 1152 26 26 UV1+UV2+AHU-2
209 Classroom 419 27 864 19 19 UV1+UV2+AHU-2
210 Classroom 614 40 837 19 19 UV1+UV2+AHU-2
211 Classroom 994 66 390 8 8 UV1+UV2+AHU-1
212 Classroom 615 41 858 19 19 UV1+UV2+AHU-2
213 Classroom 995 66 891 20 20 UV1+UV2+AHU-1
214 Classroom 625 41 924 21 21 UV1+UV2+AHU-1
216 Classroom 564 37 918 20 20 UV1+UV2+AHU-1
218 Classroom 729 48 837 19 19 UV1+UV2+AHU-1
220 Classroom 1242 82 1395 31 31 UV1+UV2+AHU-1
221 Classroom 653 43 924 21 21 UV1+UV2+AHU-1
222 Classroom 909 60 891 20 20 UV1+UV2+AHU-1
223 Classroom 848 56 864 19 19 UV1+UV2+AHU-1
224 Classroom 2035 135 1972 44 44 UV1+UV2+UV3+UV4+AHU-1
224A Office 96 6 121 2 2 AHU-1
225 Classroom 639 42 918 20 20 UV1+UV2+AHU-1
226 Classroom 1282 85 1870 42 42 UV1+UV2+UV3+UV4+AHU-1
226A Office 41 2 123 2 2 AHU-1
227 Classroom 825 55 891 20 20 UV1+UV2+AHU-1
228 Classroom 551 36 924 21 21 UV1+UV2+AHU-1
229 Classroom 800 53 878 19 19 UV1+UV2+AHU-1
- 2nd floor Corridor 1498 99 0 0 AHU-1
- Gym 40145 2676 18327 416 416 AHU-9+AHU-10
- 2nd Floor B Corridor 543 36 0 0 AHU-2
- 2nd Floor Staff toilet 0 0 0 AHU-2
- Auditorium 16961 1130 6745 153 153 AHU-6
- Small Gym 0 0 6438 146 0 AHU-11
- Weight Room 0 0 2450 55 0 AHU-12
- Counselor Center 0 0 0 0 AHU-4
- Child Care- Hallway 240 16 0 0 AHU #13
- Child Care- Kitchen 47 3 330 7 3 AHU-7
- Child Care- Lending Library 96 6 Yes 1184 26 26 AHU-7
- Library/IMC 1522 101 8640 196 101 AHU #14
- Child Care Office 9 0 99 2 0 AHU-7
- Admin 140's Area Corridor 0 0 375 8 0 AHU-4
- Gym Office 0 343 7 0
- Gym office 2  0 280 6 0
- Gym office 3  0 260 5 0
Sheet Last Modified: 04-12-2021    
School:  Lingelbach Elementary School
Vendor: Devine Brothers Part 2 Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 227.0 15 968 22 15 UV
102 Classroom 477.0 31 968 22 22 UV
103 Classroom 219.0 14 889 20 14 UV
104 Classroom 0.0 0 963 21 0 UV
105 Classroom 268.0 17 941 21 17 UV
106 Classroom 293.0 19 971 22 19 UV
200 Classroom 444.0 29 1394 31 29 UV
200A Classroom 675.0 45 1235 28 28 UV
201 Classroom 514.0 34 969 22 22 UV
202 Classroom 280.0 18 969 22 18 UV
203 Classroom 278.0 18 971 22 18 UV
204 Classroom 290.0 19 971 22 19 UV
205 Classroom 336.0 22 955 21 21 UV
206 Classroom 278.0 18 969 22 18 UV
301 Classroom 285.0 19 940 21 19 UV
302 Classroom 795.0 53 937 21 21 UV
303 Classroom 837.0 55 933 21 21 UV
303A Classroom 357.0 23 463 10 10 UV
304 Classroom 406.0 27 464 10 10 UV
305 Classroom 395.0 26 967 21 21 UV
306 Classroom 906.0 60 944 21 21 UV
- Main Office 0 Yes 332 7 7
- Principals Office 0 Yes 262 5 5
- Nurses Office 0 Yes 269 6 6
- Auditorium 841.0 56 2847 64 56 AHU
- Gym/Cafeteria 1,451.0 96 2340 53 53 AHU
- North Stairwell 0.0 0 168 3 0 UV
- South Stairwell 0.0 0 168 3 0 UV
- Library 855.0 57 2312 52 52 UV
Sheet Last Modified: 04-05-2021    
School:  Alain Locke Elementary School
Vendor: Devine Brothers Devine Brothers Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Auditorium 2700 180 3658 83 83 AHU
- Gym/Cafeteria 2014 134 4464 101 101 AHU
- Library 585 39 1352 30 30 UV
- Main Office 425 28 1213 27 27 UV
- Principals Office 0 0 Yes 384 8 8 UV
100 Classroom 421 28 840 19 19 UV
101 Classroom 454 30 840 19 19 UV
102 Classroom 425 28 864 19 19 UV
103 Classroom 318 21 432 9 9 UV
104 Classroom 405 27 744 16 16 UV
105 Classroom 453 30 840 19 19 UV
107 Classroom 435 29 1064 24 24 UV
108A Office A Library 0 Yes 156 3 3
108B Office B Library 0 Yes 156 3 3
109 Classroom 428 28 864 19 19 UV
111 Classroom 394 26 840 19 19 UV
112 Classroom 330 22 840 19 19 UV
113 Classroom 416 27 980 22 22 UV
115 Classroom 393 26 1248 28 26 UV
116A Counselor Office 0 Yes 132 3 3
116B COVID Quarantine 0 Yes 132 3 3
117 Classroom 321 21 1440 32 21 UV
200 Classroom 592 39 875 19 19 UV
201 Classroom 340 22 864 19 19 UV
202 Classroom 341 22 875 19 19 UV
203 Classroom 485 32 864 19 19 UV
204 Classroom 279 18 875 19 18 UV
205 Classroom 295 19 864 19 19 UV
207A Classroom 0 0 Yes 168 3 3 UV
207B Classroom 300 20 336 7 7 UV
208 Classroom 349 23 1225 27 23 UV
209 Classroom 348 23 864 19 19 UV
210 Classroom 295 19 480 10 10 UV
211 Classroom 360 24 864 19 19 UV
212 Classroom 332 22 840 19 19 UV
213 Classroom 297 19 875 19 19 UV
300 Classroom 419 27 840 19 19 UV
301 Classroom 416 27 840 19 19 UV
302 Classroom 375 25 840 19 19 UV
303 Classroom 395 26 840 19 19 UV
304 Classroom 398 26 840 19 19 UV
305 Classroom 411 27 840 19 19 UV
307A Office 205 13 336 7 7 UV
307B Office 0 0 Yes 168 3 3 UV
308 Classroom 383 25 864 19 19 UV
309 Classroom 365 24 840 19 19 UV
310 Classroom 325 21 875 19 19 UV
311 Classroom 309 20 840 19 19 UV
312 Classroom 419 27 840 19 19 UV
313 Classroom 346 23 840 19 19 UV
- Nurses office 0 Yes 352 8 8 UV
Sheet Last Modified: 04-08-2021    
School:  William Loesche Elementary School
Vendor: Devine Brothers Devine Brothers Retest
  Devine Brothers 2nd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 286 19 840 19 19 UV
101 Classroom 282 18 840 19 18 UV
102 Classroom 82.0 5 Yes 784 17 17 UV
103 Classroom 288 19 840 19 19 UV
104 Classroom 0.0 0 840 19 0 UV
105 Classroom 300 20 840 19 19 UV
107 Classroom 288 19 840 19 19 UV
108 Classroom 213.0 14 Yes 1122 25 25 UV
109 Classroom 185.0 12 840 19 12 UV
110 Classroom 156.0 10 Yes 840 19 19 UV
111 Classroom 190.0 12 Yes 882 20 20 UV
112 Classroom 285 19 729 16 16 UV
200 Classroom 258 17 840 19 17 UV
201 Classroom 292 19 840 19 19 UV
202 Classroom 283 18 840 19 18 UV
203 Classroom 158.0 10 Yes 840 19 19 UV
204 Classroom 262 17 840 19 17 UV
205 Classroom 205.0 13 Yes 840 19 19 UV
206 Classroom 153.0 10 476 10 10 UV
207 Classroom 297 19 840 19 19 UV
208 Classroom 210.0 14 840 19 14 UV
208A Classroom 150.0 10 252 5 5 UV
209 Classroom 184.0 12 Yes 840 19 19 UV
210 Classroom 193.0 12 780 17 12 UV
211 Classroom 142.0 9 Yes 783 17 17 UV
212 Classroom 267 17 840 19 17 UV
214 Classroom 280 18 1212 27 18 UV
215 Classroom 268 17 1232 28 17 UV
216 Classroom 415.0 27 756 17 17 UV
217 Classroom 276 18 841 19 18 UV
218 Classroom 144.0 9 Yes 840 19 19 UV
219 Classroom 106.0 7 Yes 840 19 19 UV
220 Classroom 246.0 16 870 19 16 UV
221 Classroom 140.0 9 870 19 9 UV
222 Classroom 106.0 7 840 19 7 UV
223 Classroom 175.0 11 840 19 11 UV
224 Classroom 94.0 6 840 19 6 UV
A-1 Classroom 242 16 884 20 16 UV
A-2 Classroom 254 16 884 20 16 UV
A-3 Classroom 298 19 884 20 19 UV
A-4 Classroom 281 18 884 20 18 UV
- A-wing Mech. Rm 0.0 0 358 8 0 UV
- Auditorium 0.0 0 3600 81 0 AHU
B-1 Classroom 314 20 806 18 18 UV
B-2 Classroom 311 20 806 18 18 UV
B-3 Classroom 300 20 806 18 18 UV
B-4 Classroom 313 20 806 18 18 UV
B-5 Classroom 287 19 806 18 18 UV
B-6 Classroom 297 19 905 20 19 UV
B-7 Classroom 285 19 905 20 19 UV
B-8 Classroom 304 20 905 20 20 UV
B-9 Classroom 282 18 905 20 18 UV
- Backstage 0.0 0 180 4 0 UV
- Backstage Dressing Rm. 172.0 11 252 5 5 UV
- Cafeteria 0.0 0 Yes 5540 125 125 AHU
- GYM 0.0 0 4496 102 0 AHU
- Library 0.0 0 1131 25 0 UV
- Main Office 292.0 19 992 22 19 UV
- Nurse's Office 94.0 6 706 16 6 UV
- Principal's Office 148.0 9 308 7 7 UV 
Sheet Last Modified: 03-24-2021        
School:  James Logan Elementary-Middle School House Fan Abated
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B-1 Classroom 1,228.0 81 889 20 20 House Fan
B-2 Classroom 975.0 65 737 16 16 House Fan
B-3 Classroom 1,131.0 75 1017 23 23 House Fan
101 Classroom 539.0 35 729 16 16 House Fan
102 Classroom 578.0 38 732 16 16 House Fan
103 Classroom 593.0 39 724 16 16 House Fan
104 Classroom 674.0 44 676 15 15 House Fan
104A Office 0.0 0 177 4 0 House Fan
105 Teacher's Lounge 617.0 41 650 14 14 House Fan
106 Classroom 621.0 41 726 16 16 House Fan
107 Classroom 376.0 25 722 16 16 House Fan
108 Classroom 849.0 56 717 16 16 House Fan
201 IMC 509.0 33 639 14 14 House Fan
202 IMC 632.0 42 639 14 14 House Fan
203 Classroom 551.0 36 720 16 16 House Fan
204 Office Storage 0.0 0 201 4 0 House Fan
205 Classroom 519.0 34 718 16 16 House Fan
205A Office 0.0 0 164 3 0 House Fan
206 Classroom 715.0 47 735 16 16 House Fan
206A Counselor 0.0 0 231 5 0 House Fan
207 Classroom 394.0 26 723 16 16 House Fan
208 Classroom 423.0 28 724 16 16 House Fan
209 Classroom 575.0 38 725 16 16 House Fan
209A Classroom 0.0 0 260 5 0 House Fan
301 Classroom 522.0 34 679 15 15 House Fan
302 Classroom 549.0 36 679 15 15 House Fan
303 Classroom 458.0 30 724 16 16 House Fan
304 Classroom 481.0 32 714 16 16 House Fan
305 Classroom 347.0 23 890 20 20 House Fan
306 Classroom 381.0 25 750 17 17 House Fan
307 Classroom 312.0 20 992 22 20 House Fan
308 Classroom 466.0 31 751 17 17 House Fan
309 Classroom 508.0 33 992 22 22 House Fan
310 Classroom 477.0 31 720 16 16 House Fan
311 Classroom 409.0 27 703 15 15 House Fan
312 Classroom 491.0 32 730 16 16 House Fan
313 Classroom 570.0 38 721 16 16 House Fan
- Auditorium 2,427.0 161 3685 83 83 House Fan
- Boys' Bathroom 125.0 8 561 12 8 N/A
- Girls' Bathroom 73.0 4 547 12 4 N/A
- Cafeteria 1,258.0 83 1726 39 39 House Fan
- Speech Classroom 0.0 0 Yes 192 4 4 House Fan
- Gym 0.0 0 Yes 3970 90 90 N/A
- Nurse's Office 0.0 0 Yes 220 5 5 House Fan
- IMC Office 0.0 0 158 3 0 House Fan
- Main Office 0.0 0 Yes 333 7 7 House Fan
- Principal's Office 0.0 0 Yes 342 7 7 House Fan
Sheet Last Modified: 03-26-2021    
School:  W.C. Longstreth Elementary School
Vendor: EMCOR Fluidics Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100D Faculty Dining 96.0 6 625 14 6 AHU-6
102 Main Office 110.0 7 646 14 7 AHU-6
102C Principal Office 77.0 5 225 5 5 AHU-6
102D Comference Room 72.0 4 198 4 4 AHU-6
103 Classroom 141.0 9 704 16 9 AHU-1
105 Classroom 206.0 13 609 13 13 AHU-1
106 Art Room 610.0 40 1333 30 30 AHU-2
107 Classroom 468.0 31 1320 30 30 AHU-1
109 Classroom 469.0 31 1276 29 29 AHU-1
110 Nurses Suite 45.0 3 180 4 3 AHU-6
110C Nurses Office 102.0 6 132 3 3 AHU-6
110D Audio Rm 101.0 6 132 3 3 AHU-6
110E Audio Rm 78.0 5 48 1 1 AHU-6
111 Classroom 487.0 32 1232 28 28 AHU-1
112A Building Engineers Office 90.0 6 88 2 2 AHU-6
113 Classroom 361.0 24 1364 31 24 AHU-1
200 Library 715.0 47 2859 64 47 AHU-5
200A Computer Lab 119.0 7 704 16 7 AHU-5
200B Consortium 67.0 4 552 12 4 AHU-5
201 Classroom 403.0 26 818 18 18 AHU-1
202 Classroom 360.0 24 510 11 11 AHU-2
203 Classroom 321.0 21 544 12 12 AHU-1
204 Classroom 206.0 13 Yes 510 11 11 AHU-2
205 Classroom 273.0 18 544 12 12 AHU-1
206 Classroom 364.0 24 510 11 11 AHU-2
207 Classroom 419.0 27 544 12 12 AHU-1
208 Classroom 309.0 20 510 11 11 AHU-2
209 Classroom 417.0 27 544 12 12 AHU-1
210 Classroom 276.0 18 510 11 11 AHU-2
211 Classroom 88.0 5 576 13 5 AHU-1
212 Classroom 304.0 20 765 17 17 AHU-2
213 Classroom 303.0 20 810 18 18 AHU-1
214 Classroom - WEIGHT ROOM 669.0 44 1204 27 27 AHU-2
215 Classroom 141.0 9 285 6 6 AHU-1
219 Classroom 175.0 11 220 5 5 AHU-1
220 Classroom 61.0 4 612 13 4 AHU-2
301 Classroom 311.0 20 595 13 13 AHU-1
303 Classroom 323.0 21 561 12 12 AHU-1
304 Classroom 220.0 14 570 12 12 AHU-2
305 Classroom 316.0 21 577 13 13 AHU-1
306 Classroom 462.0 30 510 11 11 AHU-2
307 Classroom 331.0 22 577 13 13 AHU-1
308 Classroom 327.0 21 510 11 11 AHU-2
309 Classroom 356.0 23 594 13 13 AHU-1
310 Classroom 320.0 21 527 11 11 AHU-2
311 Classroom 340.0 22 576 13 13 AHU-1
312 Classroom 332.0 22 544 12 12 AHU-2
313 Classroom 422.0 28 840 19 19 AHU-1
314 Classroom 577.0 38 1290 29 29 AHU-2
315 Classroom 145.0 9 280 6 6 AHU-1
319 Classroom 129.0 8 220 5 5 AHU-1
320 Classroom 171.0 11 210 4 4 AHU-2
- Auditorium 1,337.0 89 3540 80 80 AHU-3
- Cafeteria 2,211.0 147 3658 83 83 AHU-4
- Diagnostic Center 213.0 14 306 6 6 AHU-6
- Main Office Admin 82.0 5 110 2 2 AHU-6
- Main Storage Room 27.0 1 192 4 1 AHU-6
- Nurses Suite Laundry 115.0 7 372 8 7 AHU-6
- Gym 0 0 4720 107 0 AHU 1 and 2
Sheet Last Modified: 03-26-2021    
School:  James R. Lowell Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B010A Boys Bathroom 725 48 667 15 15 N/A
B10 Music 0 0 925 21 0 N/A
B11 Classroom 346 23 695 15 15 House Fan
B12 Girls Bathroom 305 20 695 15 15 House Fan
B8 Classroom 175 11 576 13 11 House Fan 
B9 Classroom 388 25 667 15 15 House Fan 
100 Classroom 0 0 240 5 0 House Fan 
101 Classroom 285 19 566 12 12 House Fan 
102 Classroom 327 21 559 12 12 House Fan 
103 Classroom 325 21 100 2 2 House Fan 
104 Classroom 102 6 640 14 6 House Fan 
105 Classroom 593 39 654 14 14 House Fan 
106 Classroom 399 26 566 12 12 House Fan
107 Classroom 0 0 667 15 0 House Fan
108 Classroom 154 10 650 14 10 House Fan
109 Classroom 304 20 602 13 13 House Fan
110 Classroom 0 0 207 4 0 House Fan
111 Counselor 0 154 3 0
200 Classroom 0 0 240 5 0 House Fan
201 Classroom 300 20 654 14 14 House Fan
202 Computer Room  0 810 18 0
203 Classroom 647 43 654 14 14 House Fan
204 Classroom 457 30 650 14 14 House Fan
205 Classroom 531 35 650 14 14 House Fan
206 Classroom 247 16 695 15 15 House Fan
207 Classroom 102 6 694 15 6 House Fan
207 Faculty Room 0 0 207 4 0 N/A
208 Classroom 200 13 695 15 13 House Fan
209 Classroom 139 9 650 14 9 House Fan
210 Classroom 275 18 560 12 12 House Fan
211 Classroom 0 0 420 9 0 House Fan
300 Classroom 0 0 240 5 0 House Fan
301A Classroom 132 8 566 12 8 House Fan
301B Classroom 139 9 300 6 6 House Fan
302 Classroom 145 9 240 5 5 House Fan
303 Classroom 318 21 666 15 15 House Fan
304 Classroom 387 25 610 13 13 House Fan
305 Classroom 432 28 620 14 14 House Fan
306 Classroom 249 16 650 14 14 House Fan
307 Classroom 325 21 650 14 14 House Fan
308 Classroom 322 21 650 14 14 House Fan
309 Classroom 262 17 654 14 14 House Fan
310 Classroom 203 13 636 14 13 House Fan
311 Classroom 0 0 221 5 0 House Fan
312 Classroom 0 0 273 6 0 House Fan
- Library 213 14 1,040 23 14 AHU
- Entrance Lobby 290 19 325 7 7 N/A
- Gym 0 0 4,368 99 0 AHU
- Music Rm 127 8 286 6 6 Unit Ventilator
S-11 Classroom 419 27 810 18 18 Unit Ventilator
S-12 Classroom 906 60 692 15 15 Unit Ventilator
S-13 Classroom 635 42 692 15 15 Unit Ventilator
S-14 Classroom 715 47 695 15 15 Unit Ventilator
S-15 Classroom 411 27 692 15 15 Unit Ventilator
S-16 Classroom 502 33 692 15 15 Unit Ventilator
S-17 Classroom 371 24 828 18 18 Unit Ventilator
S-18 Classroom 482 32 828 18 18 Unit Ventilator
S-19 Classroom 742 49 828 18 18 Unit Ventilator
S-21 Classroom 429 28 640 14 14 Unit Ventilator
S-22 Classroom 663 44 640 14 14 Unit Ventilator
S-23 Classroom 480 32 654 14 14 Unit Ventilator
S-24 Classroom 333 22 636 14 14 Unit Ventilator
S-25 Classroom 844 56 636 14 14 Unit Ventilator
S-26 Classroom 490 32 654 14 14 Unit Ventilator
S-27 Storage 393 26 610 13 13 Unit Ventilator
S-27 Classroom 266 17 610 13 13 Unit Ventilator
S-28 Classroom 450 30 610 13 13 Unit Ventilator
S-29 Classroom 260 17 610 13 13 Unit Ventilator
S-30 Teacher's Lounge 378 25 858 19 19 Unit Ventilator
S-31 Office 508 33 140 3 3 Unit Ventilator
- Main Office 0 338 7 0
- Principals Office 0 364 8 0
- Nurses Office 0 240 5 0
Sheet Last Modified: 04-27-2021      
School:  James R. Ludlow Elementary-Middle School
   
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
3 Art 0 667 15 0 House Fan
100B Home and School 0 121 2 0 House Fan
100C Counselor 0 195 4 0 House Fan
101 Classroom   0 Yes 690 15 15 House Fan
102 Classroom   0 Yes 690 15 15 House Fan
103 Classroom   0 Yes 672 15 15 House Fan
104 Classroom   0 Yes 638 14 14 House Fan
105 Classroom   0 Yes 667 15 15 House Fan
106 Classroom   0 Yes 690 15 15 House Fan
107 Classroom   0 920 20 0 House Fan
108 Classroom   0 Yes 638 14 14 House Fan
109 Classroom   0 Yes 841 19 19 House Fan
110 Counselor 0 128 2 0 House Fan
200 Classroom   0 Yes 552 12 12 House Fan
201 Classroom   0 Yes 690 15 15 House Fan
202 Classroom   0 Yes 660 15 15 House Fan
203 Classroom   0 Yes 704 16 16 House Fan
204 Classroom   0 690 15 0 House Fan
207 Classroom 0 Yes 690 15 15 House Fan
208 Classroom 0 Yes 667 15 15
209 Classroom 0 Yes 667 15 15 House Fan
211 Classroom 0 Yes 841 19 19 House Fan
300 Ladies lounge 0 276 6 0 House Fan
300A Ladies lounge 0 276 6 0 House Fan
301 Classroom   0 Yes 690 15 15 House Fan
302 Classroom   0 Yes 782 17 17 House Fan
303 Classroom   0 Yes 672 15 15 House Fan
304 Classroom   0 Yes 690 15 15 House Fan
305 Classroom   0 690 15 0 House Fan
306 Classroom   0 Yes 690 15 15 House Fan
307 Classroom   0 Yes 690 15 15 House Fan
308 Classroom   0 Yes 690 15 15 House Fan
309 Classroom   0 690 15 0 House Fan
310 Classroom   0 Yes 667 15 15 House Fan
311 Classroom   0 Yes 406 9 9 House Fan
- Library 0 Yes 1,298 29 29 House Fan
- Gym 0 Yes 5,208 118 118
- Kitchen 0 Yes 1,288 29 29 House Fan
- Lunchroom/Cafetorium 0 3,157 71 0 House Fan
- Main office 0 Yes 322 7 7 House Fan
- Nurses Office 0 Yes 128 2 2 House Fan
- Principals office 0 Yes 165 3 3 House Fan
Sheet Last Modified: 03-08-2021    
School:  John Marshall Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
102 Classroom 723.0 48 832 18 18 House Fan
103 Classroom 653.0 43 449 10 10 House Fan
104 Classroom 684.0 45 781 17 17 House Fan
105 Classroom 717.0 47 738 16 16 House Fan
106 Classroom 624.0 41 893 20 20 House Fan
107 Classroom 575.0 38 623 14 14 House Fan
200 Classroom 640.0 42 790 17 17 House Fan
201 Classroom 692.0 46 803 18 18 House Fan
202 Classroom 691.0 46 746 16 16 House Fan
203 Classroom 556.0 37 770 17 17 House Fan
204 Classroom 678.0 45 715 16 16 House Fan
205 Classroom 765.0 51 225 5 5 House Fan
206 Classroom 535.0 35 548 12 12 House Fan
300 Classroom 596.0 39 766 17 17 House Fan
300A Classroom 0 Yes 510 11 11 Wndow Fan
301 Classroom 531.0 35 884 20 20 House Fan
302 Classroom 683.0 45 766 17 17 House Fan
303 Classroom 785.0 52 748 17 17 House Fan
304 Classroom 793.0 52 779 17 17 House Fan
305 Classroom 668.0 44 757 17 17 House Fan
306 Classroom 609.0 40 876 19 19 House Fan
- 1st Fl. Corridor 1,954.0 130 352 8 8 N/A
- Grnd. Fl. Boys Bathrm. 402.0 26 234 5 5 N/A
- Grnd. Fl. Girls Bathrm. 333.0 22 156 3 3 N/A
- Main Office 343.0 22 298 6 6 House Fan
- Nurse / office 340.0 22 420 9 9 House Fan
- Cafeteria 0 Yes 3129 71 71 Wndow Fan
 
 
 
 
 
Sheet Last Modified: 03-24-2021    
School:  Thurgood Marshall Elementary School
Vendor: Goldner
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 99 6 Yes 875 19 19
101 Classroom 112 7 Yes 875 19 19
102 Classroom 53 3 Yes 875 19 19
103 Classroom 60 4 Yes 875 19 19
104 Classroom 310 20 589 13 13
105 Classroom 143 9 Yes 624 14 14
106 Office 154 10 143 3 3
106A Office 0 0 99 2 0
106B Office 0 0 99 2 0
106C Office 168 11 99 2 2
106D Office 180 12 126 2 2
106E Office 165 11 130 2 2
106G Office 191 12 130 2 2
106H Hallway 0 0 528 12 0
106 RR Office 513 34 52.5 1 1
107 Classroom 82 5 720 16 5
107-2 Classroom 0 0 215 4 0
107A Classroom 89 5 816 18 5
108 Classroom 38 2 506 11 2
108A Classroom 37 2 128 2 2
109 Classroom 71 4 1196 27 4
110 Classroom 382 25 682 15 15
111 Classroom 216 14 Yes 630 14 14
113A Principals Office 18 1 340 7 1
113D Admin Office 33 2 99 2 2
113E Admin Office 24 1 99 2 1
113F Admin Office 25 1 99 2 1
113G Admin Office 20 1 99 2 1
115 Classroom 142 9 782 17 9
200 Classroom 88 5 875 19 5
201 Classroom 157 10 Yes 875 19 19
202 Classroom 75 5 Yes 875 19 19
203 Classroom 73 4 Yes 875 19 19
204 Classroom 90 6 Yes 993 22 22
205 Classroom 53 3 327.75 7 3
206A Classroom 42 2 154 3 2
206B Classroom 31 2 270 6 2
206C Classroom 49 3 127 2 2
207 Library 519 34 2108 47 34
208 Computer Lab 73 4 Yes 1024 23 23
209 Music Room 0 0 1171 26 0
215 Faculty Lounge 279 18 400 9 9
300 Classroom 140 9 Yes 875 19 19
301 Classroom 125 8 Yes 875 19 19
302 Classroom 200 13 Yes 875 19 19
303 Classroom 37 2 875 19 2
304 Classroom 86 5 Yes 960 21 21
305 Classroom 111 7 782 17 7
306 Classroom 200 13 782 17 13
307 Classroom 132 8 782 17 8
308 Classroom 33 2 782 17 2
310 Classroom 65 4 782 17 4
311 Classroom 632 42 782 17 17
312 Classroom 99 6 782 17 6
313 Classroom 76 5 782 17 5
314 Classroom 87 5 782 17 5
315 Classroom 112 7 782 17 7
404 Classroom 90 6 1156 26 6
405 Classroom 129 8 782 17 8
405A Office 0 0 112 2 0
406 Classroom 93 6 782 17 6
407 Classroom 147 9 782 17 9
408 Classroom 40 2 782 17 2
409A Office 23 1 140 3 1
410 Classroom 0 0 782 17 0
411 Classroom 86 5 782 17 5
412 Classroom 94 6 782 17 6
413 Classroom 76 5 782 17 5
414 Classroom 84 5 782 17 5
415 Classroom 100 6 782 17 6
- Auditorium 369 24 2162 49 24
- Stage 0 0 630 14 0
- Building Engineer Office 0 0 120 2 0
- Cafeteria 3225 215 4400 100 100
- East Kitchen 0 0 360 8 0
- West Kitchen 0 0 1040 23 0
- Kitchen Office 75 5 120 2 2
- Gym 4507 300 5005 113 113
- Nurses Office 154 10 143 3 3
Sheet Last Modified: 04-19-2021    
School:  Jules E. Mastbaum High School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
SDP Building Name Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Old Building 101 Classroom 0 0 959 21 0
Old Building 102 Classroom 0 0 967 21 0
Old Building 103 Classroom 304 20 1130 25 20
Old Building 104 Classroom 455 30 801 18 18
Old Building 105 Carpentry Shop 0 Yes 2502 56 56
Old Building 201 Classroom 0 0 585 13 0
Old Building 202 Classroom 237 15 190 4 4
Old Building 206 Classroom 569 37 1045 23 23
Old Building 207 Classroom 0 0 906 20 0
Old Building 209 Classroom 738 49 603 13 13
Old Building 301 Classroom 680 45 583 13 13
Old Building 302 Classroom 271 18 915 20 18
Old Building 304 Classroom 256 17 943 21 17
Old Building 306 Classroom 1,285 85 1099 24 24
Old Building 308 Classroom 292 19 971 22 19
Old Building 310A Classroom 279 18 1015 23 18
Old Building 311 Classroom 0 0 940 21 0
Old Building 313 Classroom 572 38 939 21 21
Old Building 315 Classroom 404 26 611 13 13
Old Building 401 Classroom 194 12 562 12 12
Old Building 402 Classroom 588 39 924 20 20
Old Building 404 Classroom 337 22 936 21 21
Old Building 406 Classroom 590 39 658 14 14
Old Building 407 Classroom 0 0 750 17 0
Old Building 408 Classroom 0 0 677 15 0
Old Building 409 Classroom 0 0 659 14 0
Old Building 410 Classroom 737 49 539 12 12
Old Building 412 Classroom 956 63 935 21 21
Old Building 413 Classroom 349 23 460 10 10
Old Building 414 Classroom 446 29 462 10 10
Old Building 415 Classroom 600 40 601 13 13
Old Building 501 Classroom 0 0 583 13 0
Old Building 505 Classroom 1,040 69 701 15 15
Old Building 506 Classroom 0 0 110 2 0
Old Building 510 Classroom 595 39 652 14 14
Old Building 511 Classroom 0 Yes 917 20
Old Building 512 Classroom 0 0 734 16 0
Old Building 513 Classroom 708 47 745 16 16
Old Building 601 Classroom 352 23 562 12 12
Old Building 602 Classroom 838 55 935 21 21
Old Building 603 Classroom 1,066 71 929 21 21
Old Building 604 Classroom 604 40 884 20 20
Old Building 605 Classroom 555 37 964 21 21
Old Building 607 Classroom 733 48 930 21 21
Old Building 609 Classroom 350 23 498 11 11
Old Building 610 Classroom 1,042 69 939 21 21
Old Building 611 Classroom 944 62 943 21 21
Old Building 612 Classroom 357 23 598 13 13
Old Building 613 Classroom 312 20 696 15 15
Old Building 614 Classroom 0 0 823 18 0
Old Building 615 Classroom 411 27 1008 22 22
Old Building 616 Classroom 1,153 76 901 20 20
Old Building 617 Classroom 0 0 899 20 0
Old Building B1 A Wood Shop 475 31 2780 63 31
Old Building B2 A Classroom 499 33 967 21 21
Old Building - Auditorium 1,222 81 4005 91 81
Old Building - 3rd Flr. Gym 2,212 147 3295 74 74
Old Building - 3rd Flr.Gym Locker Room 3,013 200 1903 43 43
Old Building - Stage 532 35 993 22 22
Old Building - 1st Floor N Corridor 301 20 160 3 3
Old Building - 1st Floor E Corridor 536 35 160 3 3
Old Building - 1st Floor S Corridor 427 28 2120 48 28
Old Building - 1st Floor W Corridor 382 25 160 3 3
Old Building - 2nd Floor S Corridor 438 29 2120 48 29
Old Building - 2nd Floor W Corridor 465 31 160 3 3
Old Building - 2nd Floor N Corridor 711 47 2120 48 47
Old Building - 2nd Floor E Corridor 720 48 160 3 3
Old Building - 3rd Floor E Corridor 504 33 0 0
Old Building - 3rd Floor N Corridor 619 41 2120 48 41
Old Building - 3rd Floor W Corridor 761 50 0 0
Old Building - 3rd Floor S Corridor 569 37 2120 48 37
Old Building - 4th Floor N Corridor 502 33 2120 48 33
Old Building - 4th Floor E Corridor 633 42 0 0
Old Building - 4th Floor S Corridor 0 0 2120 48 0
Old Building - 4th Floor W Corridor 0 0 0 0
Old Building - 5th Floor N Corridor 593 39 2120 48 39
Old Building - 5th Floor Library 1,677 111 2115 48 48
Old Building - 6th Floor S Corridor 683 45 2120 48 45
Old Building - 6th Floor W Corridor 918 61 0 0
Old Building - 6th Floor N Corridor 530 35 2120 48 35
Old Building - 6th Floor E Corridor 0 0 0 0
Old Building - Café 1,559 103 734 16 16
New Building 120 Auto Shop 1,016 67 2981 67 67
New Building 124 Auto Shop 8,220 548 4344 98 98
New Building 220-221 Electrical Shop 0 0 1973 44 0
New Building 224-223 Shop 2,067 137 1150 26 26
New Building 225-226 Shop 2,858 190 3743 85 85
New Building 324-323 324-323 877 58 2781 63 58
New Building 326-325 326-325 1,135 75 2395 54 54
New Building 420 420.0 0 0 1250 28 0
New Building 421 421.0 0 0 1873 42 0
New Building 423 423.0 487 32 1693 38 32
New Building 426 426 Plumbing Shop 1,678 111 1265 28 28
New Building 427-426 427-426 0 0 1583 35 0
New Building - Gym 958 63 7556 171 63
New Building - Gym Locker Rm. 0 0 5738 130 0
New Building 321 Nursing 614 40 1898 43 40
New Building - Weld Shop 2,329 155 625 14 14
Sheet Last Modified: 04-07-2021      
School:  Julia R. Masterman Laboratory and Demonstration High School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
8 Music Room 0 630 14 0
9 Classroom 0.0 0 874 19 0
11 Classroom 0.0 0 825 18 0 AHU Inoperable
11A Classroom 0.0 0 368 8 0 AHU Inoperable
12 Classroom 0.0 0 832 18 0 AHU Inoperable
14 Art Room 0 1023 23 0 AHU Inoperable
15 Classroom 0.0 0 1148 26 0
101 Classroom 0.0 0 Yes 704 16 16 AHU Inoperable
102 Music Room 0.0 0 836 19 0 AHU Inoperable
103 Classroom 0.0 0 638 14 0 AHU Inoperable
104 Classroom 0.0 0 660 15 0 AHU Inoperable
201 Classroom 0.0 0 Yes 704 16 16 AHU Inoperable
202 Classroom 0.0 0 682 15 0 AHU Inoperable
203 Classroom 0.0 0 Yes 644 14 14 AHU Inoperable
204 Library 0.0 0 682 15 0 AHU Inoperable
205 Fitness Storage 0.0 0 Yes 690 15 15 AHU Inoperable
206 Fitness Storage 0.0 0 704 16 0 AHU Inoperable
207 Classroom 0.0 0 Yes 660 15 15 AHU Inoperable
208 Classroom 0.0 0 682 15 0 AHU Inoperable
209 Classroom 0.0 0 187 4 0 AHU Inoperable
210 Classroom 0.0 0 187 4 0 AHU Inoperable
211 Classroom 0.0 0 Yes 682 15 15 AHU Inoperable
212 Classroom 0.0 0 682 15 0 AHU Inoperable
213 Classroom 0.0 0 374 8 0 AHU Inoperable
214 Classroom 0.0 0 374 8 0 AHU Inoperable
218 Main Office 0 Yes 210 4 4 AHU Inoperable
301 Classroom 0.0 0 Yes 682 15 15
302 Classroom 0.0 0 682 15 0 AHU Inoperable
303 Classroom 0.0 0 660 15 0 AHU Inoperable
304 Classroom 0.0 0 682 15 0 AHU Inoperable
305 Classroom 0.0 0 Yes 638 14 14 AHU Inoperable
306 Classroom 0.0 0 144 3 0 AHU Inoperable
307 Classroom 0 726 16 0 AHU Inoperable
307A Office 0 264 6 0
308 Classroom 0.0 0 1,210 27 0
309 Office 0.0 0 300 6 0 AHU Inoperable
310 Classroom 0.0 0 96 2 0 AHU Inoperable
311 Classroom 0.0 0 682 15 0 AHU Inoperable
312 Classroom 0.0 0 1,078 24 0 AHU Inoperable
313 Room 0 374 8 0 AHU Inoperable
402 Classroom 0.0 0 880 20 0
404 Classroom 0.0 0 704 16 0 AHU Inoperable
406 Classroom 0.0 0 504 11 0 AHU Inoperable
408 Classroom 0.0 0 672 15 0 AHU Inoperable
410 Classroom 0.0 0 1,008 22 0 AHU Inoperable
412 Office 0.0 0 205 4 0 AHU Inoperable
502 Classroom 0.0 0 880 20 0 AHU Inoperable
506 Classroom 0.0 0 690 15 0 AHU Inoperable
- Game Room 0 790 17 0 AHU Inoperable
- Auditorium 0.0 0 5850 132 0
- Cafeteria 0.0 0 3600 81 0 AHU Inoperable
- Counselor's Office 0 110 2 0 AHU Inoperable
- Counselor's Office 0 110 2 0
- Faculty Cafeteria 0.0 0 726 16 0
- Gym 0.0 0 Yes 6208 141 141 AHU Inoperable
- Boy's Locker Room 0 580 13 0
- Girl's Locker Room 0 209 4 0
- Health room 0 100 2 0
- Kitchen 0.0 0 828 18 0 AHU Inoperable
- LIbrary Room 0 620 14 0
- Library Office 0 231 5 0
- Library A 0 506 11 0
- Library B 0 651 14 0
- Library C  0 230 5 0
- Nurse Office 0.0 0 Yes 170 3 3 AHU Inoperable
Nurse Examining 0 Yes 100 2 2
Nurse Roster Room 0 Yes 288 6 6
- Robotics 0.0 0 420 9 0 AHU Inoperable
- Science Office 0 187 4 0
- Principal 's  Office 0 210 4 0
- Assant Principal's Office 0 140 3 0
- Operations Office 0 56 1 0
- Office Waiting  Area 0 275 6 0
- Roster Office 0 136 3 0
Sheet Last Modified: 04-23-2021    
School:  Mayfair Elementary School
Vendor: Devine Brothers Devine Part 2 Devine Part 3
Vendor: Capital Capital Update Capital Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 207 13 696 15 13 Unit Ventilator
101 Classroom 201 13 696 15 13 Unit Ventilator
102 Classroom 197 13 598 13 13 Unit Ventilator
103 Classroom 189 12 720 16 12 Unit Ventilator
104 Classroom 355 23 690 15 15 Unit Ventilator
105 Classroom 231 15 624 14 14 Unit Ventilator
106 Classroom 237 15 720 16 15 Unit Ventilator
107 Classroom 458 30 720 16 16 Unit Ventilator
108 Classroom 115 7 600 13 7 Unit Ventilator
109 Classroom 186 12 744 16 12 Unit Ventilator
110 Classroom 418 27 696 15 15 Unit Ventilator
111 Classroom 202 13 624 14 13 Unit Ventilator
112 Classroom 461 30 1032 23 23 Unit Ventilator
113 Classroom 211 14 720 16 14 Unit Ventilator
114 Classroom 377 25 644 14 14 Unit Ventilator
115 Classroom 271 18 620 14 14 Unit Ventilator
116 Classroom 395 26 989 22 22 Unit Ventilator
118 Classroom 384 25 690 15 15 Unit Ventilator
119 Classroom 320 21 624 14 14 Unit Ventilator
120 Classroom 311 20 1610 36 20 Unit Ventilator
200 Classroom 0 Yes 205 4 4
201 Classroom 286 19 696 15 15 Unit Ventilator
202 Classroom 560 37 696 15 15 Unit Ventilator
203 Classroom 381 25 725 16 16 Unit Ventilator
204 Classroom 323 21 884 20 20 Unit Ventilator
205 Classroom 271 18 780 17 17 Unit Ventilator
206 Classroom 316 21 806 18 18 Unit Ventilator
207 Classroom   295 19 806 18 18 Unit Ventilator
207A Asst. Principal Office 0 0 Yes 293 6 6 Unit Ventilator
208 Classroom 305 20 528 12 12 Unit Ventilator
209 Classroom 560 37 884 20 20 Unit Ventilator
210 Classroom 290 19 1118 25 19 Unit Ventilator
211 Classroom 307 20 648 14 14 Unit Ventilator
212 Classroom 483 32 665 15 15 Unit Ventilator
213 Classroom 590 39 806 18 18 Unit Ventilator
214 Classroom 300 20 806 18 18 Unit Ventilator
215 Classroom 294 19 728 16 16 Unit Ventilator
216 Classroom 317 21 648 14 14 Unit Ventilator
217 Classroom 350 23 782 17 17 Unit Ventilator
218 Classroom 271 18 621 14 14 Unit Ventilator
219 Classroom 137 9 648 14 9 Unit Ventilator
220 Classroom 235 15 648 14 14 Unit Ventilator
221 Classroom 325 21 744 16 16 Unit Ventilator
222 Classroom 180 12 648 14 12 Unit Ventilator
301 Classroom 325 21 720 16 16 ERU
302 Classroom 304 20 720 16 16 ERU
303 Classroom 270 18 720 16 16 ERU
304 Classroom 435 29 720 16 16 ERU
305 Classroom 453 30 720 16 16 ERU
306 Classroom 480 32 720 16 16 ERU
401 Classroom 320 21 720 16 16 ERU
402 Classroom 282 18 720 16 16 ERU
403 Classroom 551 36 720 16 16 ERU
404 Classroom 412 27 720 16 16 ERU
405 Classroom 412 27 720 16 16 ERU
406 Classroom 406 27 720 16 16 ERU
510 Classroom 282 18 754 17 17 ERU
511 Classroom 430 28 754 17 17 ERU
512 Classroom 447 29 754 17 17 ERU
513 Classroom 543 36 754 17 17 ERU
515 Classroom 652 43 754 17 17 ERU
516 Classroom 519 34 754 17 17 ERU
517 Classroom 605 40 754 17 17 ERU
520 Classroom 500 33 754 17 17 ERU
521 Classroom 548 36 754 17 17 ERU
522 Classroom 530 35 754 17 17 ERU
523 Classroom 509 33 754 17 17 ERU
525 Classroom 676 45 754 17 17 ERU
526 Classroom 646 43 754 17 17 ERU
527 Classroom 568 37 774 17 17 ERU
- Main Office 0 Yes 493 11 11
- Counselor Office 0 Yes 126 2 2
- Counselor Office 0 Yes 231 5 5
- Principal Office 0 Yes 196 4 4
- Special Education 0 Yes 275 6 6
- Conference Room 0 Yes 135 3 3
- Faculty Room 0 Yes 171 3 3
- Nurse Office 0 Yes 372 8 8
- Asst. Principal 1 0 Yes 86 1 1
- Asst. Principal 2 0 Yes 97 2 2
- Auditorium 0 4920 111 0 AHU
Auditorium Room 1 0 Yes 263 5 5
Auditorium Room 2 0 Yes 254 5 5
Music 1 Room 0 Yes 354 8 8
Music 2 Room 0 Yes 711 16 16
- Cafeteria 998 66 3257 74 66 RTU
- Gym 0 Yes 3982 90 90 AHU
School Police Office 0 Yes 54 1 1
- Nurse Office 292 19 372 8 8 Unit Ventilator
1 Mobile Classroom 326 21 594 13 13 AHU
2 Mobile Classroom 328 21 594 13 13 AHU
3 Mobile Classroom 644 42 594 13 13 AHU
4 Mobile Classroom 451 30 594 13 13 AHU
5 Mobile Classroom 580 38 594 13 13 AHU
6 Mobile Classroom 438 29 594 13 13 AHU
7 Mobile Classroom 414 27 594 13 13 AHU
8 Mobile Classroom 574 38 594 13 13 AHU
Sheet Last Modified: 04-06-2021      
School:  General George A. McCall Elementary School
Vendor: Devine 2nd Retest 3rd Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
0 Classroom 0 0 Yes 572 13 13 N/A
1 Classroom 370 24 924 21 21 Unit Ventilator
2 Music Room 453 30 836 19 19 Unit Ventilator
4 Classroom 1631 108 660 15 15 AHU
5 Classroom 478 31 1012 23 23 AHU
6 Classroom 535 35 1100 25 25 AHU
101 Office 0 0 Yes 276 6 6 N/A
101A Office 182 12 Yes 440 10 10 Unit Ventilator
102 Classroom 332 22 836 19 19 Unit Ventilator
103 Classroom 283 18 Yes 880 20 20 Unit Ventilator
105 Classroom 278 18 Yes 880 20 20 Unit Ventilator
106 Classroom 340 22 924 21 21 Unit Ventilator
107 Classroom 292 19 Yes 968 22 22 Unit Ventilator
108 Classroom 303 20 836 19 19 Unit Ventilator
109 Classroom 375 25 880 20 20 Unit Ventilator
110 Classroom 0 0 Yes 220 5 5 N/A
110A Office 336 22 440 10 10 Unit Ventilator
209 Classroom 0.0 0 Yes 440 10 10 Unit Ventilator
210 Classroom 273 18 Yes 880 20 20 Unit Ventilator
211 Classroom 293 19 Yes 924 21 21 Unit Ventilator
212 Classroom 294 19 880 20 19 Unit Ventilator
213 Classroom 320 21 924 21 21 Unit Ventilator
214 Classroom 376 25 880 20 20 Unit Ventilator
216A Office 0 0 Yes 480 10 10 N/A
217 Classroom 297 19 792 18 18 Unit Ventilator
218 Classroom 309 20 924 21 20 Unit Ventilator
219 Classroom 313 20 792 18 18 Unit Ventilator
318 Classroom 172 11 Yes 748 17 17 Unit Ventilator
319 Classroom 368 24 924 21 21 Unit Ventilator
320 Classroom 401 26 836 19 19 Unit Ventilator
321 Classroom 329 21 880 20 20 Unit Ventilator
322 Classroom 292 19 924 21 19 Unit Ventilator
323 Classroom 351 23 924 21 21 Unit Ventilator
324 Classroom 284.0 18 880 20 18 Unit Ventilator
325 Classroom 396 26 924 21 21 Unit Ventilator
326 Classroom 309 20 836 19 19 Unit Ventilator
327 Classroom 345 23 792 18 18 Unit Ventilator
327A Classroom 261 17 484 11 11 Unit Ventilator
- Auditorium 1451 96 4224 96 96 AHU
- Gym/Cafeteria 1279 85 3740 85 85 AHU
- Main Office 311 20 792 18 18 Unit Ventilator
- Library 492 32 1584 36 32 Unit Ventilator
- Engineer Office 0 0 432 9 0 N/A
- Gym Office 0 0 110 2 0 AHU
- Kitchen 9 0 Yes 384 8 8 AHU
- Principals Office 0 0 Yes 493 11 11 AHU
Sheet Last Modified: 04-13-2021    
School:   John F. McCloskey Elementary School
Vendor: Chadwick Part 2 Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
2 IMC 0 Yes 1044 23 23 Unit Ventilator
7 Recovery. room 0 Yes 180 4 4 Convector
101 Classroom 229.0 15 936 21 15 Unit Ventilator
102 Classroom 192.0 12 936 21 12 Unit Ventilator
103 Classroom 394.0 26 936 21 21 Unit Ventilator
104 Classroom 155.0 10 Yes 1056 24 24 Unit Ventilator
105 Classroom 342.0 22 897 20 20 Unit Ventilator
106 Classroom 203.0 13 936 21 13 Unit Ventilator
107 Classroom 206.0 13 936 21 13 Unit Ventilator
108 Classroom 390.0 26 936 21 21 Unit Ventilator
109 Classroom 282.0 18 736 16 16 Unit Ventilator
111 Classroom 356.0 23 736 16 16 Unit Ventilator
113 Classroom 320.0 21 736 16 16 Unit Ventilator
114 Classroom 319.0 21 736 16 16 Unit Ventilator
201 Classroom 0 916 20 0 Unit Ventilator
202 Classroom 200.0 13 936 21 13 Unit Ventilator
203 Classroom 194.0 12 936 21 12 Unit Ventilator
204 Classroom 378.0 25 936 21 21 Unit Ventilator
205 Classroom 342.0 22 936 21 21 Unit Ventilator
206 Classroom 487.0 32 936 21 21 Unit Ventilator
208 Classroom 346.0 23 936 21 21 Unit Ventilator
209 Classroom 514.0 34 936 21 21 Unit Ventilator
210 Classroom 247.0 16 936 21 16 Unit Ventilator
211 Classroom 374.0 24 936 21 21 Unit Ventilator
- Auditorium 0 2700 61 0 AHU
- Computer Room 40.0 2 1080 24 2 Unit Ventilator
- Gym 0 Yes 3744 85 85 AHU
- Main Office 0 Yes 338 7 7 Convector
- Prin. Office 0 Yes 312 7 7 Convector
- Nurse. Office 0 Yes 225 5 5 Convector
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sheet Last Modified: 03-18-2021    
School:  Alexander K. McClure Elementary School
Vendor: Devine Brothers Retest 2nd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
0 Building Engineer 0.0 0 0 0 N/A
1 Gym 650.0 43 2486 56 43 House Fan
6 Art 302.0 20 894 20 20 House Fan
7 Classroom 559.0 37 839 19 19 House Fan
11 Classroom 523.0 34 821 18 18 House Fan
101 Classroom 603.0 40 887 20 20 House Fan
106 Classroom 419.0 27 927 21 21 House Fan
106A Asst. Principal 0.0 0 Yes 104 2 2 House Fan
107 Classroom 505.0 33 753 17 17 House Fan
108 Classroom 329.0 21 849 19 19 House Fan
109 Classroom 454.0 30 791 17 17 House Fan
110 Classroom 603.0 40 725 16 16 House Fan
111 Classroom 537.0 35 699 15 15 House Fan
201 Classroom 585.0 39 847 19 19 House Fan
202 Classroom 597.0 39 883 20 20 House Fan
203 Classroom 423.0 28 903 20 20 House Fan
204 Classroom 461.0 30 887 20 20 House Fan
205 Classroom 482.0 32 945 21 21 House Fan
206 Library 431.0 28 890 20 20 House Fan
206A Nurse Office 0.0 0 194 4 0 N/A
206B Nurse Exam 0.0 0 Yes 362 8 8 House Fan
207 Classroom 442.0 29 869 19 19 House Fan
208 Classroom 309.0 20 812 18 18 House Fan
209 Classroom 412.0 27 823 18 18 House Fan
210 Classroom 602.0 40 714 16 16 House Fan
211 Classroom 595.0 39 740 16 16 House Fan
301 Classroom 559.0 37 882 20 20 House Fan
302 Classroom 501.0 33 902 20 20 House Fan
303 Classroom 377.0 25 900 20 20 House Fan
304 Classroom 483.0 32 875 19 19 House Fan
305 Classroom 469.0 31 910 20 20 House Fan
306 Classroom 402.0 26 894 20 20 House Fan
306A Office 0.0 0 Yes 185 4 4 House Fan
307 Classroom 470.0 31 932 21 21 House Fan
308 Classroom 301.0 20 815 18 18 House Fan
309 Classroom 313.0 20 851 19 19 House Fan
310 Classroom 396.0 26 726 16 16 House Fan
311 Classroom 406.0 27 732 16 16 House Fan
312 Classroom 0.0 0 Yes 435 9 9 N/A
- 4th Floor Office N 0.0 0 0 0 N/A
- 4th Floor Office S 0.0 0 0 0 N/A
- Cafeteria 1,876.0 125 2974 67 67 House Fan
- Main Office 0.0 0 Yes 262 5 5 N/A
- Principal Office 0.0 0 Yes 194 4 4 N/A
- Portable Classroom 289.0 19 1290 29 19 Unit Ventilators
Sheet Last Modified: 04-29-2021    
School:  Delaplaine McDaniel Elementary-Middle School
  McDaniel Annex (St. Edmunds)
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
McDaniel Main
102 Classroom 865 57 660 15 15 Unit Ventilator
103 Classroom 250 16 660 15 15 Unit Ventilator
104 Classroom 340 22 836 19 19 Unit Ventilator
105 Classroom 275 18 660 15 15 Unit Ventilator
107 Classroom 1,025 68 660 15 15 Unit Ventilator
108 Classroom 0 Yes 464 10 10
109 Classroom 550 36 1,260 28 28 Unit Ventilator
200 Classroom 430 28 1,260 28 28 Unit Ventilator
201 Classroom 0 0 396 9 0 Unit Ventilator
203 Classroom 635 42 630 14 14 Unit Ventilator
204 Computer Lab 949 63 924 21 21 Unit Ventilator
205 Classroom 635 42 660 15 15 Unit Ventilator
206 Classroom 475 31 858 19 19 Unit Ventilator
207 Classroom 0 0 783 17 0 Unit Ventilator
209 Classroom 0 0 777 17 0 Unit Ventilator
300 Classroom 0 0 Yes 819 18 18 Unit Ventilator
301 Classroom 0 0 691 15 0 Unit Ventilator
303 Classroom 428 28 945 21 21 Unit Ventilator
304 Classroom 134 8 704 16 8 Unit Ventilator
305 Classroom 374 24 638 14 14 Unit Ventilator
306 Classroom 185 12 638 14 12 Unit Ventilator
307 Classroom 570 38 638 14 14 Unit Ventilator
308 Classroom 470 31 638 14 14 Unit Ventilator
309 Classroom 400 26 638 14 14 Unit Ventilator
310 Classroom 494 32 880 20 20 Unit Ventilator
311 Classroom 430 28 638 14 14 Unit Ventilator
313 Classroom 1099 73 814 18 18 Unit Ventilator
- Gym 0 0 Yes 3,300 75 75 AHU
- Gym Office 0 Yes 77 1 1
- Nurse Office 0 Yes 280 6 6
- Media Center 700 46 1,078 24 24 Unit Ventilator
- Kitchen 0 Yes 294 6 6
- School Police 0 Yes 90 2 2
- Counselor Office 0 Yes 117 2 2
- Principals Office 0 Yes 196 4 4
- Vice Principal 0 Yes 187 4 4
- Office 0 0 Yes 392 8 8 AHU
McDaniel Annex (St. Edmunds)
K-1 Classroom 269 17 516 11 11 Unit Ventilator
K-2 Classroom 449 29 616 14 14 Unit Ventilator
K-3 Classroom 407 27 616 14 14 Unit Ventilator
K-4 Classroom 348 23 516 11 11 Unit Ventilator
206 Classroom 350 23 616 14 14 Unit Ventilator
207 Classroom 530 35 792 18 18 Unit Ventilator
208 Classroom 632 42 660 15 15 Unit Ventilator
209 Classroom 495 33 660 15 15 Unit Ventilator
210 Classroom 375 25 440 10 10 Unit Ventilator
213 Classroom 447 29 440 10 10 Unit Ventilator
215 Classroom 640 42 792 18 18 Unit Ventilator
306 Classroom 525 35 616 14 14 Unit Ventilator
307 Classroom 653 43 792 18 18 Unit Ventilator
308 Classroom 425 28 660 15 15 Unit Ventilator
309 Classroom 630 42 660 15 15 Unit Ventilator
310 Classroom 471 31 660 15 15 Unit Ventilator
312 Classroom 481 32 704 16 16 Unit Ventilator
313 Classroom 611 40 704 16 16 Unit Ventilator
- Cafeteria / Gym 14,007 933 3960 90 90 AHU
- Classroom 15,010 1000 1,431 32 32 AHU
Sheet Last Modified: 04-06-2021    
School:   William McKinley Elementary School
Vendor: Devine Brothers Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- A1/11 529 35 858 19 19 Unit Ventilator
- A2/12 627 41 832 18 18 Unit Ventilator
- A3/13 298 19 858 19 19 Unit Ventilator
- A4/14 512 34 858 19 19 Unit Ventilator
- Autistic Support 8 231 15 726 16 15 Unit Ventilator
- B1/21 711 47 792 18 18 Unit Ventilator
- B2/22 630 42 754 17 17 Unit Ventilator
- B3/23 660 44 754 17 17 Unit Ventilator
- B4/24 538 35 744 16 16 Unit Ventilator
- C1/31 604 40 726 16 16 Unit Ventilator
- C2/32 271 18 675 15 15 Unit Ventilator
- C3/33 605 40 700 15 15 Unit Ventilator
- C4/34 669 44 720 16 16 Unit Ventilator
- CCTC 11 1062 70 1215 27 27 Unit Ventilator
- D1 426 28 858 19 19 Unit Ventilator
- D2 553 36 780 17 17 Unit Ventilator
- D3 290 19 780 17 17 Unit Ventilator
- D4 310 20 780 17 17 Unit Ventilator
- Gymnasium 1525 101 2860 65 65 AHU
- Kindergarten 1 355 23 924 21 21 Unit Ventilator
- Kindergarten 2 290 19 Yes 924 21 21 Unit Ventilator
- Kindergarten 3 282 18 Yes 924 21 21 Unit Ventilator
- Pre K 4 739 49 924 21 21 Unit Ventilator
- Room 5 611 40 726 16 16 Unit Ventilator
-- Room 6 467 31 726 16 16 Unit Ventilator
- Room 9 / Visual Arts 748 49 726 16 16 AHU
- Room 12 587 39 809 18 18 AHU
A-0 Small Classroom 37 2 150 3 2 AHU
7 Teachers Lounge 59 3 Yes 351 7 7 AHU
- Nurse Exam Large 69 4 Yes 252 5 5 AHU
- Nurse Office 38 2 119 2 2 AHU
- Nurse Exam 59 3 153 3 3 AHU
- Storage Large 61 4 216 4 4 AHU
- Storage 24 1 0 0 AHU
- Auditorium 1667 111 2453 55 55 AHU
- Music Room 319 21 727 16 16 AHU
- Library 1047 69 3888 88 69 AHU
- Cafeteria 894 59 2331 52 52 AHU
D-0 Small Classroom 36 2 150 3 2 AHU
C-0 Small Classroom 21 1 150 3 1 AHU
B-0 Small Classroom 53 3 150 3 3 AHU
10 Small Classroom 26 1 Yes 364 8 8 AHU
- Main Office 50 3 Yes 817 18 18 AHU
- Admin Office 1 52 3 128 2 2 AHU
- Admin Office 2 73 4 128 2 2 AHU
- Admin Office 3 43 2 128 2 2 AHU
- Admin Office 5 50 3 160 3 3 AHU
- Admin Office 6 49 3 285 6 3 AHU
- Admin Office 7 22 1 Yes 120 2 2 AHU
- Equip Storage 0 0 120 2 0 AHU
- Corridor 35 2 440 10 2 AHU
- Principals Office 35 2 Yes 180 4 4 AHU
Sheet Last Modified: 04-29-2021    
School:   Morton McMichael Elementary School
Vendor: Chadwick Part 2 Part 3
  Part 4    
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Staff Lounge 125 8 468 10 8 Unit Ventilator
101 Admin 281 18 1,056 24 18 Unit Ventilator
102 Superintendants 284 18 600 13 13 Unit Ventilator
- IT Office 0 459 10 0
104 Small Conf/Assis. Super 110 7 252 5 5 Unit Ventilator
105 Large Conference 319 21 1,188 27 21 Unit Ventilator
108 Classroom 375 25 864 19 19 Unit Ventilator
110 Classroom 279 18 840 19 18 Unit Ventilator
114 Classroom 284 18 576 13 13 Unit Ventilator
200 Classroom 340 22 840 19 19 Unit Ventilator
201 Classroom 328 21 840 19 19 Unit Ventilator
201A Classroom 320 21 336 7 7 Unit Ventilator
202 Classroom 292 19 840 19 19 Unit Ventilator
204 Classroom 272 18 2,592 58 18 Unit Ventilator
205 Classroom 326 21 840 19 19 Unit Ventilator
206 Classroom 275 18 2,592 58 18 Unit Ventilator
207 Classroom 318 21 840 19 19 Unit Ventilator
208 Classroom 249 16 2,592 58 16 Unit Ventilator
210 Classroom 351 23 840 19 19 Unit Ventilator
212 Classroom 363 24 840 19 19 Unit Ventilator
214 Classroom 282 18 840 19 18 Unit Ventilator
216 Classroom 262 17 864 19 17 Unit Ventilator
217 Classroom 368 24 1,944 44 24 Unit Ventilator
218 Classroom 320 21 840 19 19 Unit Ventilator
219 Classroom 351 23 1,944 44 23 Unit Ventilator
220 Classroom 403 26 840 19 19 Unit Ventilator
222 Classroom 280 18 504 11 11 Unit Ventilator
224 Classroom 0 840 19 0 Unit Ventilator
226 Classroom 240 16 840 19 16 Unit Ventilator
300 Classroom 239 15 840 19 15 Unit Ventilator
301 Classroom 291 19 840 19 19 Unit Ventilator
302 Classroom 302 20 840 19 19 Unit Ventilator
303 Classroom 288 19 840 19 19 Unit Ventilator
305 Classroom 317 21 840 19 19 Unit Ventilator
306 Classroom 546 36 1,248 28 28 Unit Ventilator
307 Classroom 274 18 840 19 18 Unit Ventilator
308 Classroom 273 18 864 19 18 Unit Ventilator
310 Classroom 272 18 840 19 18 Unit Ventilator
312 Classroom 281 18 840 19 18 Unit Ventilator
314 Classroom 306 20 840 19 19 Unit Ventilator
316 Classroom 315 21 864 19 19 Unit Ventilator
317 Classroom 392 26 840 19 19 Unit Ventilator
318 Classroom 274 18 840 19 18 Unit Ventilator
319 Classroom 276 18 840 19 18 Unit Ventilator
320 Classroom 281 18 840 19 18 Unit Ventilator
322 Classroom 270 18 576 13 13 Unit Ventilator
323 Classroom 279 18 864 19 18 Unit Ventilator
324 Classroom 326 21 840 19 19 Unit Ventilator
325 Classroom 285 19 888 20 19 Unit Ventilator
326 Classroom 262 17 864 19 17 Unit Ventilator
- Auditorium 520 34 4,914 111 34 AHU
- Cafe 590 39 2,485 56 39 AHU
- Gym 690 46 3,621 82 46 AHU
- Main Office 0 Yes 1,401 31 31
- Nurse Office 0 Yes 616 14 14
Sheet Last Modified: 04-06-2021    
School:  General George G. Meade Elementary-Middle School
Vendor: EMCOR Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
15 Classroom 378 25 Yes 644 14 14 Unit Ventilator
16 Classroom 336 22 833 18 18 Unit Ventilator
17 Classroom 184 12 330 7 7 Unit Ventilator
18 Classroom 686 45 Yes 1101 25 25 Unit Ventilator
101 Classroom 294 19 892 20 19 Unit Ventilator
102 Classroom 299 19 Yes 765 17 17 Unit Ventilator
103 Classroom 360 24 Yes 823 18 18 Unit Ventilator
104 Classroom 281 18 705 16 16 Unit Ventilator
105 Classroom 445 29 674 15 15 Unit Ventilator
106 Classroom 405 27 846 19 19 Unit Ventilator
107 Classroom 332 22 526 11 11 Unit Ventilator
108 Classroom 294 19 670 15 15 Unit Ventilator
109 Classroom 279 18 705 16 16 Unit Ventilator
115 Classroom 640 42 Yes 865 19 19 Unit Ventilator
116 Classroom 325 21 Yes 413 9 9 Unit Ventilator
117 Classroom 433 28 Yes 837 19 19 Unit Ventilator
118 Classroom 664 44 Yes 849 19 19 Unit Ventilator
200 Classroom 193 12 349 7 7 Unit Ventilator
201 Classroom 414 27 667 15 15 Unit Ventilator
202 Classroom 53 3 673 15 3 Unit Ventilator
203 Classroom 275 18 666 15 15 Unit Ventilator
204 Classroom 360 24 669 15 15 Unit Ventilator
205 Classroom 343 22 701 15 15 Unit Ventilator
206 Classroom 280 18 705 16 16 Unit Ventilator
207 Classroom 303 20 671 15 15 Unit Ventilator
208 Classroom 259 17 576 13 13 Unit Ventilator
209 Classroom 0 0 540 12 0 Unit Ventilator
210 Classroom 311 20 511 11 11 Unit Ventilator
211 Classroom 222 14 720 16 14 Unit Ventilator
215 Classroom 550 36 843 19 19 Unit Ventilator
216 Classroom 306 20 855 19 19 Unit Ventilator
217 Classroom 169 11 842 19 11 Unit Ventilator
218 Classroom 631 42 852 19 19 Unit Ventilator
285 Classroom 273 18 0 0 0 Unit Ventilator
301 Classroom 883 58 2031 46 46 Unit Ventilator
304 Classroom 276 18 670 15 15 Unit Ventilator
305 Classroom 346 23 702 15 15 Unit Ventilator
306 Classroom 319 21 706 16 16 Unit Ventilator
307 Classroom 347 23 670 15 15 Unit Ventilator
308 Classroom 112 7 852 19 7 Unit Ventilator
309 Classroom 333 22 309 7 7 Unit Ventilator
310 Classroom 247 16 510 11 11 Unit Ventilator
311 Classroom 351 23 706 16 16 Unit Ventilator
312 Classroom 305 20 514 11 11 Unit Ventilator
315 Classroom 289 19 838 19 19 Unit Ventilator
316 Classroom 285 19 855 19 19 Unit Ventilator
317 Classroom 548 36 847 19 19 Unit Ventilator
318 Classroom 647 43 852 19 19 Unit Ventilator
- Main Office 0 Yes 305.08 6 6
- Nurse Office 0 Yes 242.55 5 5
- 1st Floor Hall 310 20 2688 61 20 Unit Ventilator
- 1st Floor Nurse RR 0 0 244 5 0 N/A
- 1st Floor Staff Womens RR 0 0 393 8 0 N/A
- 2nd Floor Hall 0 0 2066 46 0 Unit Ventilator
- 2nd Floor Mens RR 99 6 355 8 6 N/A
- 2nd Floor Womens RR 236 15 328 7 7 N/A
- 3rd Floor Hall 289 19 2661 60 19 Unit Ventilator
- 3rd Floor Mens RR 95 6 259 5 5 N/A
- 3rd Floor Womens RR 219 14 328 7 7 N/A
- Cafeteria 754 50 5223 118 50 Unit Ventilator
- Bsmt: Boys RR 0 0 765 17 0 N/A
- Bsmt: Grils RR 0 0 697 15 0 N/A
- Staff Restroom: 1st Floor 0 0 168 3 0 N/A
- Library 0 0 2062.2 46 0 Unit Ventilator
- Staff Restroom: 2nd Floor 0.0 0 305 6 0 N/A
- Staff Restroom: 3rd Floor 0.0 0 308 7 0 N/A
Sheet Last Modified: 04-08-2021    
School:  Austin Meehan Middle School
Vendor: Devine
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
3 Classroom 280 18 1537 34 18 Unit Ventilator
111 Classroom 323 21 917 20 20 Unit Ventilator
112 Classroom 309 20 1490 33 20 Unit Ventilator
113 Classroom 287 19 208 4 4 Unit Ventilator
114 Classroom 307 20 1193 27 20 Unit Ventilator
115 Classroom 274 18 1192 27 18 Unit Ventilator
121 Classroom 0 0 944 21 0 Unit Ventilator
122 Classroom 503 33 1085 24 24 Unit Ventilator
123 Classroom 350 23 1175 26 23 Unit Ventilator
124 Classroom 283 18 1123 25 18 Unit Ventilator
125 Classroom 413 27 1156 26 26 Unit Ventilator
126 Classroom 400 26 1064 24 24 Unit Ventilator
127 Classroom 333 22 1198 27 22 Unit Ventilator
128 Classroom 343 22 933 21 21 Unit Ventilator
211 Classroom 327 21 867 19 19 Unit Ventilator
212 Classroom 382 25 1630 37 25 Unit Ventilator
213 Classroom 281 18 269 6 6 Unit Ventilator
214 Classroom 372 24 1317 29 24 Unit Ventilator
215 Classroom 396 26 1199 27 26 Unit Ventilator
221 Classroom 0 0 1054 23 0 Unit Ventilator
222 Classroom 337 22 1286 29 22 Unit Ventilator
223 Classroom 343 22 1230 27 22 Unit Ventilator
224 Classroom 0 0 1091 24 0 Unit Ventilator
225 Classroom 420 28 1151 26 26 Unit Ventilator
226 Classroom 397 26 1175 26 26 Unit Ventilator
227 Classroom 327 21 1292 29 21 Unit Ventilator
228 Classroom 0 0 931 21 0 Unit Ventilator
311 Classroom 310 20 1041 23 20 Unit Ventilator
312 Classroom 309 20 1602 36 20 Unit Ventilator
313 Classroom 0 0 756 17 0 Unit Ventilator
314 Classroom 0 0 1279 29 0 Unit Ventilator
315 Classroom 0 0 1219 27 0 Unit Ventilator
321 Classroom 0 0 1064 24 0 Unit Ventilator
322 Classroom 460 30 1199 27 27 Unit Ventilator
323 Classroom 0 0 1365 31 0 Unit Ventilator
324 Classroom 377 25 1039 23 23 Unit Ventilator
325 Classroom 270 18 1247 28 18 Unit Ventilator
326 Classroom 493 32 1322 30 30 Unit Ventilator
327 Classroom 417 27 1184 26 26 Unit Ventilator
328 Classroom 397 26 955 21 21 Unit Ventilator
411 Classroom 576 38 947 21 21 Unit Ventilator
412 Classroom 352 23 1474 33 23 Unit Ventilator
413 Classroom 307 20 208 4 4 Unit Ventilator
414 Classroom 313 20 1255 28 20 Unit Ventilator
415 Classroom 347 23 1215 27 23 Unit Ventilator
421 Classroom 0 Yes 1058 24 24 N/A
422 Classroom 463 30 1199 27 27 Unit Ventilator
423 Classroom 363 24 1327 30 24 Unit Ventilator
424 Classroom 300 20 1365 31 20 Unit Ventilator
425 Classroom 383 25 1350 30 25 Unit Ventilator
426 Classroom 450 30 1201 27 27 Unit Ventilator
427 Classroom 357 23 1242 28 23 Unit Ventilator
428 Classroom 390 26 1054 23 23 Unit Ventilator
A-01 A Art 599 39 1692 38 38 Unit Ventilator
A-02 Art 288 19 0 0 Unit Ventilator
A-03 A Art 648 43 1692 38 38 Unit Ventilator
- Boys Locker Room 1,404 93 700 15 15 AHU
- Girls Locker Room 1,531 102 700 15 15 AHU
Ground Level Pod #1 Auditorium Control room 0 0 102 2 0 AHU
Ground Level Pod #1 Center Core 163 10 528 12 10 AHU
Ground Level Pod #1 Center Core 297 19 1012 23 19 AHU
Ground Level Pod #1 Conference 38 2 150 3 2 AHU
Ground Level Pod #1 Counselor 0 0 80 1 0 AHU
Ground Level Pod #1 Entryway 0 0 238 5 0 AHU
Ground Level Pod #1 Entryway 32 2 238 5 2 AHU
Ground Level Pod #1 Lobby 113 7 1625 36 7 AHU
Ground Level Pod #1 Lobby Entryway 55 3 238 5 3 AHU
Ground Level Pod #1 Main Office - Waiting 143 9 1550 35 9 AHU
Ground Level Pod #1 Main Office 1 63 4 130 2 2 AHU
Ground Level Pod #1 Main Office 2 74 4 231 5 4 AHU
Ground Level Pod #1 Main Office 3 41 2 110 2 2 AHU
Ground Level Pod #1 Main Office 4 135 9 156 3 3 AHU
Ground Level Pod #1 Office 28 1 143 3 1 AHU
Ground Level Pod #1 Office Floor 0 0 500 11 0 AHU
Ground Level Pod #1 Ticket Booth 0 0 0 0 AHU
Ground level Pod #2 Cafeteria 374 24 2900 65 24 AHU
Ground level Pod #2 Center Core 68 4 400 9 4 AHU
Ground level Pod #2 Entryway 32 2 300 6 2 AHU
Ground level Pod #2 Office 8 0 0 0 AHU
Ground level Pod #2 Pod Center Core 116 7 925 21 7 AHU
Ground Level Pod #3 Cafeteria 59 3 2900 65 3 AHU
Ground Level Pod #3 Center Core 272 18 425 9 9 AHU
Ground Level Pod #3 Entryway 68 4 460 10 4 AHU
Ground Level Pod #3 Pod Center Core 174 11 900 20 11 AHU
Ground Level Pod #3 Pod Center Prep 30 2 945 21 2 AHU
Ground level Pod #4 Center Ring - Counselor 34 2 110 2 2 AHU
Ground level Pod #4 Center Ring - Police 0 0 187 4 0 AHU
Ground level Pod #4 Center Ring - Social Work 36 2 110 2 2 AHU
Ground Level Pod #4 Mayfair Center Core 63 4 425 9 4 AHU
Ground Level Pod #4 Mayfair Conference 27 1 156 3 1 AHU
Ground Level Pod #4 Mayfair Entry way 0 0 204 4 0 AHU
Ground Level Pod #4 Mayfair Nurse Office 0 0 216 4 0 AHU
Ground Level Pod #4 Mayfair Office 0 0 144 3 0 AHU
Ground Level Pod #4 Mayfair Pod Center Core 21 1 969 22 1 AHU
Ground Level Pod #4 Mayfair Pod Center Prep 0 0 646 14 0 AHU
Ground Level Pod #4 Mayfair Principal Office 0 0 190 4 0 AHU
Ground Level Pod #4 Nurse Exam 62 4 54 1 1 AHU
Ground Level Pod #4 Nurse Office 93 6 420 9 6 AHU
Ground Level Pod #4 Roster Area Entry 134 8 150 3 3 AHU
Ground Level Pod #4 Roster Room 64 4 80 1 1 AHU
- Gym 3,715 247 3700 84 84 AHU
Lower Level Pod #2 M-1 Band - Ensemble 60 4 459 10 4 AHU
Lower Level Pod #2 M-1 Band - Office 30 2 600 13 2 AHU
Lower Level Pod #2 M-1 Band - Practice 1 59 3 450 10 3 AHU
Lower Level Pod #2 Math Rm - Office 30 2 104 2 2 AHU
Lower Level Pod #2 Math Rm - Storage 0 0 50 1 0 AHU
Lower Level Pod #2 Storage 0 0 0 0 AHU
Lower Level Pod #2 Visual Com. Lab - Darkroom 58 3 380 8 3 AHU
Lower Level Pod #4 Center Core Art-01,02,03 60 4 1692 38 4 AHU
Lower Level Pod #4 Center Core Storage 21 1 0 0 AHU
Lower Level Pod #4 Classroom #3 Office 25 1 144 3 1 AHU
Lower Level Pod #4 Classroom #3 Prep 27 1 50 1 1 AHU
Lower Level Pod #4 Classroom #3 Storage 24 1 126 2 1 AHU
Lower Level Pod #4 M-5 Band Rm Ensemble 46 3 1734 39 3 AHU
Lower Level Pod #4 M-5 Band Rm Office 0 0 100 2 0 AHU
Lower Level Pod #4 M-5 Band Rm Practice 1 0 0 40 0 0 AHU
Lower Level Pod #4 M-5 Band Rm Practice 2 0 0 40 0 0 AHU
M-1 B Band Room 323 21 1178 26 21 Unit Ventilator
M-5 Band Room 0 0 1734 39 0 Unit Ventilator
Math Lab Classroom 338 22 1337 30 22 Unit Ventilator
S-01 A Power Tech Lab 312 20 1472 33 20 Unit Ventilator
S-02 A Engineering Lab 797 53 1985 45 45 Unit Ventilator
S-03 Visual Comm. Lab 321 21 1379 31 21 Unit Ventilator
Technology Lab Classroom 326 21 1025 23 21 Unit Ventilator
- Auditorium   4,818 321 4485 101 101 AHU
Upper Level Mayfair Multi-Purpose Room 835 55 5781 131 55 AHU
129A Upper Level Pod #1 Classroom 264 17 731 16 16 AHU
Upper Level Pod #1 Core 309 20 540 12 12 AHU
Upper Level Pod #1 Deans Office 355 23 480 10 10 AHU
Upper Level Pod #1 Pod Center Core 0 0 616 14 0 AHU
430 Upper Level Multi-Purpose Mayfair Classroom 90 6 Yes 1249 28 28 AHU
431 Upper Level Multi-Purpose Mayfair Classroom 136 9 Yes 789 17 17 AHU
Upper Level Pod #2 Core 0 0 425 9 0 AHU
432 Upper Level Pod #2 Lab B/C (Mayfair Room) 212 14 Yes 928 21 21 AHU
433 Upper Level Pod #2 Mayfair Kindergarten (Mayfair Room) 184 12 Yes 1145 26 26 AHU
Upper Level Pod #2 Pod Center Core 0 0 2968 67 0 AHU
Upper Level Pod #3 Center Core 0 0 616 14 0 AHU
Upper Level Pod #3 Lab C Classroom 187 12 806 18 12 AHU
Upper Level Pod #3 Lab Office 28 1 120 2 1 AHU
Upper Level Pod #3 Pod Center Core 0 0 2968 67 0 AHU
Upper Level Pod #4 Mayfair Center Core 174 11 4366 99 11 AHU
429 Upper Level Pod #4 Mayfair Classroom 263 17 1008 22 17 AHU
Upper Level Pod #4 Mayfair Counselor Office 79 5 132 3 3 AHU
Upper Level Pod #4 Mayfair Multi-Purpose Room 424 28 4662 105 28 AHU
Upper Level Pod #4 Mayfair Principal Office 83 5 180 4 4 AHU
Weight Room Classroom 107 7 210 4 4 AHU
Sheet Last Modified: 04-27-2021      
School:  William M. Meredith Elementary-Middle School
  William M. Meredith Elementary-Middle School Modular Building
Vendor: Capital    
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
B5 Classroom 0 Yes 696 15 15
102 Classroom 0 Yes 690 15 15
103 Classroom 0 Yes 690 15 15
104 Classroom 0 Yes 690 15 15
105 Classroom 0 Yes 920 20 20
106 Classroom 0 Yes 816 18 18
107 Classroom 0 Yes 664 15 15
108 Classroom 0 Yes 664 15 15
201 Classroom 0 Yes 667 15 15
202 Classroom 0 Yes 690 15 15
204.5 Classroom 0 Yes 425 9 9
205 Classroom 0 Yes 782 17 17
206 Classroom 0 Yes 759 17 17
206A Classroom 0 Yes 368 8 8
207 Classroom 0 Yes 506 11 11
208 Classroom 0 Yes 664 15 15
301 Classroom 0 Yes 696 15 15
302 Classroom 0 Yes 682 15 15
303 Classroom 0 Yes 638 14 14
304 Classroom 0 Yes 667 15 15
305 Classroom 0 Yes 1,210 27 27
306 Classroom 0 Yes 782 17 17
307 Classroom 0 Yes 667 15 15
308 Classroom 0 Yes 667 15 15
309 Classroom 0 Yes 648 14 14
309A Classroom 0 420 9 0
- Auditorium 0 3,185 72 0
- Counselors Office 0 Yes 375 8 8
- Gym 0 3,723 84 0
- Library  0 Yes 1,298 29 29
- Lunchroom 0 2,250 51 0
- Main office 0 Yes 368 8 8
- Nurses Office 0 Yes 168 3 3
- Principals office 0 Yes 256 5 5
- Psych Office #1 0 138 3 0
- Psych Office #2 0 88 2 0
- Teachers Lounge 0 322 7 0
Modular Building
1 Classroom 368 24 720 16 16 AHU
2 Classroom 378 25 720 16 16 AHU
3 Classroom 381 25 720 16 16 AHU
4 Classroom 374 24 720 16 16 AHU
Sheet Last Modified: 04-26-2021    
School:  Thomas Mifflin Elementary School
Vendor: EMCOR Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 253 16 Yes 794 18 18 Unit Ventilator
102 Classroom 555 37 1040 23 23 Unit Ventilator
103 Classroom 288 19 375 8 8 Unit Ventilator
104 Classroom 270.0 18 537 12 12 Unit Ventilator
105 Classroom 395 26 484 11 11 Unit Ventilator
106 Classroom 422 28 682 15 15 Unit Ventilator
107 Classroom 330 22 658 14 14 Unit Ventilator
108 Classroom 439 29 690 15 15 Unit Ventilator
109 Classroom 230 15 662 15 15 Unit Ventilator
110 Classroom 348 23 669 15 15 Unit Ventilator
111 Classroom 587 39 531 12 12 Unit Ventilator
114 Classroom 0 0 Yes 630 14 14 Unit Ventilator
115 Classroom 0 0 Yes 684 15 15 Unit Ventilator
128 (117) Counselor Office 376 25 350 7 7 Unit Ventilator
201 Classroom 595 39 775 17 17 Unit Ventilator
202 Classroom 638 42 764 17 17 Unit Ventilator
203 Classroom 300 20 340 7 7 Unit Ventilator
204 Classroom 354 23 639 14 14 Unit Ventilator
205 Classroom 458 30 682 15 15 Unit Ventilator
206 Classroom 432 28 688 15 15 Unit Ventilator
207 Classroom 606 40 686 15 15 Unit Ventilator
209 Classroom 241 16 686 15 15 Unit Ventilator
210 Classroom 598 39 1380 31 31 Unit Ventilator
211 Classroom 408 27 690 15 15 Unit Ventilator
212 Meeting Room 1055 70 312 7 7 Unit Ventilator
215 Classroom 0 Yes 323 7 7 Unit Ventilator
- Auditorium 0 0 3837 87 0 House Fan
- Cafeteria 270 18 Yes 2128 48 48 Unit Ventilator
- Cafeteria Hall 0 0 738 16 0 Unit Ventilator
- Library 403 26 3024 68 26 Unit Ventilator
- Music Room 425 28 966 21 21 Unit Ventilator
Pre-K 3 Classroom 489 32 972 22 22 Unit Ventilator
Pre-K 4 Classroom 335 22 920 20 20 Unit Ventilator
- Main Office 0 Yes 552 12 12
- Principal Office 0 Yes 390 8 8
- Nurses Office 0 Yes 192 4 4
- Gym 4,205.00 280 5280 120 120 RTU
6 Speech 0 Yes 544 12 12
8 Classroom 0 Yes 851 19 19
20 Special Needs 0 Yes 661 15 15
- Spanish Classroom 0 0 Yes 900 20 20 Unit Ventilator
   
   
   
   
   
   
   
   
   
   
   
   
   
   
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sheet Last Modified: 04-28-2021    
School:  E. Spencer Miller- Philadelphia Learning Academy South (9-12) and Crossroads Acelerated Academy (7-8)
Vendor: Goldner
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
153 Office 0 0 187 4 0
158 School Police Office 267 17 540 12 12
167 Staff Lounge 0 0 532 12 0
170 Office 0 0 99 2 0
175 Office 0 0 154 3 0
181 Office 49 3 344 7 3
183 Office 10 0 110 2 0
184 Office 7 0 100 2 0
185 Office 17 1 220 5 1
186 Office 27 1 208 4 1
188 Office 201 13 77 1 1
192 Office 289 19 111 2 2
245 Office 17 1 170 3 1
246 Office 41 2 131 2 2
247 Office 33 2 167 3 2
248 Office 0 0 152 3 0
252 Office 0 0 516 11 0
254 Office 166 11 231 5 5
255 Office 46 3 98 2 2
256 Office 94 6 140 3 3
257 Office 396 26 120 2 2
258 Office 58 3 531 12 3
262 Office 111 7 102 2 2
266 Office 762 50 381 8 8
267 Office 949 63 437 9 9
274 Office 192 12 148 3 3
275 Office 130 8 117 2 2
276 Office 72 4 101 2 2
277 Office 176 11 147 3 3
278 Office 107 7 109 2 2
279 Office 104 6 106 2 2
280 Office 287 19 254 5 5
282 Office 311 20 272 6 6
286 Office 636 42 290 6 6
287 Office 104 6 107 2 2
290 Office 108 7 132 3 3
291 Office 107 7 151 3 3
292 Office 210 14 150 3 3
293 Office 186 12 153 3 3
- 1st Flr Computer Room 0 0 240 5 0
- 1st Flr Corrider by B & E Section 0 0 320 7 0
- 1st Flr Kitchen 8,316.00 554 924 21 21
- 1st Flr Kitchen Dry Food Area 171 11 187 4 4
- 1st Flr Kitchen Freezer Area 85 5 420 9 5
- 1st Flr Mechanical Room 19 1 336 7 1
- 2nd Floor Conference Room 359 23 216 4 4
- 2nd Floor Corridor by Elevator 363 24 463 10 10
- 2nd Floor Meeting Room 139 9 79 1 1
- 2nd Floor Mens Restroom by Elevator 138 9 255 5 5
- 2nd Floor Restroom Vestibule by Elevator 157 10 73 1 1
- 2nd Floor Womans Restroom by Elevator 114 7 167 3 3
- 2nd Flr Corridor by Admin Office 195 13 218 4 4
- 2nd Flr Corridor by G Section 45 3 458 10 3
- 2nd Flr Reception Office 170 11 116 2 2
- 1st Flr A - Common Area 48 3 1251 28 3
A1 Classroom 58 3 960 21 3
A2 Classroom 66 4 990 22 4
A3 Classroom 60 4 990 22 4
A4 Classroom 56 3 997 22 3
- 1st Flr B - Common Area 747 49 960 21 21
B1 Classroom 304 20 868 19 19
B2 Classroom 488 32 945 21 21
B3 Classroom 942 62 980 22 22
B4 Classroom 961 64 910 20 20
- C - Common Area 1st Flr 1,014.00 67 1285 29 29
C-1 Classroom 885 59 816 18 18
C-2 Classroom 1,047.00 69 840 19 19
C-3 Classroom 1,200.00 80 840 19 19
C-4 Classroom 828 55 868 19 19
- Climate Masters Office 150 10 821 18 10
- Computer Support Specialist Office 102 6 88 2 2
- Corridor 2nd Floor near office 252 0 0 376 8 0
- 1st Flr Corridor By B Section 0 0 360 8 0
- Corridor by D Section 713 47 438 9 9
- Corridor by Main Office 38 2 610 13 2
- Corridor by Office 258 107 7 160 3 3
- 2nd Flr D - Common Area 202 13 910 20 13
D1 Classroom 206 13 960 21 13
D2 Classroom 132 8 901 20 8
D3 Classroom 268 17 1007 22 17
D4 Classroom 209 13 972 22 13
- Dr. Graham Principal Office 111 7 823 18 7
- 2nd Flr E - Common Area 431 28 934 21 21
E1 Classroom 633 42 919 20 20
E2 Classroom 593 39 1021 23 23
E3 Classroom 594 39 1046 23 23
E4 Classroom 647 43 984 22 22
- 2nd Flr G - Common Area 12 0 1214 27 0
G1 Classroom 40 2 862 19 2
G2 Classroom 29 1 878 19 1
G3 Classroom 26 1 884 20 1
G4 Classroom 33 2 872 19 2
- 1 st Flr Gym 5,785.00 385 3888 88 88
- Late Check Office 0 0 96 2 0
- Main Entrance 5 0 64 1 0
- 1st Flr Media Room 524 34 1539 34 34
- Meeting Room 21 1 90 2 1
- Mens Restroom by Elevator 26 1 190 4 1
- Nurses Office 584 38 412 9 9
- Office Corridor 228 15 702 15 15
- Parking Lot Entry 0 0 135 3 0
- Reception 47 3 521 11 3
- Restroom Vestibule Between A1/A2 6 0 56 1 0
- Restroom Vestibule Between A3/A4 4 0 56 1 0
- Restroom Vestibule Between B1/B2 83 5 63 1 1
- Restroom Vestibule Between B3/B4 49 3 63 1 1
- Restroom Vestibule Between C1/C2 89 5 56 1 1
- Restroom Vestibule Between C3/C4 93 6 63 1 1
- Restroom Vestibule Between D1/D2 20 1 50 1 1
- Restroom Vestibule Between D3/D4 27 1 51 1 1
- Restroom Vestibule Between E1/E2 55 3 51 1 1
- Restroom Vestibule Between E3/E4 54 3 51 1 1
- Restroom Vestibule Between G1/G2 3 0 50 1 0
- Restroom Vestibule Between G3/G4 2 0 51 1 0
- 1st Flr Storage Room 61 4 475 10 4
- Truancy Office 1st Floor 0 0 727 16 0
- Vestibule by stairs/Rooms 266 & 267 153 10 219 4 4
- Vistibule by Meeting Room 132 8 252 5 5
- Womans Restroom by 1st Floor Elevator 26 1 169 3 1
Sheet Last Modified: 05-03-2021          
School:  Mitchell Elementary School      
  EMCOR      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom  0 Yes 704 16 16 House Fan
102 Classroom  0 Yes 704 16 16 House Fan
103 Classroom  0 Yes 704 16 16 House Fan
104 Classroom  0 Yes 704 16 16 House Fan
105 Classroom  0 Yes 704 16 16 House Fan
106 Classroom  0 Yes 704 16 16 House Fan
107 Classroom  0 Yes 704 16 16 House Fan
108 Classroom  0 Yes 704 16 16 House Fan
109 Classroom  0 Yes 704 16 16 House Fan
110 Counselor's Office 0 Yes 255 5 5 House Fan
111 Classroom  0 Yes 704 16 16 House Fan
112 Classroom  0 Yes 704 16 16 House Fan
213 Classroom  0 Yes 704 16 16 House Fan
214 Classroom  0 Yes 704 16 16 House Fan
215 Classroom  0 Yes 704 16 16 House Fan
216 Classroom  0 Yes 704 16 16 House Fan
217 Classroom  0 Yes 704 16 16 House Fan
218 Classroom  0 Yes 704 16 16 House Fan
219 Classroom  0 Yes 704 16 16 House Fan
220 Classroom  0 Yes 704 16 16 House Fan
221 Classroom  0 Yes 704 16 16 House Fan
222 Classroom  0 Yes 704 16 16 House Fan
223 Classroom  0 Yes 704 16 16 House Fan
225 Nurse 0 Yes 378 8 8 House Fan
324 Classroom  0 Yes 704 16 16 House Fan
325 Classroom  0 Yes 704 16 16 House Fan
326 Classroom  0 Yes 704 16 16 House Fan
327 Classroom  0 Yes 704 16 16 House Fan
328 Classroom  0 Yes 704 16 16 House Fan
329 Classroom  0 Yes 704 16 16 House Fan
330 Classroom  0 Yes 704 16 16 House Fan
331 Classroom  0 Yes 704 16 16 House Fan
332 Classroom  0 Yes 704 16 16 House Fan
333 Classroom  0 Yes 704 16 16 House Fan
334 Classroom  0 Yes 704 16 16 House Fan
B1 Classroom 0 Yes 756 17 17 Unit Ventilator
B2 B.E. Office 0 Yes 200 4 4
B3 Classroom 0 Yes 609 13 13 Unit Ventilator
B4 Classroom 0 Yes 980 22 22 Unit Ventilator
B6 Classroom 0 Yes 1,344 30 30 Unit Ventilator
- SP Office 0 Yes 88 2 2
- Library 0 Yes 1,504 34 34
- Gym 0 Yes 3,495 79 79 House Fan
- Cafeteria Office  0 Yes 134 3 3
- Cafeteria 0 Yes 2,452 55 55 House Fan
- Main Office 0 Yes 494 11 11 House Fan
- Principal's Office 0 Yes 216 4 4 House Fan
110C Vice Principal's Office 0 Yes 101 2 2
110A Administrative Assistant's Office 0 Yes 191 4 4
- Teacher's Lounge/Multipurpose 0 Yes 390 8 8 House Fan
110B Counselor's Office 0 Yes 242 5 5 House Fan
Sheet Last Modified: 04-19-2021      
School:  The Promise Academy @ Martin Luther King High School
Vendor: Meehan (Auditorium) Chadwick (Building) Exhaust  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 464 30 828 18 18
102 Classroom 315 21 828 18 18
104 Classroom 260 17 900 20 17
105 Classroom 162 10 1050 23 10
106 Classroom 476 31 900 20 20
107 Classroom 229 15 864 19 15
108 Classroom 489 32 850 19 19
109 Classroom 304 20 896 20 20
110 Classroom 0 800 18 0
116 Classroom 0 800 18 0
117 Classroom 296 19 924 21 19
118 Classroom 278 18 864 19 18
120 Classroom 105 7 864 19 7
121 Classroom 176 11 864 19 11
122 Classroom 420 28 1152 26 26
123 Classroom 86 5 864 19 5
124 Classroom 252 16 900 20 16
125 Classroom 203 13 864 19 13
201 Classroom 215 14 828 18 14
202 Classroom 201 13 864 19 13
204 Classroom 0 900 20 0
205 Classroom 416 27 1050 23 23
206 Classroom 47 3 900 20 3
207 Classroom 90 6 864 19 6
208 Classroom 212 14 850 19 14
209 Classroom 360 24 896 20 20
210 Classroom 0 0 800 18 0
216 Classroom 469 31 800 18 18
217 Classroom 130 8 924 21 8
218 Classroom 293 19 864 19 19
220 Classroom 318 21 864 19 19
221 Classroom 204 13 864 19 13
222 Classroom 210 14 1152 26 14
223 Classroom 170 11 864 19 11
224 Classroom 207 13 900 20 13
225 Classroom 150 10 864 19 10
301 Classroom 161 10 828 18 10
302 Classroom 178 11 864 19 11
303 Classroom 0 Yes 805 18 18
304 Classroom 391 26 900 20 20
305 Classroom 244 16 1050 23 16
306 Classroom 347 23 900 20 20
307 Classroom 99 6 864 19 6
308 Classroom 217 14 850 19 14
309 Classroom 65 4 896 20 4
310 Classroom 347 23 800 18 18
313 Classroom 0 Yes 1368 31 31
316 Classroom 297 19 800 18 18
317 Classroom 201 13 924 21 13
318 Classroom 275 18 864 19 18
320 Classroom 303 20 864 19 19
321 Classroom 85 5 864 19 5
322 Classroom 310 20 1152 26 20
323 Classroom 310 20 864 19 19
324 Classroom 213 14 900 20 14
325 Classroom 84 5 864 19 5
327 Classroom 0 Yes 1824 41 41
- Auditorium 13,590 906 4350 98 98
Sheet Last Modified: 03-18-2021    
School:  John Moffet Elementary School
Vendor: Devine Brothers Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101A Classroom 97.0 6 360 8 6 AHU
104 Classroom 225.0 15 704 16 15 Unit Ventilator
105 Classroom 205.0 13 575 13 13 Unit Ventilator
107 Classroom 271.0 18 805 18 18 Unit Ventilator
108 Classroom 327.0 21 782 17 17 Unit Ventilator
112 Classroom 524.0 34 896 20 20 Unit Ventilator
113 Classroom 293.0 19 928 21 19 Unit Ventilator
114 Classroom 441.0 29 986 22 22 Unit Ventilator
115 Classroom 337.0 22 868 19 19 Unit Ventilator
119 Nurse 178.0 11 77 1 1 AHU
201 Classroom 105.0 7 315 7 7 Unit Ventilator
202 Classroom 745.0 49 891 20 20 Unit Ventilator
203 Classroom 301.0 20 754 17 17 Unit Ventilator
204 Classroom 357.0 23 754 17 17 Unit Ventilator
205 Classroom 267.0 17 667 15 15 Unit Ventilator
208 Classroom 183.0 12 924 21 12 Unit Ventilator
209 Classroom 542.0 36 667 15 15 Unit Ventilator
211 Classroom 543.0 36 648 14 14 Unit Ventilator
213 Classroom 114.0 7 352 8 7 Unit Ventilator
214 Classroom 210.0 14 957 21 14 Unit Ventilator
215 Classroom 261.0 17 754 17 17 Unit Ventilator
216 Classroom 470.0 31 754 17 17 Unit Ventilator
217 Classroom 666.0 44 957 21 21 Unit Ventilator
218 Classroom 260.0 17 330 7 7 Unit Ventilator
219 Classroom 0.0 0 1100 25 0 Unit Ventilator
221 Classroom 449.0 29 884 20 20 Unit Ventilator
223 Classroom 403.0 26 340 7 7 AHU
225 Classroom 266.0 17 858 19 17 Unit Ventilator
228A Classroom 60.0 4 252 5 4 AHU
229 Classroom 47.0 3 336 7 3 AHU
- Auditorium 773.0 51 2478 56 51 AHU
- Faculty Lounge 125.0 8 361 8 8 Unit Ventilator
- Library 1,025.0 68 1674 38 38 AHU
- Office 110.0 7 70 1 1 AHU
- Main Office 87.0 5 496 11 5 Unit Ventilator
- Principals Office 140.0 9 294 6 6 Unit Ventilator
Sheet Last Modified: 04-26-2021    
School:  J. Hampton Moore Elementary School
  Mobile Classrooms Main Building Little School House
Vendor: Devine Main Retest LSH Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Moore Main
- Auditorium 224 14 3015 68 14 AHU
- Gym 145 9 Yes 4500 102 102 AHU
101 Classroom 518 34 1055 23 23 Univent
102 Classroom 504 33 1055 23 23 Univent
103 Classroom 364 24 624 14 14 Univent
104 Classroom 116 7 Yes 458 10 10 Univent
105 Classroom 408 27 1082 24 24 Univent
106 Classroom 237 15 Yes 951 21 21 Univent
107 Classroom 535 35 951 21 21 Univent
108 Classroom 503 33 951 21 21 Univent
109 Classroom 220 14 Yes 951 21 21 Univent
110 Classroom 113 7 Yes 951 21 21 Univent
110A Classroom 237 15 951 21 15 Univent
112 Classroom 325 21 951 21 21 Univent
113 Classroom 472 31 951 21 21 Univent
114 Classroom 487 32 951 21 21 Univent
115 Classroom 236 15 383 8 8 Univent
201 Classroom 480 32 976 22 22 Univent
202 Classroom 319 21 976 22 21 Univent
203 Classroom 251 16 Yes 951 21 21 Univent
203B Classroom 0 Yes 624 14 14
204 Classroom 291 19 Yes 951 21 21 Univent
205A Classroom 261 17 Yes 452 10 10 Univent
205B Classroom 130 8 Yes 642 14 14 Univent
206 Classroom 326 21 970 22 21 Univent
207 Classroom 424 28 951 21 21 Univent
207A Classroom 0 Yes 239 5 5 N/A
208 Classroom 527 35 951 21 21 Univent
209 Classroom 399 26 951 21 21 Univent
210A Classroom 108 7 Yes 458 10 10 Univent
210B Classroom 335 22 Yes 458 10 10 Univent
211 Classroom 433 28 951 21 21 Univent
212 Classroom 244 16 Yes 951 21 21 Univent
213 Classroom 0 0 Yes 951 21 21 Univent
214 Classroom 64 4 Yes 820 18 18 Univent
215 Classroom 454 30 951 21 21 Univent
216 Classroom 444 29 951 21 21 Univent
217 Classroom 520 34 951 21 21 Univent
218 Classroom 347 23 951 21 21 Univent
219 Counselor Office 0 Yes 170 3 3
- Principals Office 0 0 Yes 400 9 9
Assistant Principal Office 0 Yes 172 3 3
Teachers Lounge Room 0 Yes 170 3 3
2nd Floor Copy Room Room 0 Yes 172 3 3
- Nurse Office 0 0 Yes 800 18 18 Univent
Moore LSH
- Office 224 14 200 4 4 FCU
- Kitchen 145 9 624 14 9 FCU
- Faculty Lounge 130 8 Yes 200 4 4 FCU
P101 Classroom 0 Yes 120 2 2
P102 Classroom 0 Yes 120 2 2
P110 Classroom 361 24 950 21 21 Univent
P111 Classroom 593 39 950 21 21 Univent
P112 Classroom 379 25 950 21 21 Univent
P113 Classroom 463 30 950 21 21 Univent
P114 Classroom 747 49 950 21 21 Univent
P114 Hallway 130 8 780 17 8 FCU
P115 Classroom 361 24 950 21 21 Univent
P116 Classroom 491 32 950 21 21 Univent
P117 Classroom 430 28 950 21 21 Univent
P124 Classroom 999 66 950 21 21 Univent
P124 Hallway 80 5 1122 25 5 FCU
P125 Classroom 476 31 950 21 21 Univent
P126 Classroom 304 20 950 21 20 Univent
P127 Classroom 1009 67 950 21 21 Univent
Moore Modular
A-1 Classroom 568 37 781 17 17 Univent
A-2 Classroom 453 30 781 17 17 Univent
A-3 Classroom 441 29 781 17 17 Univent
A-4 Classroom 360 24 781 17 17 Univent
A-5 Classroom 214.0 14 Yes 781 17 17 Univent
A-6 Classroom 125.0 8 Yes 781 17 17 Univent
A-7 Classroom 465.0 31 781 17 17 Univent
A-8 Classroom 629.0 41 781 17 17 Univent
Sheet Last Modified: 04-12-2021    
School:  Robert Morris Elementary School
Vendor: EMCOR Fluidics
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 192 12 Yes 1284 29 29 Univent
101 Classroom 171 11 Yes 1410 32 32 Univent
200 Classroom 185 12 Yes 858 19 19 Univent
201 Classroom 72 4 Yes 603 13 13 Univent
202 Classroom 218 14 849 19 14 Univent
203 Classroom 200 13 Yes 821 18 18 Univent
204 Classroom 163 10 Yes 846 19 19 Univent
206 Classroom 85 5 847 19 5 Univent
208 Classroom 152 10 830 18 10 Univent
210 Classroom 0 0 837 19 0 Univent
212 Lunch Room 137 9 876 19 9 Univent
213 Classroom 74 4 875 19 4 Univent
214 Classroom 125 8 848 19 8 Univent
215 Classroom 286 19 840 19 19 Univent
216 Classroom 94 6 848 19 6 Univent
217 Classroom 114 7 Yes 463 10 10 Univent
218 Classroom 283 18 1037 23 18 Univent
219 Kitchen 261 17 1204 27 17 Univent
300 Classroom 86 5 Yes 856 19 19 Univent
301 Classroom 273 18 601 13 13 Univent
302 Classroom 225 15 848 19 15 Univent
303 Classroom 266 17 818 18 17 Univent
304 Classroom 86 5 843 19 5 Univent
306 Classroom 169 11 849 19 11 Univent
308 Classroom 129 8 Yes 828 18 18 Univent
310/312/314 Library 734 48 2102 47 47 Univent
313 Classroom 264 17 975 22 17 Univent
315 Classroom 217 14 1220 27 14 Univent
316 Classroom 139 9 845 19 9 Univent
317 Classroom 152 10 Yes 462 10 10 Univent
319 Art Room 0 0 Yes 1042 23 23 Univent
400 Classroom 58 3 857 19 3 Univent
401 Classroom 121 8 Yes 602 13 13 Univent
402 Classroom 169 11 846 19 11 Univent
403 Classroom 498 33 817 18 18 Univent
404 Classroom 92 6 848 19 6 Univent
406 Classroom 60 4 845 19 4 Univent
408 Classroom 55 3 Yes 829 18 18 Univent
410 Classroom 0 0 849 19 0 Univent
412 Lunch Room 106 7 858 19 7 Univent
413 Classroom 313 20 871 19 19 Univent
414 Classroom 291 19 847 19 19 Univent
415 Classroom 147 9 Yes 836 19 19 Univent
416 Classroom 106 7 Yes 847 19 19 Univent
417 Faculty 158 10 446 10 10 Univent
418 Classroom 34 2 Yes 1044 23 23 Univent
419 Music Room 511 34 1040 23 23 Univent
- Auditorium 1066 71 5308 120 71 Univent
- Counselor's Office 70 4 474 10 4 Univent
- Gymnasium 1,100 73 3688 83 73 Univent
- Nurse's Office 0 Yes 261 5 5 N/A
- Principal's Office 0 Yes 294 6 6 N/A
- Main Office 387 25 1373 31 25 Univent
Sheet Last Modified: 03-18-2021    
School:  Andrew Morrison Elementary School
Vendor: EMCOR Fluidics EMCOR Retest 1-15-21 Retest 2-22-21
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
5 Music Rm 0 Yes 813 18 18 House Fan
8 Art Rm 0 Yes 886 20 20 House Fan
101A Nurse 0 Yes 376 8 8 House Fan
101B Counselor 0 341 7 0 House Fan
102 Classroom 0 Yes 701 15 15 House Fan
103 Classroom 0 Yes 734 16 16 House Fan
104 Classroom 0 Yes 660 15 15 House Fan
106 Lounge 0 Yes 526 11 11 House Fan
107 Classroom 0 Yes 660 15 15 House Fan
108 Classroom 0 Yes 566 12 12 House Fan
109 Classroom 376 25 765 17 17 Univent
110 Classroom 427 28 792 18 18 Univent
111 Classroom 408 27 781 17 17 Univent
112 Classroom 469 31 792 18 18 Univent
113 Classroom 380 25 767 17 17 Univent
114 Office / Classroom 271 18 351 7 7 Univent
115 Gym 0 4693 106 0 House Fan
200 Office 0 168 3 0 House Fan
201 Classroom 0 726 16 0 House Fan
202 Classroom 0 696 15 0 House Fan
203 Classroom 0 731 16 0 House Fan
204 Classroom 0 718 16 0 House Fan
204A Office 0 322 7 0 House Fan
204B Office 0 Yes 150 3 3 N/A
204C Office 0 84 1 0 N/A
205 Classroom 0 698 15 0 House Fan
206 Classroom 0 690 15 0 House Fan
207 Classroom 0 698 15 0 House Fan
208 Classroom 0 643 14 0 House Fan
212 Classroom 48 3 398 9 3 Univent
213 Classroom 194 12 742 16 12 Univent
214 Classroom 197 13 864 19 13 Univent
215 Office 0 0 100 2 0 Univent
216 Classroom 411 27 762 17 17 Univent
217 Classroom 365 24 734 16 16 Univent
218 Office / Classroom 269 17 356 8 8 Univent
300 Classroom 0 644 14 0 House Fan
301a Office 0 163 3 0 House Fan
302 Classroom 0 688 15 0 House Fan
303 Classroom 0 736 16 0 House Fan
304 Classroom 0 666 15 0 House Fan
306 Classroom 0 1085 24 0 House Fan
306A Library 0 1166 26 0 House Fan
307 Classroom 0 687 15 0 House Fan
308 Classroom 0 798 18 0 House Fan
312 Classroom 224 14 1070 24 14 Rooftop Unit
313 Classroom 0 0 944 21 0 Rooftop Unit
314 Classroom 332 22 1117 25 22 Rooftop Unit
314 Office 0 0 372 8 0 Univent
314A Office 0 372 8 0 House Fan
315A Teacher's Lounge 0 0 294 6 0 Univent
316 Office / Classroom 130 8 356 8 8 Rooftop Unit
- Auditorium 0 3657 83 0 House Fan
- Gym 857 57 4693 106 57 Univent
- Lunch Rm  0 4331 98 0 House Fan
- Main Office 0 Yes 395 8 8 House Fan
- Principals Office 0 Yes 269 6 6 House Fan
Sheet Last Modified: 04-23-2021    
School:  Thomas G. Morton Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 0 0 Yes 988 22 22 Univent
101 Classroom 0 0 Yes 875 19 19 Univent
102 Classroom 374 24 792 18 18 Air Coil Unit
104B Storage 77 5 84 1 1 Univent
108A Nurse Office 125 8 90 2 2 Univent
108B Audio 40 2 224 5 2 Univent
108C Examination 36 2 234 5 2 Univent
110 Classroom 0 0 513 11 0 Univent
111 Classroom 309 20 Yes 252 5 5 Univent
200 Classroom 0 0 Yes 1071 24 24 Univent
201 Classroom 0 0 Yes 754 17 17 Univent
202 Classroom 432 28 Yes 754 17 17 Univent
203 Classroom 475 31 8112 184 31 Univent
204 Classroom 399 26 438 9 9 Univent
205 Classroom 0 0 Yes 1015 23 23 Univent
206 Classroom 0 0 Yes 1305 29 29 Univent
207 Classroom 0 0 Yes 1305 29 29 Univent
208 Classroom 329 21 Yes 1015 23 23 Univent
209 Classroom 280 18 Yes 408 9 9 Univent
210 Classroom 0 0 Yes 725 16 16 Univent
211 Classroom 0 0 Yes 841 19 19 Univent
212 Classroom 0 0 Yes 264 6 6 Univent
213 Classroom 437 29 725 16 16 Univent
214A Classroom 94 6 190 4 4 Univent
214B Classroom 162 10 624 14 10 Univent
300 Classroom 309 20 780 17 17 Univent
301 Classroom 0 0 725 16 0 Univent
302 Classroom 685 45 240 5 5 Univent
303 Classroom 486 32 754 17 17 Univent
304 Classroom 448 29 Yes 725 16 16 Univent
305 Classroom 291 19 312 7 7 Univent
306 Classroom 483 32 Yes 754 17 17 Univent
307 Classroom 415 27 Yes 756 17 17 Univent
308 Library 1124 74 2975 67 67 Univent
308 Library Office 0 0 462 10 0 Univent
309 Classroom 283 18 Yes 806 18 18 Univent
310 Classroom 628 41 700 15 15 Univent
311 Classroom 294 19 754 17 17 Univent
312 Classroom 349 23 754 17 17 Univent
313 Classroom 547 36 486 11 11 Univent
315 Classroom 544 36 754 17 17 Univent
316 Classroom 324 21 754 17 17 Univent
317 Classroom 431 28 870 19 19 Univent
318 Classroom 305 20 312 7 7 Univent
319 Classroom 0 0 Yes 650 14 14 Univent
320 Classroom 431 28 728 16 16 Univent
- Auditorium 5700 380 2646 60 60 Air Coil Unit
- Cafeteria 2196 146 Yes 2726 61 61 Air Coil Unit
- Conference 83 5 171 3 3 Univent
- Counselors Office A 87 5 99 2 2 Univent
- Counselors Office B 91 6 128 2 2 Univent
- Counselors Office C 148 9 100 2 2 Univent
- Gym 1927 128 4640 105 105 Air Coil Unit
- Lounge 311 20 351 7 7 Univent
- Main Office 285 19 380 8 8 Univent
- Copy Room 53 3 60 1 1 Univent
- Nurse 83 5 123 2 2 Univent
- Principal Office 159 10 228 5 5 Univent
- Vice Principal Office 54 3 99 2 2 Univent
Sheet Last Modified: 04-29-2021    
School:  Motivation High School KIPP Turner West Middle School 
Vendor: Capital
Vendor: Devine Devine Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
A-PreK Corridor Corridor 314 20 600 13 13 Univent
A-PreK North Entrance-A Corridor 490 32 243 5 5 Univent
A-PreK North Entrance-B Corridor 548 36 480 10 10 Univent
A-PreK South Corridor Corridor 324 21 550 12 12 Univent
A-Wing Head Start Mech. Rm Head Start PreK A169 & A170 349 23 1440 32 23 Air Handling Unit
A-Wing-Café Mech. Rm 2nd & 3rd Flr. Staff Seminar Rms 1734 115 0 0 Air Handling Unit
A-Wing-Café Mech. Rm 3rd Flr 0 50 1 0 Air Handling Unit
A-Wing-Café Mech. Rm 2nd Flr 0 50 1 0 Air Handling Unit
A-Wing-Café Mech. Rm Ground Flr. Administration 351 23 0 0 Air Handling Unit
A130 Gym 410 27 2552 58 27 Heating Ventilation Unit
A108 Locker Rm A108 0 0 0 0 Heating Ventilation Unit
A152 Locker Rm A152 1340 89 690 15 15 Heating Ventilation Unit
A162 Storage A154 Corrective Gym 306 20 5192 118 20 Heating Ventilation Unit
A165 Storage 0 0 5,192 118 0 Heating Ventilation Unit
B-157 B-155 Fitness Rm 1593 106 1,150 26 26 Univent
MER Rm B146 B-Wing 555 37 1,012 23 23 Air Handling Unit
B-Wing B137 B-139 A, B, C, D 2003 133 4,134 93 93 Air Handling Unit
B101 Cafeteria B-Wing Roof 320 21 9,405 213 21 Air Handling Unit
House Coord North 3rd & 2nd Flr B-Wing Roof 67 4 0 0 Air Handling Unit
B318 B-Wing Roof 0 800 18 0 Air Handling Unit
B218 B-Wing Roof 0 800 18 0 Air Handling Unit
House Coord South 3rd & 2nd Flr B-Wing Roof 126 8 0 0 Air Handling Unit
B306 B-Wing Roof 0 800 18 0 Air Handling Unit
B206 B-Wing Roof 0 800 18 0 Air Handling Unit
B325 IMC Library B-Wing Roof 7 0 851 19 0 Air Handling Unit
139A Classroom 0 880 20 0
139B Classroom 0 987 22 0
139C Classroom 0 884 20 0
139D Classroom 0 1,035 23 0
151 Classroom 0 Yes 1824 41 41
152 Classroom 0 Yes 1,170 26 26
B196 Classroom 376 25 567 12 12 Univent
B197 Classroom 755 50 962 21 21 Univent
B198 Classroom 739 49 792 18 18 Univent
B200 Classroom 1468 97 1,564 35 35 Univent
B201 Classroom 673 44 850 19 19 Univent
B202 Classroom 172 11 748 17 11 Univent
B203 Classroom 673 44 748 17 17 Univent
B204 Classroom 143 9 759 17 9 Univent
B205 Classroom 555 37 720 16 16 Univent
B207 Classroom 629 41 748 17 17 Univent
B208 Classroom 640 42 759 17 17 Univent
B209 Classroom 108 7 816 18 7 Univent
B210 Classroom 630 42 720 16 16 Univent
B211 Classroom 350 23 720 16 16 Univent
B212 Classroom 538 35 1,326 30 30 Univent
B213 Classroom 244 16 759 17 16 Univent
B214 Classroom 0 0 759 17 0 Univent
B215 Classroom 341 22 748 17 17 Univent
B216 Classroom 339 22 748 17 17 Univent
B217 Classroom 273 18 624 14 14 Univent
B219 Classroom 378 25 748 17 17 Univent
B220 Classroom 242 16 759 17 16 Univent
B221 Classroom 456 30 816 18 18 Univent
B222 Classroom 633 42 598 13 13 Univent
B223 Classroom 642 42 690 15 15 Univent
B301 Classroom 200 13 850 19 13 Univent
B302 Classroom 129 8 748 17 8 Univent
B304 Classroom 630 42 1,564 35 35 Univent
B305 Classroom 150 10 720 16 10 Univent
306 Classroom 0 Yes 900 20 20
B307 Classroom 193 12 748 17 12 Univent
B308 Classroom 110 7 759 17 7 Univent
B309 Classroom 186 12 816 18 12 Univent
B310 Classroom 196 13 720 16 13 Univent
B311 Classroom 222 14 720 16 14 Univent
B312 Classroom 691 46 1,326 30 30 Univent
B313 Classroom 264 17 759 17 17 Univent
B314 Classroom 436 29 759 17 17 Univent
B315 Classroom 198 13 748 17 13 Univent
B316 Classroom 160 10 748 17 10 Univent
B317 Classroom 198 13 624 14 13 Univent
318 Classroom 0 Yes 900 20 20
B319 Classroom 304 20 748 17 17 Univent
B320 Classroom 144 9 759 17 9 Univent
B321 Classroom 290 19 816 18 18 Univent
B322 Classroom 213 14 598 13 13 Univent
B323 Classroom 156 10 690 15 10 Univent
B324 Classroom 577 38 1435 32 32 Univent
Main Office Main Office 0 Yes 950 21 21
Teachers Lounge Lounge 0 Yes 728 16 16
Nurse Office 0 Yes 910 20 20
C-Wing Auditorium
 Music Rm
346 23 Yes 1476 33 33 Air Handling Unit
C-Wing Auditorium Comm. Rm. 1811 120 7,392 168 120 Air Handling Unit
C-Wing Auditorium/ Auditorium Stage 3862 257 1,890 42 42 Air Handling Unit
Head Start
 Mech Rm.
B110 Learning Lab & B104 Student Store 457 30 81 1 1 Air Handling Unit
Sheet Last Modified: 05-03-2021    
School:  Luis Munoz – Marin Elementary School
Vendor: Chadwick
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100B CORRIDOR 149 9 618 14 9 Air Handling Unit
100E CORRIDOR 115 7 1780 40 7 Air Handling Unit
100F CORRIDOR 250 16 1210 27 16 Air Handling Unit
100G CORRIDOR 142 9 1404 31 9 Air Handling Unit
100H CORRIDOR 0 1780 40 0 Air Handling Unit
102 Classroom  193 12 792 18 12 Air Handling Unit
104 Classroom  225 15 Yes 805 18 18 Air Handling Unit
105 Classroom  195 13 Yes 713 16 16 Air Handling Unit
106 Classroom  213 14 Yes 713 16 16 Air Handling Unit
107 Classroom  170 11 Yes 682 15 15 Air Handling Unit
108 Classroom  202 13 Yes 682 15 15 Air Handling Unit
109 Classroom  227 15 682 15 15 Air Handling Unit
110 Classroom  212 14 Yes 682 15 15 Air Handling Unit
111 Classroom  469 31 700 15 15 Air Handling Unit
115 LOBBY 648 43 1368 31 31 Air Handling Unit
116 - 215 14 609 13 13 Air Handling Unit
118 - 177 11 Yes 672 15 15 Air Handling Unit
120 - 188 12 Yes 768 17 17 Air Handling Unit
121 HEALTH 87 5 816 18 5 Air Handling Unit
124A OFFICE 19 1 120 2 1 Air Handling Unit
125 SPE. 17 1 Yes 336 7 7 Air Handling Unit
125 OCC 51 3 272 6 3 Air Handling Unit
126 FAM MGMT 272 18 1215 27 18 Air Handling Unit
127 CLASSROOM 56 3 670 15 3 Air Handling Unit
127B 15 39 0 Air Handling Unit
127C 18 149 0 Air Handling Unit
160 Classroom  27 1 39 0 0 Air Handling Unit
161 Classroom  33 2 375 8 2 Air Handling Unit
162 Classroom  55 3 114 2 2 Air Handling Unit
163 Classroom  62 4 114 2 2 Air Handling Unit
164 Classroom  33 2 117 2 2 Air Handling Unit
166 Classroom  23 1 102 2 1 Air Handling Unit
168 Classroom  33 2 109 2 2 Air Handling Unit
169 Classroom  23 1 81 1 1 Air Handling Unit
170 Classroom  35 2 134 3 2 Air Handling Unit
171 OFFICE  223 14 148 3 3 Air Handling Unit
172 - 58 3 148 3 3 Air Handling Unit
173 PRINCIPAL 87 5 304 6 5 Air Handling Unit
176 - 114 7 148 3 3 Air Handling Unit
177 - 69 4 134 3 3 Air Handling Unit
180 CONFR 54 3 244 5 3 Air Handling Unit
181 ASS PRINC 100 6 188 4 4 Air Handling Unit
181A OFFICE  42 2 125 2 2 Air Handling Unit
182 - 42 2 131 2 2 Air Handling Unit
183 - 42 2 97 2 2 Air Handling Unit
200A CORRIDOR  160 10 1780 40 10 Air Handling Unit
200C CORRIDOR  148 9 1780 40 9 Air Handling Unit
200D CORRIDOR  240 16 1359 30 16 Air Handling Unit
200E CORRIDOR  100 6 1404 31 6 Air Handling Unit
200F - 156 10 100 2 2 Air Handling Unit
201 Classroom  204 13 Yes 714 16 16 Univent and Air Handling Unit
202 Classroom  94 6 Yes 713 16 16 Univent and Air Handling Unit
203 Classroom  68 4 Yes 704 16 16 Univent and Air Handling Unit
204 Classroom  418 27 764 17 17 Univent and Air Handling Unit
205 Classroom  152 10 Yes 764 17 17 Univent and Air Handling Unit
206 Classroom  241 16 Yes 764 17 17 Univent and Air Handling Unit
207 Classroom  148 9 648 14 9 Univent and Air Handling Unit
208 IMC 338 22 1,757 39 22 Air Handling Unit
209 Classroom  272 18 648 14 14 Univent and Air Handling Unit
213 Classroom  155 10 764 17 10 Univent and Air Handling Unit
214 Classroom  140 9 118 2 2 Univent 
214 IMC 311 20 1,405 31 20 Air Handling Unit
214A WORK 32 2 118 2 2 Air Handling Unit
215 Classroom  232 15 Yes 840 19 19 Univent and Air Handling Unit
216A OFFICE  64 4 165 3 3 Air Handling Unit
217 Classroom  200 13 782 17 13 Univent and Air Handling Unit
218 Classroom  120 8 374 8 8 Univent 
218B STR.  65 4 Yes 2,255 51 51 Air Handling Unit
218S Classroom  71 4 241 5 4 Air Handling Unit
219 Classroom  153 10 Yes 7,825 177 177 Univent and Air Handling Unit
220 Classroom  117 7 Yes 648 14 14 Univent and Air Handling Unit
221 Classroom  253 16 Yes 764 17 17 Univent and Air Handling Unit
222 OFFICE  50 3 1,105 25 3 Air Handling Unit
223 Classroom  188 12 Yes 690 15 15 Univent and Air Handling Unit
225 Classroom  73 4 Yes 870 19 19 Univent 
225 COMP. 124 8 96 2 2 Air Handling Unit
226 TECH. 94 6 Yes 906 20 20 Air Handling Unit
226 (right)  Classroom  104 6 343 7 6 Univent 
226(left)  Classroom  191 12 104 2 2 Univent 
226C SHOP 91 6 104 2 2 Air Handling Unit
227 Classroom  150 10 660 15 10 Univent and Air Handling Unit
300b Corridor 191 12 1404 31 12 Air Handling Unit
300d Corridor 225 15 1359 30 15 Air Handling Unit
301 Classroom  224 14 Yes 714 16 16 Univent and Air Handling Unit
302 Classroom  229 15 Yes 757 17 17 Univent and Air Handling Unit
303 Classroom  188 12 Yes 704 16 16 Univent and Air Handling Unit
304 Classroom  194 12 Yes 757 17 17 Univent and Air Handling Unit
305 Classroom  232 15 Yes 704 16 16 Univent and Air Handling Unit
306 Classroom  243 16 Yes 757 17 17 Univent and Air Handling Unit
307 Classroom  139 9 Yes 648 14 14 Univent and Air Handling Unit
308 Classroom  86 5 734 16 5 Univent and Air Handling Unit
309 Classroom  120 8 Yes 648 14 14 Univent and Air Handling Unit
313 Classroom  156 10 Yes 1160 26 26 Univent and Air Handling Unit
314 Classroom  119 7 Yes 1163 26 26 Univent and Air Handling Unit
315 Classroom  107 7 Yes 713 16 16 Univent and Air Handling Unit
316 Classroom  49 3 Yes 782 17 17 Univent and Air Handling Unit
317 Classroom  99 6 Yes 782 17 17 Univent and Air Handling Unit
318 Classroom  118 7 Yes 684 15 15 Univent and Air Handling Unit
319 Classroom  358 23 782 17 17 Univent and Air Handling Unit
320 Classroom  252 16 648 14 14 Univent and Air Handling Unit
321 Classroom  454 30 648 14 14 Univent and Air Handling Unit
322 OFFICE  0 0 100 2 0 Air Handling Unit
- AUDITORIUM 2082 138 2938 66 66 Air Handling Unit
- CAFETERIA  251 16 Yes 4402 100 100 Air Handling Unit
Sheet Last Modified: 04-29-2021          
School:  George W. Nebinger Elementary-Middle School      
Vendor: EMCOR Fluidics      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 Yes 44 1 1 House Fan
102 Classroom 0 Yes 880 20 20 House Fan
103 Classroom 0 644 14 0 House Fan
104 Classroom 0 644 14 0 House Fan
105 Classroom 0 Yes 644 14 14 House Fan
106 Classroom 0 Yes 644 14 14 House Fan
107 Classroom 0 Yes 660 15 15 House Fan
201 Classroom 0 Yes 660 15 15 House Fan
202 Classroom 0 Yes 660 15 15 House Fan
203 Classroom 0 Yes 644 14 14 House Fan
204 Classroom 0 Yes 899 20 20 House Fan
204A Classroom 0 Yes 285 6 6 House Fan
205 Classroom 0 Yes 330 7 7 House Fan
206 Classroom 0 Yes 644 14 14 House Fan
207 Classroom 0 Yes 660 15 15 House Fan
208 Classroom 0 Yes 660 15 15 House Fan
301 Classroom 0 Yes 660 15 15 House Fan
302 Classroom 0 Yes 660 15 15 House Fan
303 Classroom 0 Yes 644 14 14 House Fan
304 Classroom 0 Yes 644 14 14 House Fan
305 Classroom 0 Yes 667 15 15 House Fan
305A Classroom 0 450 10 0 House Fan
306 Classroom 0 Yes 644 14 14 House Fan
307 Classroom 0 Yes 660 15 15 House Fan
308 Classroom 0 Yes 750 17 17 House Fan
401 Classroom 0 Yes 720 16 16 House Fan
402 Classroom 0 Yes 720 16 16 House Fan
- Gym 0 2,870 65 0 House Fan
- Main Office 0 Yes 330 7 7 House Fan
- Principal's Office 0 Yes 247 5 5 House Fan
- Health Room 0 Yes 99 2 2 House Fan
Sheet Last Modified: 03-18-2021    
School:  Northeast High School
Vendor: Capital Programs Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Devine Brothers Data
1 Classroom 591 39 705 16 16 Unit Ventilator
2 Classroom 520 34 619 14 14 Unit Ventilator
3 Classroom 546 36 759 17 17 Unit Ventilator
4 Classroom 545 36 749 17 17 Unit Ventilator
5 Classroom 586 39 807 18 18 Unit Ventilator
6 Classroom 564 37 782 17 17 Unit Ventilator
7 Classroom 572 38 761 17 17 Unit Ventilator
8 Classroom 539 35 775 17 17 Unit Ventilator
9 Classroom 280 18 762 17 17 Unit Ventilator
10 Classroom 271 18 749 17 17 Unit Ventilator
11 Classroom 337 22 770 17 17 Unit Ventilator
12 Classroom 633 42 1673 38 38 Unit Ventilator
13 Classroom 541 36 1744 39 36 Unit Ventilator
14 Classroom 334 22 1047 23 22 Unit Ventilator
15 Classroom 507 33 1526 34 33 Unit Ventilator
16A Classroom 238 15 731 16 15 Unit Ventilator
16B Classroom 264 17 885 20 17 Unit Ventilator
17A Classroom 380 25 661 15 15 Unit Ventilator
17B Classroom 419 27 853 19 19 Unit Ventilator
17C Classroom 259 17 1050 23 17 Unit Ventilator
18B Classroom 0 0 962 21 0 Unit Ventilator
18D Classroom 0 0 843 19 0 Unit Ventilator
19B Classroom 374 24 862 19 19 Unit Ventilator
21 Offices 0 0 1233 28 0 Vertical Fan Coil Unit
22 Office 230 15 172 3 3 Unit Ventilator
23 Classroom 260 17 741 16 16 Unit Ventilator
24 Classroom 129 8 370 8 8 Unit Ventilator
27 Teacher's Lounge 378 25 1205 27 25 Unit Ventilator
31 Classroom 0 0 562 12 0 Unit Ventilator
32 Classrm. Lab 2,251 150 824 18 18 Unit Ventilator
32A Classrm. Lab 0 0 435 9 0 Unit Ventilator
34A Office 0 0 187 4 0 Unit Ventilator
33 Classroom 499 33 571 12 12 Unit Ventilator
35 Office 0 0 459 10 0 Unit Ventilator
105 Offices 517 34 519 11 11 Unit Ventilator
106 Classroom 748 49 1031 23 23 Unit Ventilator
108 Classroom 739 49 948 21 21 Unit Ventilator
109 Classroom 508 33 940 21 21 Unit Ventilator
110 Library 610 40 386 8 8 Unit Ventilator
111 Classroom 553 36 993 22 22 Unit Ventilator
112 Classroom 602 40 980 22 22 Unit Ventilator
113 Classroom 535 35 883 20 20 Unit Ventilator
114 Classroom 363 24 717 16 16 Unit Ventilator
115 Room 541 36 965 21 21 Unit Ventilator
116 Classroom 623 41 745 16 16 Unit Ventilator
117 Classroom 0 0 686 15 0 Unit Ventilator
118 Classroom 543 36 842 19 19 Unit Ventilator
119 Classroom 436 29 766 17 17 Unit Ventilator
120 Classroom 370 24 741 16 16 Unit Ventilator
121 Classroom 370 24 767 17 17 Unit Ventilator
122 Classroom 495 33 1571 35 33 Unit Ventilator
123 Classroom 403 26 738 16 16 Unit Ventilator
124 Classroom 458 30 1410 32 30 Unit Ventilator
125 Classroom 392 26 802 18 18 Unit Ventilator
126 Classroom 326 21 698 15 15 Unit Ventilator
127 Classroom 425 28 751 17 17 Unit Ventilator
130 Classroom 481 32 1091 24 24 Unit Ventilator
131 Classroom 409 27 713 16 16 Unit Ventilator
132 Classroom 726 48 1038 23 23 Unit Ventilator
133 Classroom 679 45 1627 36 36 Unit Ventilator
133A Office 0 0 293 6 0 Unit Ventilator
134 Classroom 181 12 402 9 9 Unit Ventilator
136 Classroom 712 47 1206 27 27 Unit Ventilator
137 Classroom 537 35 773 17 17 Unit Ventilator
138 Classroom 453 30 1240 28 28 Unit Ventilator
139 Classroom 601 40 798 18 18 Unit Ventilator
140 Classroom 356 23 694 15 15 Unit Ventilator
141 Classroom 510 34 773 17 17 Unit Ventilator
143 Classroom 368 24 778 17 17 Unit Ventilator
150 Classroom 118 7 845 19 7 Unit Ventilator
152 Classroom 127 8 881 20 8 Unit Ventilator
154 Classroom 0 0 874 19 0 Unit Ventilator
156 Classroom 132 8 815 18 8 Unit Ventilator
158 Classroom 160 10 849 19 10 Unit Ventilator
160 Classroom 158 10 835 18 10 Unit Ventilator
162 Classroom 0 0 711 16 0 Unit Ventilator
175 Classroom 480 32 1223 27 27 Unit Ventilator
200 Classroom 137 9 715 16 9 Unit Ventilator
201 Classroom 548 36 728 16 16 Unit Ventilator
202 Classroom 525 35 755 17 17 Unit Ventilator
203 Classroom 232 15 555 12 12 Unit Ventilator
203A Classroom 418 27 546 12 12 Unit Ventilator
204 Classroom 523 34 572 13 13 Unit Ventilator
205 Classroom 441 29 1073 24 24 Unit Ventilator
206 Classroom 463 30 677 15 15 Unit Ventilator
207 Classroom 790 52 651 14 14 Unit Ventilator
208 Classroom 704 46 724 16 16 Unit Ventilator
209 Classroom 769 51 1069 24 24 Unit Ventilator
210 Classroom 410 27 730 16 16 Unit Ventilator
211 Classroom 730 48 1069 24 24 Unit Ventilator
212 Classroom 504 33 662 15 15 Unit Ventilator
213 Classroom 650 43 1100 25 25 Unit Ventilator
214 Classroom 522 34 713 16 16 Unit Ventilator
215 A&B Offices 842 56 410 9 9 Unit Ventilator
215 C&D Offices 833 55 410 9 9 Unit Ventilator
216 Classroom 552 36 678 15 15 Unit Ventilator
218 Classroom 527 35 677 15 15 Unit Ventilator
219A Classroom 313 20 607 13 13 Unit Ventilator
219B Classroom 322 21 446 10 10 Unit Ventilator
220 Classroom 534 35 662 15 15 Unit Ventilator
221A Classroom 307 20 717 16 16 Unit Ventilator
221B Classroom 334 22 391 8 8 Unit Ventilator
222 Classroom 547 36 792 18 18 Unit Ventilator
223A Classroom 267 17 598 13 13 Unit Ventilator
223C Classroom 426 28 373 8 8 Unit Ventilator
225 Classroom 708 47 1445 32 32 Unit Ventilator
227A Classroom 311 20 590 13 13 Unit Ventilator
227B Classroom 298 19 494 11 11 Unit Ventilator
228 Classroom 525 35 784 17 17 Unit Ventilator
229B Classroom 165 11 525 11 11 Unit Ventilator
229C Classroom 325 21 570 12 12 Unit Ventilator
230 Classroom 503 33 657 14 14 Unit Ventilator
231 Classroom 562 37 751 17 17 Unit Ventilator
232 Classroom 592 39 691 15 15 Unit Ventilator
233 Classroom 557 37 705 16 16 Unit Ventilator
234 Classroom 532 35 703 15 15 Unit Ventilator
235 Classroom 458 30 704 16 16 Unit Ventilator
236 Classroom 405 27 701 15 15 Unit Ventilator
237 Room 148 9 384 8 8 Unit Ventilator
238 Classroom 389 25 675 15 15 Unit Ventilator
240 Classroom 411 27 685 15 15 Unit Ventilator
242 Classroom 479 31 711 16 16 Unit Ventilator
244 Classroom 518 34 634 14 14 Unit Ventilator
1st Fl. Corridor Corridor 0 0 892 20 0 Unit Ventilator
2nd Fl. Corr. 2nd Fl. Corr. 0 0 9100 206 0 Unit Ventilator
- Auditorium 1,799 119 12288 279 119 Heating Ventilation Unit
- Band Room 254 16 1028 23 16 Heating Ventilation Unit
Boys Gym #1 Gym 336 22 3701 84 22 Heating Ventilation Unit
Boys Gym #1 Gym 307 20 3701 84 20 Heating Ventilation Unit
Boys Gym #2 Gym 2,587 172 3701 84 84 Heating Ventilation Unit
Boys Gym #2 Gym 1,367 91 3701 84 84 Heating Ventilation Unit
Boys Lckr. Rm. Locker Rm. 1,229 81 5966 135 81 Heating Ventilation Unit
Cafeteria Cafeteria 1,685 112 12073 274 112 Heating Ventilation Unit
Girls Gym #1 Gym 317 21 3514 79 21 Heating Ventilation Unit
Girls Gym #1 Gym 397 26 3514 79 26 Heating Ventilation Unit
Girls Gym #2 Gym 187 12 3514 79 12 Heating Ventilation Unit
Girls Lckr. Rm. Locker Rm. 0 0 3920 89 0 Heating Ventilation Unit
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Grnd. Fl. Corridor Corridor 0 0 3443 78 0 Unit Ventilator
Library Library 2,751 183 1816 41 41 Heating Ventilation Unit
Library Library 453 30 454 10 10 Unit Ventilator
Library Library 525 35 454 10 10 Unit Ventilator
Library Library 509 33 454 10 10 Unit Ventilator
Library Library 477 31 454 10 10 Unit Ventilator
Main office Offices 446 29 2450 55 29 Unit Ventilator
Stage Stage 235 15 1743 39 15 Unit Ventilator
Stage Stage 262 17 1743 39 17 Unit Ventilator
Sheet Last Modified: 04-29-2021    
School:  Olney Elementary School
Vendor: Devine Main Building ABR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
101 Classroom 180.0 12 520 11 11 AIr Handling Unit
102 Classroom 122.0 8 520 11 8 AIr Handling Unit
103 Classroom 142.0 9 520 11 9 AIr Handling Unit
104 Classroom 527.0 35 520 11 11 AIr Handling Unit
107 Classroom 63.0 4 667 15 4 Univent
108 Classroom 235.0 15 840 19 15 Univent
111 Classroom 88.0 5 378 8 5 Univent
201 Classroom 289.0 19 682 15 15 Univent
203 Classroom 327.0 21 928 21 21 Univent
204 Classroom 286.0 19 756 17 17 Univent
205 Classroom 303.0 20 784 17 17 Univent
206 Classroom 296.0 19 812 18 18 Univent
207 Classroom 309.0 20 594 13 13 Univent
208 Classroom 324.0 21 748 17 17 Univent
209 Classroom 282.0 18 1232 28 18 Univent
210 Classroom 327.0 21 330 7 7 Univent
211 Classroom 326.0 21 756 17 17 Univent
301 Classroom 0.0 0 682 15 0 Univent
302 Classroom 328.0 21 682 15 15 Univent
303 Classroom 281.0 18 899 20 18 Univent
304 Classroom 280.0 18 729 16 16 Univent
305 Classroom 324.0 21 812 18 18 Univent
306 Classroom 285.0 19 783 17 17 Univent
307 Classroom 279.0 18 594 13 13 Univent
308 Classroom 291.0 19 782 17 17 Univent
309 Classroom 325.0 21 638 14 14 Univent
310 Classroom 328.0 21 638 14 14 Univent
311 Classroom 309.0 20 756 17 17 Univent
- Main Office 0 480 10 0
- Principal's Office 173.0 11 396 9 9 Univent
- Boys' Cafeteria  0 Yes 1,271 28 Active Pure
- Girls' Cafeteria 0 Yes 943 21 Active Pure
Annex
1 Classroom 0 Yes 684 15 15
2 Classroom 0 Yes 1050 23 23
3 Classroom 0 Yes 792 18 18
4 Classroom 0 Yes 840 19 19
5 Classroom 0 Yes 1104 25 25
6 Classroom 0 Yes 700 15 15
7 Classroom 0 Yes 1050 23 23
8 Classroom 0 Yes 816 18 18
9 Classroom 0 Yes 840 19 19
10 Classroom 0 Yes 875 19 19
- Lobby 0 Yes 180 4 4
- Counselor Office 0 Yes 108 2 2
- Asst Principal's Office 0 Yes 89 2 2
- Gym 0 Yes 4328 98 98 Hydroxyl Unit
- Nurse Open area (Office D) and Early Lit 0 Yes 547 12 12
-  Conference room (medical waiting) 0 Yes 141 3 3
Sheet Last Modified: 03-18-2021    
School:  One Bright Ray- Elmwood
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 313 20 0 0 Air Handling Unit
102 Classroom 189 12 0 0 Air Handling Unit
103 Classroom 249 16 0 0 Air Handling Unit
104 Classroom 215 14 0 0 Air Handling Unit
105 Classroom 250 16 0 0 Air Handling Unit
105 Principal's Office 58 3 0 0 Air Handling Unit
- Dean of Students Office 56 3 0 0 Air Handling Unit
- Faculty Lounge 69 4 0 0 Air Handling Unit
- Foyer / Hallway 147 9 0 0 Air Handling Unit
- Open Space / Classroom 475 31 0 0 Air Handling Unit
- SW Office 48 3 0 0 Air Handling Unit
Sheet Last Modified: 04-30-2021    
School:  Overbrook Educational Center Elementary School
Vendor: Goldner Retest
School:  Overbrook Education Center Annex
Vendor: EMCOR Fluidics
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
- Boiler Room 602 40 1,496 34 34 AHU
- BE Office 0 491 11 0 AHU
- Cafeteria 233 15 Yes 1,936 44 44 AHU
- Corridor 49 3 0 0 AHU
- Kitchen 53 3 440 10 3 AHU
- Music Room 204 13 748 17 13 AHU
- Computer Room 79 5 176 4 4 AHU
- 1st Flr Entryway 42 2 396 9 2 AHU
- Exam Office 32 2 176 4 2 AHU
- Gym Office 28 1 132 3 1 AHU
- Gym /Stage 1,257 83 2,332 53 53 AHU
- Gym Lobby 109 7 0 0 AHU
1st flr Hallway Corridor 20 1 0 0 AHU
1st flr Lobby Main Lobby 71 4 396 9 4 AHU
1st flr Main Office Administration 65 4 220 5 4 AHU
1st flr Nurse's Office Medical 38 2 264 6 2 AHU
1st flr Office Principal 49 3 220 5 3 AHU
1st flr Office Copy Room 19 1 88 2 1 AHU
1st flr Office Conference Room 47 3 176 4 3 AHU
201 Faculty Lounge 161 10 220 5 5 AHU
204 Office 171 11 Yes 176 4 4 RTU
206 Classroom 370 24 660 15 15 Univent
207 Classroom 353 23 748 17 17 Univent
208 Classroom 446 29 748 17 17 Univent
209 Classroom 475 31 572 13 13 Univent
210 Classroom 425 28 660 15 15 Univent
211 Classroom (Life Skills) 536 35 748 17 17 Univent
2nd flr Library Library 344 22 1,496 34 22 AHU
2nd flr Art Classroom 74 4 924 21 4 AHU
2nd Flr Hallway Corridor 197 13 0 0 AAON unit
2nd flr Science Classroom 84 5 836 19 5 AHU
301 Classroom 452 30 220 5 5 RTU
302 Office 284 18 176 4 4 AHU
304 Classroom 463 30 660 15 15 Univent
305 Classroom 517 34 748 17 17 Univent
306 Classroom 550 36 704 16 16 Univent
307 Classroom 596 39 572 13 13 Univent
308 Classroom 461 30 660 15 15 Univent
309 Classroom 1,030 68 748 17 17 Univent
316 Classroom 0 Yes 695 15 15
Annex Building
5 Kitchen 0 Yes 157 3 3
6 Office 0 Yes 122 2 2
7 Lobby 0 890 20 0
1 Classroom 0 Yes 1,077 24 24
2 Classroom 0 Yes 404 9 9
25 Classroom 0 Yes 555 12 12
24 Office 0 Yes 177 4 4
22 Classroom 0 Yes 902 20 20
21 Classroom 0 Yes 297 6 6
31 Classroom 0 Yes 304 6 6
32 Classroom 0 Yes 909 20 20
34 Classroom 0 232 5 0
Sheet Last Modified: 03-18-2021    
School:  Overbrook Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 825.0 55 720 16 16 House fan
2 Classroom 798.0 53 720 16 16 House fan
3 Classroom 872.0 58 720 16 16 House fan
4 Classroom 838.0 55 528 12 12 House fan
5 Classroom 579.0 38 720 16 16 House fan
6 Classroom 499.0 33 720 16 16 House fan
7 Classroom 816.0 54 768 17 17 House fan
8 Classroom 614.0 40 768 17 17 House fan
9 Classroom 788.0 52 768 17 17 House fan
12 Classroom 522.0 34 720 16 16 House fan
13 Classroom 581.0 38 720 16 16 House fan
14 Classroom 472.0 31 720 16 16 House fan
15 Classroom 412.0 27 720 16 16 House fan
16 Classroom 505.0 33 720 16 16 House fan
17 Classroom 524.0 34 720 16 16 House fan
18 Classroom 508.0 33 768 17 17 House fan
19 Classroom 654.0 43 768 17 17 House fan
20 Classroom 498.0 33 768 17 17 House fan
- Boys Bathroom 826.0 55 736 16 16 House fan
- Cafeteria 1,236.0 82 1,560 35 35 House fan
- Faculty bathroom 40.0 2 64 1 1 House fan
- Girls Bathroom 445.0 29 340 7 7 House fan
Sheet Last Modified: 04-30-2021            
School:  Overbrook High School        
             
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
10 - 0 1,041 23 0
11 - 0 1,450 32 0
100 Classroom 0 1,409 32 0
100A Classroom 0 Yes 435 9 9
100B Classroom 0 Yes 479 10 10
100C Classroom 0 Yes 1,407 31 31
101 Classroom 0 Yes 832 18 18
102 Classroom 0 742 16 0
103 Classroom 0 692 15 0
104 Classroom 0 649 14 0
105 Classroom 0 990 22 0
105A Classroom 0 228 5 0
106A Classroom 0 535 12 0
160B Classroom 0 534 12 0
107 Classroom 0 703 15 0
108 Classroom 0 677 15 0
109A Classroom 0 551 12 0
109B Classroom 0 507 11 0
110 Classroom 0 931 21 0
117 Classroom 0 515 11 0
118 Classroom 0 556 12 0
119 Classroom 0 753 17 0
120 Classroom 0 1,026 23 0
121 Classroom 0 1,048 23 0
200 Classroom 0 304 6 0
201 Classroom 0 496 11 0
201 Classroom 0 490 11 0
202 Classroom 0 486 11 0
204 Classroom 0 881 20 0
205 Classroom 0 733 16 0
206 Classroom 0 1,003 22 0
207 Classroom 0 718 16 0
209 Classroom 0 337 7 0
210 Classroom 0 460 10 0
211 Classroom 0 713 16 0
212 Classroom 0 728 16 0
213 Classroom 0 902 20 0
214 Classroom 0 796 18 0
215 Classroom 0 3,413 77 0
216 Classroom 0 850 19 0
217 Classroom 0 712 16 0
218 Classroom 0 700 15 0
219 Classroom 0 719 16 0
220 Classroom 0 359 8 0
221 Classroom 0 877 19 0
222 Classroom 0 877 19 0
223 Classroom 0 729 16 0
224 Classroom 0 731 16 0
225 Classroom 0 694 15 0
300 Classroom 0 747 16 0
301 Classroom 0 724 16 0
302 Classroom 0 737 16 0
303 Classroom 0 907 20 0
304 Classroom 0 941 21 0
305 Classroom 0 724 16 0
306 Classroom 0 738 16 0
307 Classroom 0 739 16 0
308 Classroom 0 834 18 0
309 Classroom 0 733 16 0
311 Classroom 0 721 16 0
312 Classroom 0 704 16 0
313 Classroom 0 491 11 0
314 Classroom 0 669 15 0
315 Classroom 0 673 15 0
316 Classroom 0 Yes 762 17 17
317 Classroom 0 Yes 917 20 20
318 Classroom 0 669 15 0
319 Classroom 0 681 15 0
320 Classroom 0 724 16 0
321 Classroom 0 712 16 0
322 Classroom 0 499 11 0
323 Classroom 0 437 9 0
324 Classroom 0 801 18 0
325 Classroom 0 936 21 0
326 Classroom 0 690 15 0
327 Classroom 0 191 4 0
328 Classroom 0 683 15 0
329 Classroom 0 711 16 0
330 Classroom 0 690 15 0
331 Classroom 0 204 4 0
332 Classroom 0 687 15 0
333 Classroom 0 720 16 0
334 Classroom 0 817 18 0
- Main Office 0 1,057 24 0
- Principal Office 0 562 12 0
- Auditorium Balcony 0 1,436 32 0
- Auditorium 0 8,711 197 0
- Teachers Lounge 0 310 7 0
- Cafeteria A 0 2,778 63 0
- Cafeteria B 0 4,516 102 0
Sheet Last Modified: 04-29-2021    
School:  Academy @ Palumbo High School
Vendor: EMCOR Fluidics
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
103 Graphics Arts 1248 83 1058 24 24 Air Handling Unit
104 Fine Arts 271 18 782 17 17 Air Handling Unit
118 Conference Room 1440 96 690 15 15 Air Handling Unit
129 Main Office 723 48 528 12 12 Air Handling Unit
132 Mixed Choir 736 49 966 21 21 Air Handling Unit
134 Music Theory 1170 78 946 21 21 Air Handling Unit
135 Intro to Music 1709 113 968 22 22 Air Handling Unit
136 Music Equipment Storage 609 40 396 9 9 Air Handling Unit
204 Creative Writing 843 56 660 15 15 Air Handling Unit
205 Computer Lab 653 43 768 17 17 Air Handling Unit
206 Environment Club 713 47 690 15 15 Air Handling Unit
207 Language & Journalism 1069 71 690 15 15 Air Handling Unit
212 Visitor's Locker Room 615 41 720 16 16 Air Handling Unit
221 History 618 41 690 15 15 Air Handling Unit
223 Literature 750 50 1104 25 25 Air Handling Unit
224 English / History 113 7 660 15 7 Air Handling Unit
231 Office 595 39 484 11 11 Air Handling Unit
301 Forensics / Algebra 2 604 40 528 12 12 Air Handling Unit
302 Dean's Office 1510 100 440 10 10 Air Handling Unit
305 History 257 17 690 15 15 Air Handling Unit
306 Spanish 554 36 690 15 15 Air Handling Unit
307 American History 282 18 690 15 15 Air Handling Unit
312 Cardio & Weight Lifting 615 41 720 16 16 Air Handling Unit
321 Spanish 666 44 690 15 15 Air Handling Unit
321 History 532 35 690 15 15 Air Handling Unit
322 History 1582 105 690 15 15 Air Handling Unit
323 Spanish 567 37 690 15 15 Air Handling Unit
332 Black History 84 5 638 14 5 Air Handling Unit
333 History 1066 71 792 18 18 Air Handling Unit
334 Psychologist 0 0 567 12 0 Air Handling Unit
336 Spanish 0 0 1058 24 0 Air Handling Unit
403 Physics Lab 322 21 1056 24 21 Air Handling Unit
407 Biology Lab 587 39 1440 32 32 Air Handling Unit
411 Chemistry 651 43 720 16 16 Air Handling Unit
412 Unknown 668 44 720 16 16 Air Handling Unit
421 Spanish 117 7 690 15 7 Air Handling Unit
422 Chinese 965 64 690 15 15 Air Handling Unit
423 English 1 628 41 690 15 15 Air Handling Unit
432 Literature 484 32 760 17 17 Air Handling Unit
433 History 142 9 760 17 9 Air Handling Unit
436 Science 769 51 1058 24 24 Air Handling Unit
437 Geometry 723 48 552 12 12 Air Handling Unit
501 Algebra 2 677 45 768 17 17 Air Handling Unit
502 Forensics / Algebra 415 27 768 17 17 Air Handling Unit
503 Statistics 483 32 768 17 17 Air Handling Unit
504 Algebra 190 12 768 17 12 Air Handling Unit
506 Algebra 707 47 768 17 17 Air Handling Unit
507 Computer Science 420 28 768 17 17 Air Handling Unit
521 Algebra 190 12 690 15 12 Air Handling Unit
522 Math 2026 135 968 22 22 Air Handling Unit
524 Algebra 1222 81 770 17 17 Air Handling Unit
529 Film 493 32 660 15 15 Air Handling Unit
201A Exercise 323 21 23 0 0 Air Handling Unit
201B Exercise 627 41 1771 40 40 Air Handling Unit
304A Computer Lab 571 38 500 11 11 Air Handling Unit
304B Computer Lab 637 42 446 10 10 Air Handling Unit
329A Admin. Office 605 40 660 15 15 Air Handling Unit
329B Admin. Office 196 13 660 15 13 Air Handling Unit
337A Study Skills / AS 860 57 337 7 7 Air Handling Unit
337B Study Skills / AS 975 65 552 12 12 Air Handling Unit
404A Chemistry Lab 230 15 720 16 15 Air Handling Unit
404B Chemistry Lab 2087 139 720 16 16 Air Handling Unit
409A Office 43 2 280 6 2 Air Handling Unit
409B Office 123 8 280 6 6 Air Handling Unit
429A Robotics 574 38 1320 30 30 Air Handling Unit
429B Robotics 652 43 429 9 9 Air Handling Unit
434A Algebra 541 36 434 9 9 Air Handling Unit
434B Algebra 276 18 1188 27 18 Air Handling Unit
B14 Storage 594 39 374 8 8 Air Handling Unit
B15 Storage 237 15 384 8 8 Air Handling Unit
B16 Storage 37 2 90 2 2 Air Handling Unit
B17 Storage 326.0 21 364 8 8 Air Handling Unit
B19 Storage 723 48.00 1013 23 23 Air Handling Unit
B24-A Storage 723 48 1013 23 23 Air Handling Unit
B24-B Storage 461 30 1013 23 23 Air Handling Unit
- Auditorium 16042 1069 12420 282 282 Air Handling Unit
- Gyms and Cafeteria 7343 489 21078 479 479 Air Handling Unit
- Home Locker Room 417 27 720 16 16 Air Handling Unit
- Locker Room 417 27 720 16 16 Air Handling Unit
- Main Library 1095 73 4608 104 73 Air Handling Unit
- Library A 1256 83 238 5 5 Air Handling Unit
- Library B 1078 71 238 5 5 Air Handling Unit
- Library Storage 917 61 288 6 6 Air Handling Unit
- Men's Room 50 3 252 5 3 Air Handling Unit
- Ladies Room 46 3 252 5 3 Air Handling Unit
- Safe Room 1158 77 675 15 15 Air Handling Unit
B18 Storage 477 31 723 16 16
B20 Storage 461 30.00 1013 23 23
B21 Storage 736 49 966 21 21
B22 Storage 723 48 528 12 12
B23 Storage 323 21 23 0 0
B24 Storage 627 41 1,771 40 40
B25 Storage 843 56 660 15 15
B26 Storage 113 7 660 15 7
B27 Storage 595 39 484 11 11
B28 Storage 604 40 528 12 12
B29 Storage 1510 100 440 10 10
B30 Storage 571 38 500 11 11
B31 Storage 637 42 446 10 10
B32 Storage 666 44 690 15 15
B33 Storage 567 37 690 15 15
B34 Storage 605 40 660 15 15
B35 Storage 196 13 660 15 13
B36 Storage 84 5 638 14 5
B37 Storage 1066 71 792 18 18
B38 Storage 0 0 567 12 0
B39 Storage 0 0 1058 24 0
B40 Storage 860 57 337 7 7
B41 Storage 975 65 552 12 12
B42 Storage 322 21 1056 24 21
B43 Storage 230 15 720 16 15
B44 Storage 2087 139 720 16 16
B45 Storage 628 41 690 15 15
B46 Storage 574 38 1320 30 30
B47 Storage 652 43 429 9 9
B48 Storage 484 32 760 17 17
B49 Storage 142 9 760 17 9
B50 Storage 541 36 434 9 9
B51 Storage 276 18 1188 27 18
B52 Storage 769 51 1058 24 24
B53 Storage 723 48 552 12 12
B54 Storage 677 45 768 17 17
B55 Storage 415 27 768 17 17
B56 Storage 483 32 768 17 17
B57 Storage 1222 81 770 17 17
B58 Storage 493 32 660 15 15
B59 Storage 1158 77 0 0
B60 Storage 26166 1744 0 0
B61 Storage 594 39 374 8 8
B62 Storage 237 15 384 8 8
B63 Storage 37 2 90 2 2
B64 Storage 1170 78 946 21 21
B65 Storage 1709 113 968 22 22
B66 Storage 609 40 396 9 9
B67 Storage 1248 83 1058 24 24
B68 Storage 271 18 782 17 17
B69 Storage 1440 96 690 15 15
B70 Storage 653 43 768 17 17
B71 Storage 713 47 690 15 15
B72 Storage 1069 71 690 15 15
B73 Storage 615 41 720 16 16
B74 Storage 417 27 720 16 16
B75 Storage 618 41 690 15 15
B76 Storage 750 50 1104 25 25
B77 Storage 257 17 690 15 15
B78 Storage 554 36 690 15 15
B79 Storage 282 18 690 15 15
B80 Storage 615 41 720 16 16
B81 Storage 532 35 690 15 15
B82 Storage 1582 105 690 15 15
B83 Storage 917 61 N/A 0 0
B84 Storage 1256 83 N/A 0 0
B85 Storage 1078 71 N/A 0 0
B86 Storage 587 39 1440 32 32
B87 Storage 651 43 720 16 16
B88 Storage 668 44 720 16 16
B89 Storage 117 7 690 15 7
B90 Storage 965 64 690 15 15
B91 Storage 417 27 0 0
B92 Storage 190 12 768 17 12
B93 Storage 707 47 768 17 17
B94 Storage 420 28 768 17 17
B95 Storage 190 12 690 15 12
B96 Storage 2026 135 968 22 22
B97 Storage 16042 1069 12420 282 282
B98 Storage 7343 489 21078 479 479
B99 Storage 1095 73 4608 104 73
B100 Storage 43 2 280 6 2
B101 Storage 123 8 280 6 6
B102 Storage 50 3 252 5 3
B103 Storage 46 3 252 5 3
Sheet Last Modified: 03-18-2021        
School:  Parkway Northwest High School former Hill, JE (Hill-Freedman)
Vendor: Goldner Goldner Retest  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
108 Room 676 45 676 15 15 Univent
109 Room 333 22 714 16 16 Fan Coil Unit
110 Room 168 11 1015 23 11 Univent
130 Room 564 37 630 14 14 Univent
131 Room 476 31 580 13 13 Univent
132 Room 528 35 580 13 13 Univent
133 Room 452 30 469 10 10 Univent
134 Room 496 33 1015 23 23 Univent
135 Room 304 20 812 18 18 Univent
136 Room 424 28 424 9 9 Univent
203 Room 409 27 600 13 13 Univent
204 Room 363 24 667 15 15 Univent
205 Room 376 25 720 16 16 Univent
206 Room 350 23 810 18 18 Univent
207 Room 371 24 783 17 17 Univent
210 Room 482 32 1116 25 25 Fan Coil Unit
211 Room 329 21 957 21 21 Univent
221 Room 300 20 580 13 13 Univent
222 Room 75 5 580 13 5 Univent
223 Room 523 34 580 13 13 Univent
224 Room 717 47 580 13 13 Univent
225 Room 250 16 580 13 13 Univent
226 Room 163 10 580 13 10 Univent
- Auditurium 912 60 1050 23 23 Univent
- Gym 969 64 2460 55 55 Univent
- Main Office 0 0 399 9 0
Sheet Last Modified: 04-30-2021        
School:  John M. Patterson Elementary School House fan Abated
Vendor: Devine Brothers Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 0 Yes 648 14 14 House Fan
2  Classroom  0 Yes 648 14 14 House Fan
3 Classroom 0 Yes 648 14 14 House Fan
100 Office 0 0 143 3 0 House Fan
101 Classroom 659 43 704 16 16 House Fan
102 Classroom 568 37 616 14 14 House Fan
103 Classroom 403 26 616 14 14 House Fan
104 Classroom 663 44 616 14 14 House Fan
105 Classroom 518 34 616 14 14 House Fan
106 Classroom 639 42 616 14 14 House Fan
107 Classroom 698 46 616 14 14 House Fan
108 Classroom 656 43 704 16 16 House Fan
109 Classroom 658 43 704 16 16 House Fan
110 Classroom 722 48 704 16 16 House Fan
200 Classroom 0 0 Yes 704 16 16 House Fan
200A Counselor 0 0 240 5 0 House Fan
201 Classroom 373 24 704 16 16 House Fan
202 Classroom 578 38 703 15 15 House Fan
203 Classroom 504 33 616 14 14 House Fan
204 Classroom 474 31 616 14 14 House Fan
205 Classroom 421 28 616 14 14 House Fan
206 Classroom 541 36 616 14 14 House Fan
207 Classroom 637 42 616 14 14 House Fan
208 Classroom 209 13 704 16 13 House Fan
209 Classroom 585 39 704 16 16 House Fan
210 Classroom 583 38 410 9 9 House Fan
300 Classroom 394 26 704 16 16 House Fan
301 Classroom 530 35 704 16 16 House Fan
302 Classroom 511 34 704 16 16 House Fan
303 Classroom 576 38 704 16 16 House Fan
304 Classroom 359 23 616 14 14 House Fan
305 Classroom 561 37 616 14 14 House Fan
306 Classroom 604 40 616 14 14 House Fan
307 Classroom 103 6 616 14 6 House Fan
308 Classroom 418 27 704 16 16 House Fan
309 Classroom 101 6 704 16 6 House Fan
310 Classroom 429 28 704 16 16 House Fan
- Auditorium 5125 341 2880 65 65 House Fan
- Admin Office 0 0 Yes 88 2 2 House Fan
- Principal Office 0 Yes 120 2 2 House Fan
- Book Room Storage 0 0 230 5 0 House Fan
- Boiler Rm. 22650 1510 1440 32 32 House Fan
- Small Cafeteria 689 45 1232 28 28 House Fan
- Kitchen 212 14 200 4 4 House Fan
- Gym/Cafeteria 0 0 Yes 3762 85 85 House Fan
- Storage 574 38 0 0 House Fan
- Music 375 25 560 12 12 House Fan
- Nurse's Room 0 0 Yes 336 7 7 House Fan
- Teacher's Lounge 0 0 Yes 410 9 9 House Fan
Sheet Last Modified: 04-20-2021    
School:  Penn Alexander Elementary-Middle School
Vendor: Devine Brothers Part 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B24 Classroom 37.0 2 130 2 2 Air Handling Unit
B26 Classroom 120.0 8 216 4 4 Air Handling Unit
B28 Classroom 483.0 32 722 16 16 Air Handling Unit
106 Classroom 1,065.0 71 806 18 18 Air Handling Unit
108 Classroom 310 20 842 19 19 Univent
109 Classroom 311 20 759 17 17 Univent
110 Classroom 305 20 693 15 15 Univent
113 Classroom 220.0 14 222 5 5 Air Handling Unit
117 Classroom 285 19 741 16 16 Univent
118 Classroom 329 21 759 17 17 Univent
119 Classroom 315 21 683 15 15 Univent
123 Classroom 0.0 0 150 3 0 Air Handling Unit
125 Classroom 73.0 4 209 4 4 Air Handling Unit
126 Classroom 13.0 0 99 2 0 Air Handling Unit
127 Classroom 14.0 0 99 2 0 Air Handling Unit
128 Classroom 10.0 0 Yes 99 2 2 Air Handling Unit
129 Classroom 84.0 5 Yes 291 6 6 Air Handling Unit
131 Classroom 302 20 694 15 15 Univent
133 Classroom 0.0 0 Yes 644 14 14 Univent
134 Classroom 330 22 683 15 15 Univent
201 Classroom 491.0 32 875 19 19 Air Handling Unit
202 Classroom 74.0 4 324 7 4 Air Handling Unit
208 Classroom 0.0 0 Yes 842 19 19 Univent
209 Classroom 0.0 0 Yes 759 17 17 Univent
210 Classroom 0.0 0 Yes 693 15 15 Univent
213 Classroom 75.0 5 222 5 5 Air Handling Unit
217 Classroom 0.0 0 Yes 741 16 16 Univent
218 Classroom 0.0 0 Yes 728 16 16 Univent
219 Classroom 0.0 0 Yes 683 15 15 Univent
220 Classroom 241.0 16 224 5 5 Air Handling Unit
221 Classroom 0.0 0 Yes 96 2 2 Air Handling Unit
222 Classroom 0.0 0 169 3 0 Air Handling Unit
225 Classroom 0.0 0 Yes 209 4 4 Air Handling Unit
227 Classroom 0.0 0 99 2 0 Air Handling Unit
228 Classroom 0.0 0 154 3 0 Air Handling Unit
229 Classroom 0.0 0 108 2 0 Air Handling Unit
230 Classroom 318 21 736 16 16 Univent
231 Classroom 301 20 840 19 19 Univent
233 Classroom 266 17 739 16 16 Univent
234 Classroom 328 21 671 15 15 Univent
301 Classroom 1,176.0 78 1005 22 22 Air Handling Unit
302 Classroom 0.0 0 324 7 0 Univent
308 Classroom 0.0 0 Yes 842 19 19 Univent
309 Classroom 0.0 0 Yes 713 16 16 Univent
310 Classroom 0.0 0 Yes 693 15 15 Univent
317 Classroom 0.0 0 Yes 741 16 16 Univent
318 Classroom 0.0 0 Yes 759 17 17 Univent
319 Classroom 0.0 0 Yes 683 15 15 Univent
320 Classroom 0.0 0 320 7 0 Air Handling Unit
- Cafeteria 7,801.0 520 3766 85 85 Air Handling Unit
- GYM 1,362.0 90 4271 97 90 Air Handling Unit
- Library 550.0 36 2658 60 36 Air Handling Unit
- Main Office 205.0 13 1063 24 13 Air Handling Unit
Sheet Last Modified: 04-28-2021    
School:  Penn Treaty High School
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 classroom 0 Yes 624 14 14 House Fan
102 Administration  0 Yes 336 7 7 House Fan
102A classroom 0 Yes 768 17 17 House Fan
104 classroom 0 Yes 1,539 34 34 House Fan
105 classroom 0 Yes 594 13 13 House Fan
106 classroom 0 Yes 864 19 19 House Fan
107 classroom 0 Yes 920 20 20 House Fan
108 Administration  0 Yes 780 17 17 House Fan
109 classroom 0 Yes 864 19 19 House Fan
110 classroom 0 Yes 672 15 15 House Fan
110A classroom 0 Yes 768 17 17 House Fan
111 classroom 0 650 14 0 House Fan
115 Auditorium 0 3,594 81 0 House Fan
H11A Main office  0 560 12 0 House Fan
H11b Main office  0 576 13 0 House Fan
H12 Main office  0 1,150 26 0 House Fan
H13 Main office  0 792 18 0 House Fan
H13a Main office  0 312 7 0 House Fan
H13b Main office  0 814 18 0 House Fan
H13c Main office  0 275 6 0 House Fan
H13d Main office  0 1,150 26 0 House Fan
201 classroom 0 650 14 0 House Fan
202 classroom 0 690 15 0 House Fan
203 classroom 0 696 15 0 House Fan
203A classroom 0 253 5 0 House Fan
204 classroom 0 130 2 0 House Fan
204A classroom 0 552 12 0 House Fan
205 Nurse 0 Yes 325 7 7 House Fan
207 Main office  0 Yes 667 15 15 House Fan
207A Speech 0 Yes 70 1 1 House Fan
207B Office 0 120 2 0 House Fan
207D Principal Office 0 Yes 300 6 6 House Fan
207G Conference Room 0 Yes 144 3 3 House Fan
208 classroom 0 1,056 24 0 House Fan
209 classroom 0 1,032 23 0 House Fan
210 IMC 0 Yes 2,352 53 53 House Fan
213 classroom 0 696 15 0 House Fan
214 classroom 0 624 14 0 House Fan
217 Auditorium 0 2,304 52 0 House Fan
301 classroom 0 650 14 0 House Fan
301A Administration  0 375 8 0 House Fan
303 classroom 0 696 15 0 House Fan
303A Admin 0 275 6 0 House Fan
304 classroom 0 696 15 0 House Fan
305 classroom 0 696 15 0 House Fan
305A classroom 0 912 20 0 House Fan
307 classroom 0 696 15 0 House Fan
308 classroom 0 672 15 0 House Fan
309 classroom 0 744 16 0 House Fan
310 classroom 0 696 15 0 House Fan
311 classroom 0 720 16 0 House Fan
312 classroom 0 720 16 0 House Fan
313 classroom 0 696 15 0 House Fan
314 classroom 0 624 14 0 House Fan
315 Admin 0 238 5 0 House Fan
316 classroom 0 696 15 0 House Fan
317 classroom 0 672 15 0 House Fan
401 classroom 0 624 14 0 House Fan
402A Admin 0 828 18 0 House Fan
402 classroom 0 322 7 0 House Fan
403 classroom 0 1,032 23 0 House Fan
404 classroom 0 984 22 0 House Fan
405 classroom 0 984 22 0 House Fan
406 classroom 0 984 22 0 House Fan
407 classroom 0 720 16 0 House Fan
408 classroom 0 1,008 22 0 House Fan
409 classroom 0 1,008 22 0 House Fan
410 classroom 0 1,008 22 0 House Fan
412 Admin 0 506 11 0 House Fan
412A classroom 0 768 17 0 House Fan
412b classroom 0 84 1 0 House Fan
412c Admin 0 484 11 0 House Fan
413 classroom 0 720 16 0 House Fan
414 classroom 0 650 14 0 House Fan
415 Cafe 0 2,200 50 0 House Fan
417 Kitchen 0 Yes 455 10 10 House Fan
417A kitchen 0 700 15 0 House Fan
419 Cafe 0 2,150 48 0 House Fan
- boys gym  0 4,725 107 0 House Fan
- girls gym  0 4,725 107 0 House Fan
Sheet Last Modified: 03-24-2021    
School:  Joseph Pennell Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 - 0 0 Yes 1,152 26 26 Univent
2 - 0 0 Yes 1,152 26 26 Univent
101 Classroom 0 0 288 6 0 Air Handling Unit
102 Classroom 0 0 Yes 720 16 16 Air Handling Unit
103 Classroom 0 0 Yes 875 19 19 Air Handling Unit
104 Classroom 0 0 Yes 175 3 3 Air Handling Unit
104A Classroom 0 0 375 8 0 Air Handling Unit
104B Classroom 0 0 175 3 0 Air Handling Unit
104C Classroom 0 0 125 2 0 Air Handling Unit
105 Classroom 0 0 900 20 0 Air Handling Unit
106 Classroom 0 0 Yes 816 18 18 Air Handling Unit
107 Classroom 0 0 Yes 1,025 23 23 Air Handling Unit
110 Classroom 0 0 Yes 870 19 19 Air Handling Unit
201 Classroom 0 0 Yes 816 18 18 Air Handling Unit
202 Classroom 0 0 Yes 816 18 18 Air Handling Unit
203 Classroom 0 0 875 19 0 Air Handling Unit
204 Classroom 0 0 875 19 0 Air Handling Unit
205 Classroom 0 0 875 19 0 Air Handling Unit
206 Classroom 0 0 875 19 0 Air Handling Unit
207 Classroom 0 0 Yes 816 18 18 Air Handling Unit
208 Classroom 0 0 Yes 984 22 22 Air Handling Unit
209 Classroom 0 0 870 19 0 Air Handling Unit
210 Classroom 0 0 870 19 0 Air Handling Unit
211 Classroom 0 0 870 19 0 Air Handling Unit
301 Classroom 0 0 816 18 0 Air Handling Unit
302 Classroom 0 0 816 18 0 Air Handling Unit
303 Classroom 0 0 875 19 0 Air Handling Unit
304 Classroom 0 0 875 19 0 Air Handling Unit
305 Classroom 0 0 875 19 0 Air Handling Unit
306 Classroom 0 0 Yes 875 19 19 Air Handling Unit
307 Classroom 0 0 816 18 0 Air Handling Unit
308 Classroom 0 0 Yes 910 20 20 Air Handling Unit
309 Classroom 0 0 870 19 0 Air Handling Unit
310 Classroom 0 0 870 19 0 Air Handling Unit
311 Classroom 0 0 870 19 0 Air Handling Unit
- Basement Boys Room 0 0 650 14 0 Air Handling Unit
- Basement Corridor 0 0 352 8 0 Air Handling Unit
- Gym 0 0 Yes 5,096 115 115 Air Handling Unit
- Library 0 0 1,593 36 0 Air Handling Unit
- Nurse 0 0 Yes 384 8 8 Air Handling Unit
- Counselor Office 0 384 8 0
- Office 0 Yes 456 10 10
- Principal's Office 0 Yes 234 5 5
Sheet Last Modified: 04-27-2021      
School:  Samuel Pennypacker Elementary-Middle School
Vendor: Devine
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B2 Classroom 0 0 Yes 928 21 21 House Fan
B3 Classroom 923 61 1160 26 26 House Fan
B4 Classroom 0.00 0 Yes 1260 28 28 House Fan
B8 Classroom 488.00 32 576 13 13 House Fan
B9 Classroom 439.00 29 460 10 10 House Fan
B10 Classroom 425 28 576 13 13 House Fan
101 Classroom 545 36 1131 25 25 House Fan
102 Classroom 440 29 841 19 19 House Fan
103 Classroom 545 36 870 19 19 House Fan
104 Classroom 611 40 870 19 19 House Fan
105 Classroom 340 22 841 19 19 House Fan
106 Classroom 395 26 841 19 19 House Fan
107 Classroom 503.00 33 841 19 19 House Fan
108 Classroom 650 43 899 20 20 House Fan
109 Classroom 437 29 841 19 19 House Fan
110 Classroom 459 30 899 20 20 House Fan
201 Classroom 351 23 899 20 20 House Fan
202 Classroom 424 28 841 19 19 House Fan
203 Classroom 390 26 870 19 19 House Fan
204 Classroom 338 22 841 19 19 House Fan
205 Classroom 649 43 841 19 19 House Fan
208 Classroom 586 39 899 20 20 House Fan
209 Classroom 508 33 841 19 19 House Fan
210 Classroom 356 23 899 20 20 House Fan
212 Storage 0 0 360 8 0 House Fan
301 Classroom 382 25 899 20 20 House Fan
302 Classroom 653 43 841 19 19 House Fan
303 Classroom 355 23 870 19 19 House Fan
304 Classroom 407 27 841 19 19 House Fan
305 Classroom 583 38 841 19 19 House Fan
306 Classroom 554 36 870 19 19 House Fan
307 Classroom 513 34 841 19 19 House Fan
308 Classroom 515 34 899 20 20 House Fan
309 Classroom 676 45 841 19 19 House Fan
310 Classroom 422 28 899 20 20 House Fan
311 Classroom 550 36 720 16 16 House Fan
312 Classroom 0 0 Yes 138 3 3 House Fan
- Auditorium 1967 131 4272 97 97 House Fan
- Counselor's Office 0 0 Yes 386 8 8 House Fan
- Gym/Café 0 0 Yes 3608 82 82 House Fan
- Nurse 0 0 Yes 361 8 8 House Fan
- Library 928 61 1620 36 36 House Fan
- Main Office 0 0 Yes 342 7 7 House Fan
- Principals Office 0.0 0 Yes 346 7 7 House Fan
- Teacher's Lounge 0.0 0 105 2 0 House Fan
Sheet Last Modified: 04-23-2021      
School:  Penrose Elementary School- Main Building
  Main Exhaust Report      
School:  Penrose Little School House
  Penrose LSH Exhaust Report LSH Part 2 and Exhaust LSH Part 3 and Exhaust
School:  TB Read – former Motivation High School Building
  TB Read Exhaust Report TB Read Exhaust Retest    
Vendor: Chadwick
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Penrose Main Building
101 Classroom 373.0 24 884 20 20 Rooftop Unit
102 Classroom 387.0 25 884 20 20 Rooftop Unit
103 Classroom 359.0 23 884 20 20 Rooftop Unit
104 Classroom 505.0 33 884 20 20 Rooftop Unit
105 Classroom 469.0 31 884 20 20 Rooftop Unit
106 office 119.0 7 315 7 7 Rooftop Unit
106a  principal 26.0 1 72 1 1 Rooftop Unit
106b council 36.0 2 176 4 2 Rooftop Unit
107 Classroom 99.0 6 884 20 6 Rooftop Unit
111 Classroom 233.0 15 884 20 15 Rooftop Unit
113 Classroom 256.0 17 884 20 17 Rooftop Unit
115 Classroom 287.0 19 884 20 19 Rooftop Unit
116 cafe 330.0 22 1,794 40 22 Rooftop Unit
116 Classroom 387.0 25 884 20 20 Rooftop Unit
117 Classroom 337.0 22 884 20 20 Rooftop Unit
118 Classroom 306.0 20 884 20 20 Rooftop Unit
119 Classroom 297.0 19 884 20 19 Rooftop Unit
121 Classroom 291.0 19 884 20 19 Rooftop Unit
201 Classroom 704.0 46 884 20 20 Rooftop Unit
202 Classroom 475.0 31 884 20 20 Rooftop Unit
203 Classroom 697.0 46 884 20 20 Rooftop Unit
204 Classroom 457.0 30 884 20 20 Rooftop Unit
205 Classroom 292.0 19 884 20 19 Rooftop Unit
206 Classroom 399.0 26 496 11 11 Rooftop Unit
207 Classroom 574.0 38 884 20 20 Rooftop Unit
211 Classroom 423.0 28 884 20 20 Rooftop Unit
213 Classroom 159.0 10 884 20 10 Rooftop Unit
214 Classroom 202.0 13 884 20 13 Rooftop Unit
215 Classroom 208.0 13 884 20 13 Rooftop Unit
216 Classroom 144.0 9 884 20 9 Rooftop Unit
217 Classroom 142.0 9 884 20 9 Rooftop Unit
218 Classroom 153.0 10 1,768 40 10 Rooftop Unit
219 Classroom 131.0 8 884 20 8 Rooftop Unit
221 Classroom 151.0 10 884 20 10 Rooftop Unit
Penrose Little School House
1 Classroom  289.0 19 978 22 19 Blower Coil Unit
2 Classroom  340.0 22 978 22 22 Blower Coil Unit
3 Classroom  289.0 19 978 22 19 Blower Coil Unit
4 Classroom  340.0 22 978 22 22 Blower Coil Unit
5 Classroom  350.0 23 978 22 22 Blower Coil Unit
6 Classroom  374.0 24 978 22 22 Blower Coil Unit
7 Classroom  374.0 24 978 22 22 Blower Coil Unit
8 Classroom  493.0 32 978 22 22 Blower Coil Unit
9 Classroom  311.0 20 978 22 20 Blower Coil Unit
10 Classroom  493.0 32 978 22 22 Blower Coil Unit
11 Classroom  311.0 20 978 22 20 Blower Coil Unit
- multipurpose 2,960.0 197 2,067 46 46 Blower Coil Unit
- Corridor 58.0 3 684 15 3 Blower Coil Unit
- Boy's Restroom 59.0 3 200 4 3 Blower Coil Unit
- Girl's Rest Room 64.0 4 200 4 4 Blower Coil Unit
- General Office 0 146 3 0 Blower Coil Unit
- Principal's Office 0 72 1 0 Blower Coil Unit
- Psychiastrist's Office 0 72 1 0 Blower Coil Unit
TB Read
101 Classroom 324.0 21 792 18 18 Heating Ventilation Unit
102 Classroom 101.0 6 Yes 792 18 18 Heating Ventilation Unit
103 Classroom 492.0 32 792 18 18 Heating Ventilation Unit
104 Classroom 584.0 38 792 18 18 Heating Ventilation Unit
105 Classroom 400.0 26 792 18 18 Heating Ventilation Unit
201 Classroom 443.0 29 792 18 18 Heating Ventilation Unit
202 Classroom 1,636.0 109 792 18 18 Heating Ventilation Unit
203 Classroom 717.0 47 792 18 18 Heating Ventilation Unit
204 Classroom 948.0 63 792 18 18 Heating Ventilation Unit
205 Classroom 397.0 26 792 18 18 Heating Ventilation Unit
14 Computer Lab 473.0 31 792 18 18 Heating Ventilation Unit
- Corridor #1 795.0 53 1,298 29 29 Heating Ventilation Unit
- Corridor #2 413.0 27 1,600 36 27 Heating Ventilation Unit
- GYM 7,270.0 484 8,969 203 203 Heating Ventilation Unit
- Library 442.0 29 874 19 19 Heating Ventilation Unit
Sheet Last Modified: 05-03-2021      
School:  Philadelphia Learning Academy North/ Camelot Academy East/ Crossroads Academy at Hunting Park (former CEP Hunting Park) Alternative School
Vendor: Goldner  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
3 Room (Split Level South) 25 1 86 1 1 Rooftop Unit
5 Room (Split Level South) 141 9 396 9 9 Rooftop Unit
 005A Room (Split Level South) 20 1 87 1 1 Rooftop Unit
6 Room 27 1 83 1 1 Rooftop Unit
 006A Room 14 0 80 1 0 Rooftop Unit
 006B Room 13 0 79 1 0 Rooftop Unit
10 Room 7 0 84 1 0 Rooftop Unit
 010A Room 53 3 80 1 1 Rooftop Unit
103 Room 20 1 87 1 1 Rooftop Unit
104 Room 19 1 85 1 1 Rooftop Unit
105 Room 27 1 81 1 1 Rooftop Unit
106 Room 22 1 83 1 1 Rooftop Unit
108 Room 14 0 89 2 0 Rooftop Unit
109 Room 13 0 92 2 0 Rooftop Unit
110 Room 15 0 269 6 0 Rooftop Unit
113 Room (Split Level South) 56 3 134 3 3 Rooftop Unit
114 Room (Split Level South) 26 1 136 3 1 Rooftop Unit
115 Room (Split Level South) 41 2 139 3 2 Rooftop Unit
116 Room (Split Level South) 25 1 139 3 1 Rooftop Unit
117 Room (Split Level South) 80 5 355 8 5 Rooftop Unit
120 Admin Office -231 -15 92 2 -15 Rooftop Unit
121 Admin Office 145 9 396 9 9 Rooftop Unit
122 Admin Office 208 13 94 2 2 Rooftop Unit
123 Admin Office 97 6 92 2 2 Rooftop Unit
124 Admin Office -65 -4 92 2 -4 Rooftop Unit
126 Admin Office 57 3 139 3 3 Rooftop Unit
127 Admin Office -417 -27 95 2 -27 Rooftop Unit
129 Admin Office -65 -4 355 8 -4 Rooftop Unit
130 Admin Office -52 -3 Yes 140 3 3 Rooftop Unit
133 Admin Office 104 6 266 6 6 Rooftop Unit
133A Admin Office 322 21 927 21 21 Rooftop Unit
133B Admin Office 316 21 927 21 21 Rooftop Unit
134 Media Room 195 13 1769 40 13 Rooftop Unit
135 Admin Office 253 16 709 16 16 Rooftop Unit
136 Media Room 465 31 407 9 9 Rooftop Unit
142 Admin Office 339 22 225 5 5 Rooftop Unit
147 AEP Office 146 9 413 9 9 Rooftop Unit
148 AEP Office -245 -16 92 2 -16 Rooftop Unit
149 AEP Office -104 -6 94 2 -6 Rooftop Unit
150 AEP Office -38 -2 136 3 -2 Rooftop Unit
151 AEP Office 178 11 179 4 4 Rooftop Unit
152 AEP Office 10 0 91 2 0 Rooftop Unit
153 AEP Office 36 2 92 2 2 Rooftop Unit
154 AEP Office 69 4 96 2 2 Rooftop Unit
155 AEP Office 179 11 184 4 4 Rooftop Unit
156 AEP Office -34 -2 80 1 -2 Rooftop Unit
157 AEP Office 70 4 79 1 1 Rooftop Unit
158 AEP Office 119 7 85 1 1 Rooftop Unit
159 AEP Office 21 1 84 1 1 Rooftop Unit
160 AEP Office 184 12 142 3 3 Rooftop Unit
161 Library Office -59 -3 91 2 -3 Rooftop Unit
162 Library Office -99 -6 269 6 -6 Rooftop Unit
164 Main Library 980 65 973 22 22 Rooftop Unit
174 Office -270 -18 83 1 -18 Rooftop Unit
175 Office 80 5 82 1 1 Rooftop Unit
180 Office 87 5 93 2 2 Rooftop Unit
181 Office -31 -2 92 2 -2 Rooftop Unit
182 Office 166 11 92 2 2 Rooftop Unit
184 Office 122 8 93 2 2 Rooftop Unit
185 Office 27 1 92 2 1 Rooftop Unit
186A Office -272 -18 449 10 -18 Rooftop Unit
186B Office -47 -3 449 10 -3 Rooftop Unit
187 Office -182 -12 94 2 -12 Rooftop Unit
188 Office 100 6 92 2 2 Rooftop Unit
189 Office 78 5 227 5 5 Rooftop Unit
192 Office -269 -17 72 1 -17 Rooftop Unit
193 Office 283 18 82 1 1 Rooftop Unit
194 Office 106 7 48 1 1 Rooftop Unit
195 Office 78 5 232 5 5 Rooftop Unit
196 Classroom 190 12 528 12 12 Rooftop Unit
201 Classroom 248 16 712 16 16 Rooftop Unit
204 Electrical Closet 13 0 80 1 0 Rooftop Unit
205 IT Room -3 0 84 1 0 Rooftop Unit
207 Closet 0 0 136 3 0 Rooftop Unit
210 Office -127 -8 96 2 -8 Rooftop Unit
211 Office -20 -1 94 2 -1 Rooftop Unit
212 Office 0 0 96 2 0 Rooftop Unit
213 Room 0 Yes 880 20 20
 213A Office 63 4 180 4 4 Rooftop Unit
 213B Office 284 18 792 18 18 Rooftop Unit
214 Office -12 0 89 2 0 Rooftop Unit
215 Office 0 0 92 2 0 Rooftop Unit
217 Office -31 -2 96 2 -2 Rooftop Unit
218 Office -23 -1 86 1 -1 Rooftop Unit
219 Office 0 0 93 2 0 Rooftop Unit
221 IT Room 13 0 52 1 0 Rooftop Unit
222 Electrical Closet 195 13 94 2 2 Rooftop Unit
223 Closet 0 0 55 1 0 Rooftop Unit
303 Room (Split Level South) 45 2 86 1 1 Rooftop Unit
304 Room (Split Level South) 124 8 231 5 5 Rooftop Unit
307 Room (Split Level South) 118 7 312 7 7 Rooftop Unit
311 Room (Split Level South) 13 0 136 3 0 Rooftop Unit
 311A Room (Split Level South) 20 1 63 1 1 Rooftop Unit
 311B Room (Split Level South) 12 0 86 1 0 Rooftop Unit
313 Room 20 1 98 2 1 Rooftop Unit
314 Room 21 1 85 1 1 Rooftop Unit
316 Room 62 4 449 10 4 Rooftop Unit
320 Room 19 1 87 1 1 Rooftop Unit
321 Room 16 1 89 2 1 Rooftop Unit
322 Room 17 1 87 1 1 Rooftop Unit
 H01 Room (Split Level South) 34 2 89 2 2 Rooftop Unit
 H01 Room 15 0 72 1 0 Rooftop Unit
 H21 Room (Split Level South) 159 10 446 10 10 Rooftop Unit
 H21 Room 7 0 52 1 0 Rooftop Unit
 L4/L5 Room 84 5 225 5 5 Rooftop Unit
A1 Classroom 594 39 Yes 794 18 18 Rooftop Unit
A2 Classroom 876 58 793 18 18 Rooftop Unit
A3 Classroom 219 14 795 18 14 Rooftop Unit
A4 Classroom 905 60 796 18 18 Rooftop Unit
B1 Classroom 430 28 793 18 18 Rooftop Unit
B2 Classroom 1048 69 792 18 18 Rooftop Unit
B3 Classroom 84 5 794 18 5 Rooftop Unit
B4 Classroom 769 51 794 18 18 Rooftop Unit
C1 Classroom 551 36 797 18 18 Rooftop Unit
C2 Classroom 927 61 795 18 18 Rooftop Unit
C3 Classroom 115 7 794 18 7 Rooftop Unit
C4 Classroom 70 4 795 18 4 Rooftop Unit
D1 Classroom 587 39 797 18 18 Rooftop Unit
D2 Classroom 935 62 795 18 18 Rooftop Unit
D3 Classroom 14 0 793 18 0 Rooftop Unit
D4 Classroom 617 41 796 18 18 Rooftop Unit
E1 Classroom 312 20 Yes 794 18 18 Rooftop Unit
E2 Classroom 752 50 Yes 796 18 18 Rooftop Unit
E3 Classroom 269 17 793 18 17 Rooftop Unit
E4 Classroom 715 47 Yes 795 18 18 Rooftop Unit
G1 Classroom 66 4 Yes 794 18 18 Rooftop Unit
G2 Classroom 857 57 Yes 796 18 18 Rooftop Unit
G3 Classroom 197 13 Yes 793 18 18 Rooftop Unit
G4 Classroom 813 54 Yes 797 18 18 Rooftop Unit
Gym Recreational Area 1 442 29 1276 29 29 Rooftop Unit
Gym Gym Cafeteria 306 20 886 20 20 Rooftop Unit
Gym Recreational Area 1 630 42 1848 42 42 Rooftop Unit
Gym Gym 2A 716 47 9196 209 47 Rooftop Unit
Gym Gym 2B 601 40 9196 209 40 Rooftop Unit
Gym Vestibule 0 0 176 4 0 Rooftop Unit
H1 Classroom 807 53 796 18 18 Rooftop Unit
H17 Hallway 91 6 264 6 6 Rooftop Unit
H2 Classroom 706 47 794 18 18 Rooftop Unit
H3 Classroom -660 -44 793 18 -44 Rooftop Unit
H4 Classroom 11 0 795 18 0 Rooftop Unit
Hallway Hallway (Split Level South) 48 3 136 3 3 Rooftop Unit
Hunter Office 229 15 664 15 15 Rooftop Unit
Hunting Park Lobby 1738 115 5069 115 115 Rooftop Unit
J Hallway 0 0 616 14 0 Rooftop Unit
J1 Classroom -493 -32 Yes 529 12 12 Rooftop Unit
J2 Classroom 381 25 792 18 18 Rooftop Unit
J3 Classroom 493 32 528 12 12 Rooftop Unit
J4 Classroom 1208 80 528 12 12 Rooftop Unit
K Hallway 0 0 616 14 0 Rooftop Unit
K1 Classroom 189 12 792 18 12 Rooftop Unit
K2 Classroom 682 45 794 18 18 Rooftop Unit
K3 Classroom 130 8 Yes 796 18 18 Rooftop Unit
K4 Classroom 617 41 797 18 18 Rooftop Unit
Kitchen Kitchen 1953 130 880 20 20 Rooftop Unit
Kitchen Lounge -3 0 73 1 0 Rooftop Unit
L Hallway 0 0 704 16 0 Rooftop Unit
L1 Classroom 79 5 Yes 794 18 18 Rooftop Unit
L2 Classroom 636 42 793 18 18 Rooftop Unit
L3 Classroom 109 7 Yes 792 18 18 Rooftop Unit
L4 Classroom 707 47 797 18 18 Rooftop Unit
Lobby Main Lobby North 147 9 410 9 9 Rooftop Unit
M Hallway 0 0 704 16 0 Rooftop Unit
M1 Classroom 226 15 794 18 15 Rooftop Unit
M2 Classroom 855 57 796 18 18 Rooftop Unit
M3 Classroom 17 1 793 18 1 Rooftop Unit
M4 Classroom 684 45 795 18 18 Rooftop Unit
Men's Bathroom Men's Bathroom 0 0 132 3 0 Rooftop Unit
MS0S1 Office 432 28 528 12 12 Rooftop Unit
MS0S2 Office 1153 76 880 20 20 Rooftop Unit
MS2 MS2 (Woodshop) 480 32 1408 32 32 Rooftop Unit
MS2 MS2 (Woodshop) 768 51 1408 32 32 Rooftop Unit
MS6 Office 107 7 176 4 4 Rooftop Unit
MS7 Office 0 0 132 3 0 Rooftop Unit
N1 Classroom 612 40 794 18 18 Rooftop Unit
N2 Classroom (with office) 100 6 796 18 6 Rooftop Unit
N3 Classroom (with office) 1490 99 795 18 18 Rooftop Unit
N4 Classroom 781 52 796 18 18 Rooftop Unit
Office Office 12 0 132 3 0 Rooftop Unit
S11 AEP Office -244 -16 396 9 -16 Rooftop Unit
- Staff Lounge 243 16 528 12 12 Rooftop Unit
- Women's Bathroom 0 0 132 3 0 Rooftop Unit
Sheet Last Modified: 04-23-2021    
School:  Robert B. Pollock Elementary School
Vendor: EMCORE Fluidics Retest Report
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 313 20 945 21 20 Perimeter Heater
2 Classroom 385 25 945 21 21 Perimeter Heater
3 Classroom 141 9 Yes 945 21 21 Perimeter Heater
4 Classroom 406 27 945 21 21 Perimeter Heater
5 Classroom 222 14 Yes 945 21 21 Perimeter Heater
6 Classroom 278 18 720 16 16 Perimeter Heater
7 Classroom 270 18 945 21 18 Perimeter Heater
8 Classroom 329 21 945 21 21 Perimeter Heater
9 Classroom 301 20 945 21 20 Perimeter Heater
10 Classroom 482 32 945 21 21 Perimeter Heater
11 Classroom 0 0 Yes 945 21 21 Perimeter Heater
12 Classroom 369 24 945 21 21 Perimeter Heater
13 Classroom 282 18 945 21 18 Perimeter Heater
14 Classroom 338 22 945 21 21 Perimeter Heater
15 Classroom 275 18 945 21 18 Perimeter Heater
16 Classroom 311 20 840 19 19 Perimeter Heater
17 Classroom 294 19 945 21 19 Perimeter Heater
101 Classroom 505 33 1450 32 32 Perimeter Heater
102 Classroom 280 18 945 21 18 Perimeter Heater
103 Classroom 305 20 945 21 20 Perimeter Heater
104 Classroom 277 18 945 21 18 Perimeter Heater
105 Classroom 273 18 945 21 18 Perimeter Heater
106 Classroom 707 47 945 21 21 Perimeter Heater
107 Classroom 0 Yes 945 21 21
108 Classroom 315 21 594 13 13 Perimeter Heater
110 Classroom 301 20 Yes 945 21 21 Perimeter Heater
111 Classroom 276 18 480 10 10 Perimeter Heater
112 Classroom 276 18 945 21 18 Perimeter Heater
113 Classroom 272 18 945 21 18 Perimeter Heater
114 Classroom 277 18 945 21 18 Perimeter Heater
115 Classroom 275 18 945 21 18 Perimeter Heater
116 Classroom 289 19 945 21 19 Perimeter Heater
117A Classroom 579 38 1890 42 38 Perimeter Heater
118 Classroom 323 21 945 21 21 Perimeter Heater
- Main Office 0 Yes 674 15 15
- Principals Office 0 Yes 96 2 2
- Nurses Office 0 Yes 96 2 2
- Office 0 Yes 108 2 2
- Auditorium 5,528 368 4240 96 96 Air Handling Unit
- Cafeteria 5,093 339 4032 91 91 Air Handling Unit
- Confrence Room 275 18 374 8 8 Perimeter Heater
- Gym 3,930 262 3901 88 88 Air Handling Unit
- Kindergarten Classroom 438 29 1450 32 29 Perimeter Heater
- First Flr Office 0 0 674 15 0 Perimeter Heater
- P1 Bungalow Building 527 35 1248 28 28 Perimeter Heater
- P2 Bungalow Building 298 19 806 18 18 Perimeter Heater
- P3 Bungalow Building 385 25 1040 23 23 Perimeter Heater
Sheet Last Modified: 04-21-2021      
School:  Potter Thomas Promise Academy Elementary School
Vendor: Goldner Retest  
  Devine 2nd Retest 2-15-21
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 322 21 1,350 30 21 Univent
102 Classroom 387 25 1,590 36 25 Univent
103 Classroom 374 24 1,590 36 24 Univent
104 Classroom 817 54 1,590 36 36 Univent
105 Classroom 296 19 1024 23 19 Univent
106 Music Room 216 14 754 17 14 Univent
106 Computer Lab 149 9 Yes 1,989 45 45 Univent
201 Classroom 245 16 812 18 16 Univent
202 Classroom 275 18 870 19 18 Univent
203 Classroom 329 21 870 19 19 Univent
204 Classroom 350 23 870 19 19 Univent
205 Classroom 356 23 870 19 19 Univent
206 Classroom 338 22 783 17 17 Univent
207 Classroom 469 31 841 19 19 Univent
208 Classroom 397 26 870 19 19 Univent
209 Classroom 257 17 870 19 17 Univent
210 Classroom 368 24 870 19 19 Univent
211 Classroom 348 23 870 19 19 Univent
212 Classroom 291 19 870 19 19 Univent
213 Classroom 280 18 870 19 18 Univent
214 Classroom 319 21 870 19 19 Univent
215 Classroom 297 19 870 19 19 Univent
216 Classroom 286 19 870 19 19 Univent
217 Classroom 392 26 896 20 20 Univent
218 Classroom 296 19 870 19 19 Univent
219 Classroom 307 20 870 19 19 Univent
220 Classroom 235 15 870 19 15 Univent
221 Classroom 293 19 870 19 19 Univent
222 Classroom 312 20 783 17 17 Univent
223 Classroom 238 15 870 19 15 Univent
224 Classroom 300 20 870 19 19 Univent
226 Classroom 365 24 942 21 21 Univent
226A - 0 Yes 269 6 6
228 Classroom 364 24 942 21 21 Univent
228A - 0 Yes 269 6 6
- Art room 642 42 1800 40 40 Univent
Art Room B 0 260 5 0
- Cafeteria/Theatre 0 0 Yes 5280 120 120 Air Handling Unit
ESOL Suite 0 Yes 119 2 2
- Community Room 239 15 839 19 15 Univent
- Gym 0 0 5016 114 0 Air Handling Unit
- Gym Offices 0 0 Yes 200 4 4 Air Handling Unit
- Kitchen 273 18 1332 30 18 Air Handling Unit
- Library 5,562 370 1944 44 44 Air Handling Unit
Counselor Office 0 Yes 261 5 5
- Main Office 1,418 94 1800 40 40 Air Handling Unit
- Faculty lounge 0 840 19 0
Sheet Last Modified: 04-29-2021    
School:  Powel/SLAMS Elementary School
Vendor: Capital Retest 3-31-2021
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Report Classroom ID / Area ID Number Posted Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
026 026 Electrical room 0 502.0 11 0 Fan Coil Unit
021 021 Lockers 98 6.0 114.0 2 2 Fan Coil Unit
023 023 Lockers 101 6 149 3 3 Fan Coil Unit
017 017 Storage 203 13 330 7 7 Fan Coil Unit
018 018 Workshop 362 24 305 6 6 Fan Coil Unit
103 101 Cafeteria 3580 238 3579 81 81 Rooftop Unit
104 - Corridor 498 33 977 22 22 Fan Coil Unit
105 100 Waiting Area 241 16 404 9 9 Fan Coil Unit
112 100A Conselor's Office 15 1 104 2 1 Fan Coil Unit
113 100G Office 16 1 123 2 1 Fan Coil Unit
114 100B Dean's Office 16 1 104 2 1 Fan Coil Unit
115 100F Records 14 0 101 2 0 Fan Coil Unit
115 - Open Office Space 29 1 332 7 1 Fan Coil Unit
116 100C Principal's Office 30 2 166 3 2 Fan Coil Unit
118 100D Conference Room 67 4 186 4 4 Fan Coil Unit
119 101F Kitchen Storage 36 2 152 3 2 Rooftop Unit
121 101E Kitchen 535 35 841 19 19 Rooftop Unit
123 - Servery 270 18 486 11 11 Rooftop Unit
124 101B Office 33 2 91 2 2 Rooftop Unit
126 - Corridor 251 16 2146 48 16 Fan Coil Unit
127 102 Kindergarten Classroom 314 20 1023 23 20 Fan Coil Unit
128 103 Classroom 302 20 853 19 19 Fan Coil Unit
129 104 Kindergarten Classroom 317 21 1022 23 21 Fan Coil Unit
130 105 Classroom 318 21 851 19 19 Fan Coil Unit
131 106 Kindergarten Classroom 321 21 1022 23 21 Fan Coil Unit
132 107 Classroom 322 21 853 19 19 Fan Coil Unit
133 108 Special Education Classroom 147 9 378 8 8 Fan Coil Unit
134 109 Classroom 314 20 853 19 19 Fan Coil Unit
135 110 Classroom 326 21 852 19 19 Fan Coil Unit
136 111 Classroom 322 21 853 19 19 Fan Coil Unit
137 112 Classroom 323 21 842 19 19 Fan Coil Unit
138 113 Classroom 310 20 842 19 19 Fan Coil Unit
139 114 Classroom 317 21 844 19 19 Fan Coil Unit
140 115 Classroom 318 21 844 19 19 Fan Coil Unit
141 116 Classroom 325 21 851 19 19 Fan Coil Unit
142 117 Classroom 313 20 853 19 19 Fan Coil Unit
143 118 Special Education Classroom 151 10 388 8 8 Fan Coil Unit
145 119 Library 546 36 1712 38 36 Fan Coil Unit
146 119B Conference Room 32 2 261 5 2 Fan Coil Unit
147 119A Work Room 19 1 270 6 1 Fan Coil Unit
148 120/121 Art Classroom 379 25 956 21 21 Fan Coil Unit
149 120A Art Storage Room 50 3 61 1 1 Fan Coil Unit
150 121/123 Music Classroom 200 13 1,083 24 13 Fan Coil Unit
152 123A Music Studio 53 3 237 5 3 Fan Coil Unit
161 - Lobby 208 13 475 10 10 Fan Coil Unit
162 122 Gym 4453 296 5,236 119 119 Rooftop Unit
163 125A Office 55 3 161 3 3 Rooftop Unit
164 125B Storage 35 2 141 3 2 Rooftop Unit
167 - Small Group 1288 85 963 21 21 Fan Coil Unit
168 - Open Space/Corridor 196 13 324 7 7 Fan Coil Unit
201 - Corridor 472 31 563 12 12 Fan Coil Unit
212 200A Conselor's Office 22 1 104 2 1 Fan Coil Unit
214 200B Principal's Office 33 2 166 3 2 Fan Coil Unit
216 200C Conference Room 65 4 189 4 4 Fan Coil Unit
217 200D Small Meeting Room 20 1 96 2 1 Fan Coil Unit
218 200E Small Meeting Room 20 1 96 2 1 Fan Coil Unit
219 200F Records 8 0 180 4 0 Fan Coil Unit
202 201 Nurse's Suite 23 1 221 5 1 Fan Coil Unit
203 201D Exam Room 12 0 81 1 0 Fan Coil Unit
204 201A Exam Room 13 0 102 2 0 Fan Coil Unit
205 200 Waiting Area 161 10 359 8 8 Fan Coil Unit
213 201E Building Storage 44 2 494 11 2 Fan Coil Unit
215 - Open Office 121 8 1263 28 8 Fan Coil Unit
220 - Corridor 11 0 266 6 0 Fan Coil Unit
221 201H Faculty Lounge 126 8 419 9 8 Fan Coil Unit
226 - Corridor 233 15 3096 70 15 Fan Coil Unit
227 202 Classroom 421 28 858 19 19 Fan Coil Unit
228 203 Classroom 446 29 860 19 19 Fan Coil Unit
229 204 Classroom 427 28 856 19 19 Fan Coil Unit
230 205 Classroom 416 27 858 19 19 Fan Coil Unit
231 206 Classroom 426 28 858 19 19 Fan Coil Unit
232 207 Classroom 417 27 860 19 19 Fan Coil Unit
233 208 Special Education Classroom 195 13 377 8 8 Fan Coil Unit
234 209 Classroom 438 29 860 19 19 Fan Coil Unit
235 210 Art Classroom 494 32 1235 28 28 Fan Coil Unit
237 210A Storage 18 1 48 1 1 Fan Coil Unit
239 210B Storage 33 2 113 2 2 Fan Coil Unit
236 211 Classroom 435 29 860 19 19 Fan Coil Unit
241 212 Classroom 450 30 852 19 19 Fan Coil Unit
238 213 Classroom 425 28 851 19 19 Fan Coil Unit
243 214 Classroom 447 29 859 19 19 Fan Coil Unit
240 215 Classroom 456 30 852 19 19 Fan Coil Unit
244 216 Small Group Classroom 119 7 388 8 7 Fan Coil Unit
242 217 Pre-Eng. Classroom 417 27 860 19 19 Fan Coil Unit
245 219 Makerspace 677 45 165 3 3 Fan Coil Unit
248 220 Science Classroom 1385 92 1,289 29 29 Fan Coil Unit
249 220B Prep Room 739 49 403 9 9 Fan Coil Unit
250 221 Classroom 1356 90 1,285 29 29 Fan Coil Unit
256 221C Storage 0 0 50 1 0 Fan Coil Unit
253 221C Room 489 32 632 14 14 Fan Coil Unit
254 225 Office 50 3 173 3 3 Rooftop Unit
266 - West Hallway 208 13 779 17 13 Fan Coil Unit
Sheet Last Modified: 03-31-2021    
School:  Anna B. Pratt Elementary School
Vendor: Capital Devine ABR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
106 Classroom / Swing Space 597 39 936 21 21 Univent
109 Classroom 651 43 936 21 21 Univent
110 Classroom 327 21 936 21 21 Univent
111 Classroom 320 21 936 21 21 Univent
112 Classroom 393 26 936 21 21 Univent
113 Special Education 453 30 936 21 21 Univent
114 Classroom 442 29 936 21 21 Univent
201 Classroom / Swing Space 473 31 936 21 21 Univent
200 / 202 Library 776 51 1848 42 42 Univent
208 Classroom 367 24 936 21 21 Univent
209 Classroom 489 32 936 21 21 Univent
210 Technology Classroom 422 28 936 21 21 Univent
211 Classroom 313 20 936 21 20 Univent
212 Classroom 526 35 936 21 21 Univent
213 Classroom 468 31 936 21 21 Univent
214 Data Room 433 28 399 9 9 Univent
301 Music Room 327 21 936 21 21 Univent
302 Classroom 311 20 936 21 20 Univent
308 Classroom 386 25 936 21 21 Univent
309 Special Education 459 30 936 21 21 Univent
310 Special Education 447 29 936 21 21 Univent
311 Classroom 430 28 936 21 21 Univent
312 Classroom 615 41 936 21 21 Univent
313 Classroom 330 22 936 21 21 Univent
314 Classroom 522 34 936 21 21 Univent
315 Staff Room 361 24 399 9 9 Univent
- Main Office 0 Yes 352 8 8
- Principal Office 0 Yes 228 5 5
- AS Office 0 Yes 192 4 4
- Nurses Office 0 Yes 156 3 3
- Climate Office 0 Yes 156 3 3
- Counselors Office 0 Yes 156 3 3
Sheet Last Modified: 04-23-2021    
School:  Prince Hall Elementary School
Vendor: Devine Brothers Retest Gymnasium
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
1 Classroom 380 25 1200 27 25 Univent
2 Classroom 321 21 1200 27 21 Univent
3 Classroom 387 25 1200 27 25 Univent
4 Classroom 304 20 1200 27 20 Univent
5 Classroom 313 20 900 20 20 Univent
6 Classroom 268 17 Yes 900 20 20 Univent
7 Classroom 351 23 836 19 19 Univent
8 Classroom 334 22 874 19 19 Univent
9 Classroom 235 15 Yes 1050 23 23 Univent
10 Classroom 375 25 888 20 20 Univent
11 Classroom 242 16 Yes 1066 24 24 Univent
12 Classroom 234 15 Yes 1134 25 25 Univent
13 Classroom 227 15 Yes 1100 25 25 Univent
103 Classroom 601 40 1280 29 29 Univent
104 Classroom 696 46 1280 29 29 Univent
105 Classroom 664 44 1360 30 30 Univent
106 Classroom 739 49 1280 29 29 Univent
112 Classroom 0 Yes 1360 30 30
116 Classroom 279 18 400 9 9 Univent
117 Classroom 322 21 700 15 15 Univent
201 Classroom 418 27 1200 27 27 Univent
202 Classroom 292 19 Yes 1200 27 27 Univent
203 Classroom 311 20 1200 27 20 Univent
204 Classroom 259 17 Yes 1200 27 27 Univent
205 Classroom 377 25 900 20 20 Univent
206 Classroom 338 22 900 20 20 Univent
207 Classroom 238 15 836 19 15 Univent
208 Classroom 312 20 874 19 19 Univent
209 Classroom 244 16 Yes 1050 23 23 Univent
210 Classroom 240 16 888 20 16 Univent
211 Classroom 263 17 1066 24 17 Univent
212 Classroom 332 22 1170 26 22 Univent
213 Classroom 614 40 988 22 22 Univent
- AUDITORIUM 1185 79 3363 76 76 Air Handling Unit
- Admin. Main Office 56 3 255 5 3 Univent
- Admin. Office 28 1 126 2 1 Univent
- Main Office 301 20 720 16 16 Univent
- Principal's Office 0 Yes 255 5 5
- Copy Room Office 16 1 98 2 1 Univent
- Counselor's Office 107 7 416 9 7 Univent
- Computer Room Classroom 380 25 1600 36 25 Univent
- IMC Classroom 1021 68 4335 98 68 Univent
- Gym 0 0 4800 109 0 Air Handling Unit
- Gym Locker Rooms 335 22 403 9 9 Air Handling Unit
- Main Entrance 68 4 150 3 3 Univent
- Multi-Purpose/Cafe 2016 134 2760 62 62 Air Handling Unit
- Nurse's Office 1 50 3 90 2 2 Univent
- Nurse's Office 2 40 2 110 2 2 Univent
- Nurse's Office 71 4 Yes 160 3 3 Univent
Sheet Last Modified: 03-18-2021    
School:  A. Philip Randolph Career and Technical High School  
Vendor: Goldner    
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
20 Classroom 1,172.00 78 0 0 Air Coil Unit
21 Classroom 1,124.00 74 600 13 13 Air Coil Unit
23 Classroom 1,177.00 78 720 16 16 Air Coil Unit
24 Classroom 889 59 792 18 18 Air Coil Unit
36 Classroom 93 6 0 0 Rooftop Unit
37 Classroom 176 11 704 16 11 Rooftop Unit
38 DENTAL SHOP 236 15 1596 36 15 Rooftop Unit
38 DENTAL IMAGE ROOM 8 0 0 0 Rooftop Unit
38 DENTAL X-RAY ROOM 12 0 0 0 Rooftop Unit
39 Classroom 73 4 0 0 Rooftop Unit
50 Art Room 694 46 1008 22 22 Air Coil Unit
51 Classroom 199 13 510 11 11 Air Coil Unit
52 Classroom 435 29 420 9 9 Air Coil Unit
53 Classroom 483.00 32 612 13 13 Air Coil Unit
54 Classroom 784.00 52 798 18 18 Air Coil Unit
55 Classroom 149.00 9 660 15 9 Air Coil Unit
56 Classroom 570 38 1190 27 27 Air Coil Unit
57 Classroom 505 33 522 11 11 Air Coil Unit
71 Room 262 17 480 10 10 Air Coil Unit
72 Room 289 19 510 11 11 Air Coil Unit
73 Classroom 0 0 616 14 0 Air Coil Unit
74 Room 0 0 572 13 0 Air Coil Unit
75 Classroom 0 0 660 15 0 Air Coil Unit
76 Classroom 0 0 600 13 0 Air Coil Unit
94 Room 88 5 72 1 1 Air Coil Unit
100 Classroom 197 13 396 9 9 Air Coil Unit
- Automotive 80 5 0 0 Air Coil Unit
- AV storage 96 6 0 0 Air Coil Unit
- BEHAVIORAL THERAPIST OFFICE 26.00 1 0 0 Rooftop Unit
- Boys Bathroom 0.00 0 0 0 Air Coil Unit
- Break Room 168 11 0 0 Air Coil Unit
- CAFETERIA 2,027.00 135 3828 87 87 Rooftop Unit
- Cafeteria 2,027.00 135 704 16 16 Air Coil Unit
- Classrooms 392.00 26 600 13 13 Air Coil Unit
- Classrooms 5,734.00 382 720 16 16 Air Coil Unit
- Classrooms 4,521.00 301 792 18 18 Air Coil Unit
- Classrooms 0.00 0 572 13 0 Air Coil Unit
- COUNSELORS OFFICE 19 1 0 0 Rooftop Unit
- Engineers Office 238 15 0 0 Air Coil Unit
- Girls Bathroom 0 0 200 4 0 Air Coil Unit
- Hallway 245 16 0 0 Air Coil Unit
- IMC side area 657 43 0 0 Air Coil Unit
- IMC area 118 7 1664 37 7 Air Coil Unit
- INSPECTORS OFFICE 0 0 0 0 Rooftop Unit
- IT ROOM 40 2 0 0 Rooftop Unit
- kitchen 1,766.00 117 722 16 16 Air Coil Unit
- Kitchen 3,575.00 238 722 16 16 Air Coil Unit
- Kitchen Dining 93.00 6 252 5 5 Air Coil Unit
- Library 29.00 1 1664 37 1 Air Coil Unit
- MAIL ROOM 50 3 384 8 3 Rooftop Unit
- MAIN OFFICE 113 7 134 3 3 Rooftop Unit
- CONFERENCE ROOM 23 1 247 5 1 Rooftop Unit
Main office, classrooms Main office, classrooms 1,328.00 88 285 6 6 Air Coil Unit
- Ms. SMALLEY OFFICE 7.00 0 120 2 0 Rooftop Unit
- NURSES OFFICE 156 10 196 4 4 Rooftop Unit
- office next to electrical room 136.00 9 140 3 3 Air Coil Unit
office diffuser s1 office 223 14 140 3 3 Air Coil Unit
- kitchen office 21 1 320 7 1 Air Coil Unit
- VP office 0 0 130 2 0 Air Coil Unit
office Diffuser S6 office 0 0 192 4 0 Air Coil Unit
office Diffuser S1 office 0 0 320 7 0 Air Coil Unit
office diffuser s18 office 78 5 120 2 2 Air Coil Unit
office diffuser s17 office 84 5 308 7 5 Air Coil Unit
office diffuser s16 office 108 7 280 6 6 Air Coil Unit
OFFICE IN BACK OF MAIN OFFICE OFFICE IN BACK OF MAIN OFFICE 0 0 110 2 0 Rooftop Unit
OFFICE NEXT TO RM 39 OFFICE NEXT TO RM 39 23 1 216 4 1 Rooftop Unit
- Paint shop 0 0 320 7 0 H2-7
- Paint shop 0 0 0 0 H2-8
PRINCIPLE OFFICE PRINCIPLE OFFICE 49 3 16 0 0 Rooftop Unit
security office diffuser s4 180 12 0 0 Air Coil Unit
- Shop area 408 27 0 0 H2-5
- Shop area 1,346.00 89 0 0 H1-4
- Shop area 591.00 39 0 0 H1-3
- Shop area 450 30 0 0 H4-14
- Shop area 0 0 0 0 H4-13
- Shop area 0 0 0 0 H4-12
- Shop area 0 0 0 0 H3-10
- Shop area 0 0 0 0 H3-11
- Shop Classrooms 2,065.00 137 0 0 Air Coil Unit
- SPEECH THERAPIST NEXT TO PRINCIPLE OFFICE 60.00 4 0 0 Rooftop Unit
- SPEECH THERAPIST OFFICE 20 1 0 0 Rooftop Unit
storage diffuser s11 storage 53.00 3 0 0 Air Coil Unit
storage diffuser s10 storage 192 12 0 0 Air Coil Unit
storage diffuser s9 storage 170.00 11 0 0 Air Coil Unit
storage diffuser s2 storage 120 8 0 0 Air Coil Unit
storage diffuser s1 storage 115.00 7 0 0 Air Coil Unit
storage diffuser S19 storage 0.00 0 0 0 Air Coil Unit
storage diffuser S17 storage 0 0 0 0 Air Coil Unit
storage diffuser S16 storage 0 0 0 0 Air Coil Unit
Storage Diffuser S5 Storage 0 0 0 0 Air Coil Unit
storage diffuser s6 storage 76 5 0 0 Air Coil Unit
storage diffuser s4 storage 64 4 0 0 Air Coil Unit
- STORAGE ROOM IN MAIN OFFICE 16 1 0 0 Rooftop Unit
teacher lounge diffuser S19 teachers lounge 37.00 2 572 13 2 Air Coil Unit
- TOM MCLAUGHLIN OFFICE 29 1 572 13 1 Rooftop Unit
- vending machine shop 0 0 0 0 H1-1
- welding shop 0 0 0 0 H2-9
Sheet Last Modified: 04-07-2021    
School:  Rhawnhurst Elementary School
Vendor: Devine Part 2 Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 301 20 1485 33 20 Univent
101 Classroom 341 22 1056 24 22 Univent
102 Classroom 296 19 1056 24 19 Univent
102B Office 0 Yes 110 2 2 Univent
103 Classroom 297 19 1056 24 19 Univent
104 Classroom 335 22 1056 24 22 Univent
105 Classroom 307 20 1073 24 20 Univent
106 Classroom 624 41 1020 23 23 Univent
107 Classroom 321 21 1056 24 21 Univent
108 Classroom 313 20 1056 24 20 Univent
109 Classroom 302 20 1056 24 20 Univent
110 Classroom 301 20 1056 24 20 Univent
200 Classroom 520 34 1056 24 24 Univent
201 Classroom 259 17 1056 24 17 Univent
202 Classroom 306 20 1056 24 20 Univent
203 Classroom 586 39 1056 24 24 Univent
203A Office 0 Yes 275 6 6 Univent
203B Office 0 Yes 198 4 4 Univent
204 Classroom 452 30 1056 24 24 Univent
Annex 301 Classroom 246 16 792 18 16 Univent
Annex 302 Classroom 291 19 792 18 18 Univent
Annex 303 Classroom 303 20 792 18 18 Univent
Annex 304 Classroom 198.00 13 Yes 792 18 18 Univent
Annex 305 Classroom 248.00 16 792 18 16 Univent
Annex 306 Classroom 216.00 14 Yes 792 18 18 Univent
- Main Office 0 Yes 240 5 5 Univent
Principal Office 0 Yes 264 6 6 Univent
- Nurses Office 0 Yes 460 10 10 Univent
- Special Education Office 0 Yes 360 8 8 Univent
- Counselor Office 0 Yes 241 5 5 Univent
- Auditorium 2,049.00 136 3431 77 77 Air Handling Unit
- Cafeteria 362 24 2814 63 24 Univent
- Gym 116 7 3969 90 7 Air Handling Unit
- Library 140 9 Yes 1134 25 25 Univent
- Trailer 286 19 649 14 14 Air Handling Unit
A1 Annex 75 5 792 18 5 Univent
A2 Annex 95 6 792 18 6 Univent
A3 Annex 54 3 792 18 3 Univent
A4 Annex 62 4 792 18 4 Univent
A5 Annex 63 4 792 18 4 Univent
A6 Annex 70 4 792 18 4 Univent
Sheet Last Modified: 04-15-2021    
School:  James Rhoads Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 122.0 8 552 12 8 Univent
102 Classroom 87.0 5 Yes 968 22 22 Univent
104 Classroom 136.0 9 Yes 968 22 22 Univent
200 Classroom 0.0 0 805 18 0 Univent
201 Classroom 190.0 12 Yes 805 18 18 Univent
202 Classroom 237.0 15 805 18 15 Univent
203 Classroom 212.0 14 Yes 805 18 18 Univent
204 Classroom 0.0 0 Yes 805 18 18 Univent
205 Classroom 162.0 10 Yes 805 18 18 Univent
206 Classroom 201.0 13 Yes 805 18 18 Univent
207 Classroom 0.0 0 805 18 0 Univent
208 Classroom 236.0 15 805 18 15 Univent
209 Classroom 174.0 11 Yes 805 18 18 Univent
210 Classroom 212.0 14 805 18 14 Univent
300 Classroom 318.0 21 805 18 18 Univent
301 Classroom 202.0 13 805 18 13 Univent
302 Classroom 197.0 13 805 18 13 Univent
303 Classroom 300.0 20 805 18 18 Univent
304 Classroom 203.0 13 805 18 13 Univent
305 Classroom 205.0 13 805 18 13 Univent
306 Classroom 169.0 11 805 18 11 Univent
307 Classroom 233.0 15 805 18 15 Univent
308 Classroom 201.0 13 805 18 13 Univent
309 Classroom 174.0 11 805 18 11 Univent
310 Classroom 342.0 22 805 18 18 Univent
400 Classroom 0.0 0 805 18 0 Univent
401 Classroom 0.0 0 805 18 0 Univent
402 Classroom 0.0 0 805 18 0 Univent
403 Classroom 0.0 0 805 18 0 Univent
404 Classroom 0.0 0 Yes 805 18 18 Univent
405 Classroom 0.0 0 Yes 805 18 18 Univent
406 Classroom 0.0 0 Yes 805 18 18 Univent
407 Classroom 0.0 0 Yes 805 18 18 Univent
408 Classroom 0.0 0 805 18 0 Univent
409 Classroom 0.0 0 Yes 805 18 18 Univent
410 Classroom 0.0 0 805 18 0 Univent
- Main Office 0 Yes 616 14 14
- Principal Office 0 Yes 300 6 6
- Nurse Office 0 Yes 120 2 2
- Auditorium 0.0 0 1800 40 0 Air Handling Unit
- Café/Gym 0.0 0 6480 147 0 Air Handling Unit
- IMC 0.0 0 897 20 0 Univent
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sheet Last Modified: 03-08-2021    
School:  E. Washington Rhodes Elementary School
Vendor: Goldner Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- 1ST/2ND FLR A&B POD AREAS 0 0 1829 41 0 Air Handling Unit
- 1ST/2ND FLR C&D POD AREAS 0 0 1829 41 0 Air Handling Unit
A1 CLASSROOM 365 24 850 19 19 Univent
A2 CLASSROOM 326 21 850 19 19 Univent
A3 CLASSROOM 0 0 850 19 0 Univent
A4 CLASSROOM 0 0 1085 24 0 Univent
A5 CLASSROOM 289 19 720 16 16 Univent
A6 CLASSROOM 308 20 890 20 20 Univent
A7 CLASSROOM 0 0 0 0 0 Univent
A101 CLASSROOM 283 18 850 19 18 Univent
A102 CLASSROOM 369 24 850 19 19 Univent
A103 CLASSROOM 279 18 816 18 18 Univent
A104 CLASSROOM 238 15 1120 25 15 Univent
A105 CLASSROOM 296 19 744 16 16 Univent
A106 CLASSROOM 227 15 1100 25 15 Univent
B1 CLASSROOM 275 18 850 19 18 Univent
B2 CLASSROOM 308 20 850 19 19 Univent
B3 CLASSROOM 338 22 850 19 19 Univent
B4 CLASSROOM 300 20 1085 24 20 Univent
B5 CLASSROOM 233 15 720 16 15 Univent
B6 CLASSROOM 296 19 890 20 19 Univent
B101 CLASSROOM 237 15 850 19 15 Univent
B102 CLASSROOM 325 21 850 19 19 Univent
B103 CLASSROOM 275 18 816 18 18 Univent
B104 CLASSROOM 307 20 1120 25 20 Univent
B105 CLASSROOM 301 20 744 16 16 Univent
B106 CLASSROOM 297 19 1100 25 19 Univent
C1 CLASSROOM 297 19 850 19 19 Univent
C2 CLASSROOM 0 0 Yes 850 19 19 Univent
C3 CLASSROOM 0 0 Yes 850 19 19 Univent
C4 CLASSROOM 367 24 1085 24 24 Univent
C5 CLASSROOM 368 24 720 16 16 Univent
C6 CLASSROOM 333 22 890 20 20 Univent
C7 CLASSROOM 293 19 0 0 0 Univent
C101 CLASSROOM 253 16 850 19 16 Univent
C102 CLASSROOM 404 26 850 19 19 Univent
C103 CLASSROOM 230 15 816 18 15 Univent
C104 CLASSROOM 353 23 1120 25 23 Univent
C105 CLASSROOM 290 19 744 16 16 Univent
C106 CLASSROOM 241 16 1100 25 16 Univent
D1 CLASSROOM 274 18 850 19 18 Univent
D2 CLASSROOM 449 29 850 19 19 Univent
D3 CLASSROOM 314 20 850 19 19 Univent
D4 CLASSROOM 293 19 1085 24 19 Univent
D5 CLASSROOM 273 18 720 16 16 Univent
D6 CLASSROOM 405 27 890 20 20 Univent
D101 CLASSROOM 283 18 850 19 18 Univent
D102 CLASSROOM 304 20 850 19 19 Univent
D103 CLASSROOM 326 21 816 18 18 Univent
D104 CLASSROOM 244 16 1120 25 16 Univent
D105 CLASSROOM 235 15 744 16 15 Univent
D106 CLASSROOM 0 0 1100 25 0 Univent
D200 MUSIC CLASSROOM 2 729 48 1600 36 36 Univent
D205 MUSIC CLASSROOM 1 620 41 1600 36 36 Univent
E12 SCIENCE CLASSROOM 0 0 1232 28 0 Univent
E-147 BREAK ROOM, OFFICE AREA 0 0 120 2 0 Univent
E-148 VICE PRINCIPAL OFFICE 0 0 120 2 0 Univent
E-149 CONFERENCE AREA 47 3 260 5 3 Univent
E-150 PRINCIPAL OFFICE 36 2 225 5 2 Univent
E204 EARLY CHILDROOM ED CLASSROOM 0 0 0 0 Univent
E205 CREATIVE WRITING CLASSROOM (LEFT) 577 38 0 0 Univent
E207 COMPUTER LAB 3 0 2070 47 0 Univent
- GIRLS GYM 0 0 4897 111 0 Air Handling Unit
- BOYS GYM 0 0 4897 111 0 Air Handling Unit
- IMC - LIBRARY 0 0 3985 90 0 Air Handling Unit
- INDUSTRIAL ART (WOODSHOP) 0 0 1564 35 0 Air Handling Unit
- SWIMMING POOL 0 0 10200 231 0 Air Handling Unit
- ADMIN + HEALTH OFFICE 0 0 130 2 0 Air Handling Unit
- ART STUDIOS  0 0 3860 87 0 Air Handling Unit
- AUDITORIUM + STAGE 0 0 12450 282 0 Air Handling Unit
- CLASSROOM (YMCA 2) 0 0 704 16 0 Air Handling Unit
- CLASSROOM (YMCA OST1) 0 0 544 12 0 Air Handling Unit
Sheet Last Modified: 04-05-2021    
School:  Richmond Elementary School
Vendor: Devine
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
3 - 0 1,000 22 0 Radiators/House fan
8 - 0 1,200 27 0 Radiators/House fan
101 Classroom 0 Yes 759 17 17 Radiators/House fan
102 Classroom 0 Yes 759 17 17 Radiators/House fan
102A Nurse 0 Yes 216 4 4 Radiators/House fan
103 Classroom 0 Yes 812 18 18 Radiators/House fan
104 Classroom 0 Yes 812 18 18 Radiators/House fan
105 Main Office 0 Yes 416 9 9 Radiators/House fan
106 Classroom 0 Yes 762 17 17 Radiators/House fan
107 Classroom 0 Yes 742 16 16 Radiators/House fan
108 Faculty Lounge 0 440 10 0 Radiators/House fan
109 Classroom 0 Yes 1,180 26 26 Radiators/House fan
201 Classroom 0 Yes 759 17 17 Radiators/House fan
202 Classroom 0 Yes 759 17 17 Radiators/House fan
203 Classroom 0 Yes 960 21 21 Radiators/House fan
203A Counselor Office 0 167 3 0 Radiators/House fan
204 Classroom 0 Yes 960 21 21 Radiators/House fan
205 Classroom 0 Yes 896 20 20 Radiators/House fan
206 - 0 896 20 0 Radiators/House fan
207 - 0 Yes 792 18 18 Radiators/House fan
208 - 0 792 18 0 Radiators/House fan
209 - 0 Yes 841 19 19 Radiators/House fan
210 - 0 202 4 0 Radiators/House fan
301 - 0 792 18 0 Radiators/House fan
302 Classroom 0 792 18 0 Radiators/House fan
303 - 0 840 19 0 Radiators/House fan
303A - 0 390 8 0 Radiators/House fan
304 - 0 900 20 0 Radiators/House fan
305 - 0 840 19 0 Radiators/House fan
306 Classroom 0 870 19 0 Radiators/House fan
307 - 0 850 19 0 Radiators/House fan
308 - 0 850 19 0 Radiators/House fan
309 - 0 900 20 0 Radiators/House fan
310 - 0 202 4 0 Radiators/House fan
- Principal's Office 0 448 10 0 Radiators/House fan
- Gym 0 2,760 62 0 Heating Ventalation Unit
Sheet Last Modified: 04-01-2021    
School:  Rivera (Bright Futures) Early Childhood Center
Vendor: Goldner
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Basement Cafeteria 1,016 67 4,000 90 67 Air Handling Unit
Basement VVT's in the small Building 138 9 247 5 5 Air Handling Unit
2nd floor Common area vvt's(tall Building) 131 8 247 5 5 Air Handling Unit
4th for upper building Zoned AH for 5 zone floor 0 0 247 5 0 Air Handling Unit
5th floor upper building Zoned AH for 6 zone floor 1 0 247 5 0 Air Handling Unit
- Zone1( group learning room) 0 0 135 3 0 Air Handling Unit
- Zone2 0 0 135 3 0 Air Handling Unit
- Zone3 0 0 135 3 0 Air Handling Unit
- Zone4 0 0 135 3 0 Air Handling Unit
- Zone5 0 0 135 3 0 Air Handling Unit
- Zone6 0 0 135 3 0 Air Handling Unit
Zone1 Group learning open area 1 804 53 280 6 6 Air Handling Unit
Zone 1 Group learning open area 2 0 0 270 6 0 Air Handling Unit
Zone 1 Group learning office 0 0 276 6 0 Air Handling Unit
Zone 1 Large storage 0 0 112 2 0 Air Handling Unit
Zone 1 Small storage 21 1 80 1 1 Air Handling Unit
Zone 2 Office 1 85 5 80 1 1 Air Handling Unit
Zone 2 Office 2 72 4 80 1 1 Air Handling Unit
Zone 2 Office 3 37 2 80 1 1 Air Handling Unit
Zone 2 Spare room 83 5 85 1 1 Air Handling Unit
Zone 2 Hallway 0 0 110 2 0 Air Handling Unit
Zone 2 Copy room 38 2 84 1 1 Air Handling Unit
Zone 3 Conference room vent 1 314 20 1,344 30 20 Air Handling Unit
Zone 3 Conference room vent 2 0 0 1,344 30 0 Air Handling Unit
Zone 3 Conference room vent 3 0 0 1,344 30 0 Air Handling Unit
Zone 4 Admin open area 1 307 20 182 4 4 Air Handling Unit
Zone 4 Admin open area 2 0 0 182 4 0 Air Handling Unit
Zone 4 copy room 57 3 84 1 1 Air Handling Unit
Zone 4 elevator hallway 0 0 144 3 0 Air Handling Unit
Zone 4 admin waiting area 0 0 380 8 0 Air Handling Unit
Zone 4 Vacant office 1 0 0 80 1 0 Air Handling Unit
Zone 4 Vacant office 2 0 0 80 1 0 Air Handling Unit
Zone 4 Supply Room 0 0 110 2 0 Air Handling Unit
Zone 5 Office 1 0 0 80 1 0 Air Handling Unit
Zone 5 Office 2 0 0 80 1 0 Air Handling Unit
Zone 5 Zone 5 meeting Room 1 42 2 80 1 1 Air Handling Unit
Zone 5 Zone 5 meeting Room 2 0 0 80 1 0 Air Handling Unit
Zone 6 Storage 110 7 80 1 1 Air Handling Unit
Zone 6 Office 1 272 18 80 1 1 Air Handling Unit
Zone 6 Office 2 121 8 80 1 1 Air Handling Unit
Zone 6 Office 3 115 7 80 1 1 Air Handling Unit
Zone 6 Office 4 198 13 80 1 1 Air Handling Unit
Zone 6 Office 5 147 9 80 1 1 Air Handling Unit
- Zone 1 0 0 0 0 Air Handling Unit
- Zone 2 0 0 0 0 Air Handling Unit
- Zone 3 0 0 0 0 Air Handling Unit
- Zone 4 0 0 0 0 Air Handling Unit
- Zone 5 0 0 0 0 Air Handling Unit
Zone 1 Group learning area. Diffuser 1 91 6 0 0 Air Handling Unit
Zone 1 Group learning area. Diffuser 2 0 0 0 0 Air Handling Unit
Zone 1 Group learning area. Diffuser 3 0 0 0 0 Air Handling Unit
Zone 1 Group learning area. Diffuser 4 0 0 0 0 Air Handling Unit
Zone 1 Group learning area. Diffuser 5 0 0 0 0 Air Handling Unit
Zone 1 Office 1 18 1 80 1 1 Air Handling Unit
Zone 1 Office 2 19 1 80 1 1 Air Handling Unit
Zone 1 Office 3 12 0 80 1 0 Air Handling Unit
Zone 2 Elevator lobby 0 0 144 3 0 Air Handling Unit
Zone 2 Reception diffuser 1 34 2 0 0 Air Handling Unit
Zone 2 Reception diffuser 2 0 0 80 1 0 Air Handling Unit
Zone 2 Office 1 0 0 80 1 0 Air Handling Unit
Zone 2 Office 2 0 0 80 1 0 Air Handling Unit
Zone 3 Office 1 0 0 80 1 0 Air Handling Unit
Zone 3 Office 2 0 0 80 1 0 Air Handling Unit
Zone 3 Office 3 0 0 80 1 0 Air Handling Unit
Zone 3 Kitchen 1 0 0 214 4 0 Air Handling Unit
Zone 3 Kitchen 2 0 0 214 4 0 Air Handling Unit
Zone 3 Hallway 1 0 0 276 6 0 Air Handling Unit
Zone 3 Hallway 2 0 0 168 3 0 Air Handling Unit
Zone 4 Office 411 0 0 75 1 0 Air Handling Unit
Zone 4 Office 2 0 0 80 1 0 Air Handling Unit
Zone 4 Office 3 0 0 80 1 0 Air Handling Unit
Zone 4 Storage 415 0 0 39 0 0 Air Handling Unit
Zone 4 Hallway 0 0 80 1 0 Air Handling Unit
Zone 4 Assistant Superintendent 0 0 460 10 0 Air Handling Unit
Zone 4 Assistant Superintendent 0 0 460 10 0 Air Handling Unit
Zone 4 Assistant Superintendent 0 0 460 10 0 Air Handling Unit
Zone 4 Storage 408 0 0 80 1 0 Air Handling Unit
Zone 5 Office 403 0 0 80 1 0 Air Handling Unit
Zone 5 Office 403 0 0 80 1 0 Air Handling Unit
Zone 5 Office 404 0 0 80 1 0 Air Handling Unit
Zone 5 Office 0 0 80 1 0 Air Handling Unit
Zone 5 Office 0 0 80 1 0 Air Handling Unit
Zone 5 Conference room 406 0 0 80 1 0 Air Handling Unit
Zone 5 Conference room 406 0 0 80 1 0 Air Handling Unit
Zone 5 Office 407 0 0 142 3 0 Air Handling Unit
Zone 5 Office 409 0 0 80 1 0 Air Handling Unit
3rd floor. VVT#11 Commons area total 50 3 247 5 3 Air Handling Unit
- Elevator hall 9 0 400 9 0 Air Handling Unit
- Elevator hall 0 0 602 13 0 Air Handling Unit
- Commons Area Diffuser 11 0 0 0 Air Handling Unit
- Commons Area Diffuser 11 0 0 0 Air Handling Unit
- Commons Area Diffuser 11 0 0 0 Air Handling Unit
- Commons Area Diffuser 12 0 0 0 Air Handling Unit
- Commons Area Office 2 0 0 0 Air Handling Unit
2nd floor. VVT#8 Commons Are Total 58 3 247 5 3 Air Handling Unit
- Elevator hall 2 0 400 9 0 Air Handling Unit
- Commons Area Diffuser 14 0 0 0 Air Handling Unit
- Commons Area Diffuser 14 0 0 0 Air Handling Unit
- Commons Area Diffuser 12 0 0 0 Air Handling Unit
- Commons Area Diffuser 8 0 0 0 Air Handling Unit
- Commons area office 3 0 0 0 Air Handling Unit
- Class bathroom 3 0 75 1 0 Air Handling Unit
- Staff Bathroom 2 0 0 0 Air Handling Unit
- Elevator hall 2 0 0 0 Air Handling Unit
1st floor VVT#4 1st floor Commons Area Total 46 3 247 5 3 Air Handling Unit
- elevator hall 14 0 480 10 0 Air Handling Unit
- elevator hall 7 0 700 15 0 Air Handling Unit
- Commons area diffuser 7 0 0 0 Air Handling Unit
- Commons area diffuser 8 0 0 0 Air Handling Unit
- Commons area diffuser 2 0 0 0 Air Handling Unit
- Commons area diffuser 4 0 0 0 Air Handling Unit
- Commons area office 3 0 126 2 0 Air Handling Unit
- Class bathroom 0 0 75 1 0 Air Handling Unit
- Staff bathroom 2 0 48 1 0 Air Handling Unit
Room110 Classroom 400 26 900 20 20 Univent
Room 111 Classroom 335 22 900 20 20 Univent
Room 112 Classroom 410 27 900 20 20 Univent
Room 113 Classroom 375 25 900 20 20 Univent
205A Office space 290 19 480 10 10 Univent
205B Office space 484 32 613 13 13 Univent
Room 212 Classroom 259 17 900 20 17 Univent
Room 213 Classroom 502 33 900 20 20 Univent
Room 214 Classroom 277 18 900 20 18 Univent
Room 215 Classroom 544 36 900 20 20 Univent
Room303 Office space 482 32 1,414 32 32 Univent
Room 303B Office space 256 17 360 8 8 Univent
Room 309 Classroom 517 34 1,110 25 25 Univent
Room 310 Classroom 290 19 900 20 19 Univent
Room 311 Classroom 326 21 900 20 20 Univent
Room 312 Classroom 394 26 900 20 20 Univent
VVT 9 Total 10 0 0 0 Air Handling Unit
- Office 3 0 144 3 0 Air Handling Unit
- Office 4 0 144 3 0 Air Handling Unit
- Hallway 4 0 688 15 0 Air Handling Unit
VVT 10 Total 43 2 688 15 2 Air Handling Unit
- Teachers Lounge 16 1 390 8 1 Air Handling Unit
- Bathroom 4 0 48 1 0 Air Handling Unit
- Women's Room 8 0 112 2 0 Air Handling Unit
- Men's Room 3 0 112 2 0 Air Handling Unit
- Hallway 11 0 688 15 0 Air Handling Unit
VVT 6 Total 18 1 0 0 Air Handling Unit
- office 6 0 100 2 0 Air Handling Unit
- Office 5 0 100 2 0 Air Handling Unit
- Office 5 0 100 2 0 Air Handling Unit
- Hallway 2 0 688 15 0 Air Handling Unit
VVT 7 Total 32 2 0 0 Air Handling Unit
- Men's room 7 0 112 2 0 Air Handling Unit
- Women's room 11 0 112 2 0 Air Handling Unit
- Staff bathroom 4 0 52 1 0 Air Handling Unit
- Hallway 4 0 688 15 0 Air Handling Unit
- Hallway 4 0 688 15 0 Air Handling Unit
VVT1 Total 29 1 0 0 Air Handling Unit
- kitchen 6 0 288 6 0 Air Handling Unit
- Storage 4 0 450 10 0 Air Handling Unit
- Men's room 4 0 77 1 0 Air Handling Unit
- Women's room 6 0 77 1 0 Air Handling Unit
- Unisex bathroom 3 0 77 1 0 Air Handling Unit
VVT 3 Total 0 0 0 0 Air Handling Unit
- storage 0 0 328 7 0 Air Handling Unit
- storage 0 0 450 10 0 Air Handling Unit
- storage 0 0 250 5 0 Air Handling Unit
- storage 0 0 175 3 0 Air Handling Unit
VVT 5 Total 41 2 0 0 Air Handling Unit
- hallway 7 0 425 9 0 Air Handling Unit
- Lobby 11 0 375 8 0 Air Handling Unit
- Guard office 8 0 120 2 0 Air Handling Unit
- Staff lockers 4 0 450 10 0 Air Handling Unit
- Hallway 4 0 800 18 0 Air Handling Unit
- Hallway 8 0 168 3 0 Air Handling Unit
Sheet Last Modified: 03-18-2021    
School:  Paul Robeson High School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B-2 Classroom 0.0 0 1,073 24 0 Fan Coil Unit
100 Classroom 380.0 25 940 21 21 Univent
106 Classroom 470.0 31 840 19 19 Univent
108 Classroom 11.0 0 828 18 0 Univent
200 Classroom 89.0 5 696 15 5 Univent
202 Classroom 231.0 15 696 15 15 Univent
204 Classroom 301.0 20 696 15 15 Univent
205 Classroom 304.0 20 672 15 15 Univent
206 Classroom 200.0 13 696 15 13 Univent
207 Classroom 191.0 12 696 15 12 Univent
208 Classroom 125.0 8 696 15 8 Univent
209 Classroom 178.0 11 384 8 8 Univent
210 Classroom 200.0 13 690 15 13 Univent
211 Classroom 262.0 17 851 19 17 Univent
212 Classroom 280.0 18 875 19 18 Univent
213 Classroom 0.0 0 875 19 0 Univent
- AUDITORIUM 0.0 0 2,793 63 0 Air Handling Unit
- Cafeteria 862.0 57 2,343 53 53 Univent
- GYM 812.0 54 3,478 79 54 Air Handling Unit
- MAIN OFFICE 0.0 0 552 12 0 Univent
- Student Lounge 64.0 4 552 12 4 Univent
Sheet Last Modified: 05-03-2021            
School:  Roosevelt Elementary School      
         
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 Yes 1035 23 23 House Fan
102 Classroom 0 Yes 1012 23 23 House Fan
103 Classroom 0 Yes 650 14 14 House Fan
104 Main Office 0 Yes 1225 27 27 House Fan
105 Classroom 0 Yes 660 15 15 House Fan
106 & 106a Classroom 0 Yes 1298 29 29 House Fan
107 Parent Liason 0 Yes 550 12 12 House Fan
108 Classroom 0 Yes 814 18 18 House Fan
109 Classroom 0 Yes 1104 25 25 House Fan
110 Classroom 0 Yes 960 21 21 House Fan
- Lunchroom A 0 Yes 2881 65 65 House Fan
- Lunchroom B 0 Yes 2898 65 65 House Fan
200A Counselor 0 Yes 342 7 7 House Fan
200B Counselor 0 342 7 0 House Fan
200C Counselor 0 Yes 342 7 7 House Fan
201 Classroom 0 Yes 704 16 16 House Fan
202 Classroom 0 Yes 638 14 14 House Fan
203 Classroom 0 Yes 748 17 17 House Fan
205 IMC 0 Yes 1320 30 30 House Fan
206A Counselor 0 Yes 140 3 3 House Fan
206B Counselor 0 Yes 116 2 2 House Fan
206C Counselor 0 Yes 115 2 2 House Fan
206D Counselor 0 Yes 142 3 3 House Fan
206E Counselor 0 Yes 126 2 2 House Fan
207A Room 0 Yes 108 2 2 House Fan
207B Room 0 145 3 0 House Fan
207C Room 0 Yes 108 2 2 House Fan
207D Room 0 103 2 0 House Fan
207E Room 0 Yes 132 3 3 House Fan
208 Art Room 0 Yes 1152 26 26 House Fan
209 Faculty Lounge 0 Yes 696 15 15 House Fan
- Principal Office 0 Yes 629 14 14 House Fan
- Nurse Suite 0 Yes 552 12 12 House Fan
210 Science Lab 0 Yes 700 15 15 House Fan
211 Music 0 Yes 858 19 19 House Fan
212 Classroom 0 Yes 768 17 17 House Fan
213 Classroom 0 Yes 720 16 16 House Fan
214 Classroom 0 Yes 768 17 17 House Fan
215 Classroom 0 Yes 572 13 13 House Fan
216 Classroom 0 Yes 768 17 17 House Fan
217 Classroom 0 Yes 704 16 16 House Fan
218 Classroom 0 Yes 704 16 16 House Fan
219 Classroom 0 Yes 704 16 16 House Fan
220 Classroom 0 704 16 0 House Fan
221A Classroom 0 Yes 342 7 7 House Fan
221B Classroom 0 342 7 0 House Fan
221C Classroom 0 342 7 0 House Fan
222 Classroom 0 336 7 0 House Fan
300A Counselor // Storage 0 342 7 0 House Fan
300B Counselor // Storage 0 342 7 0 House Fan
300C Counselor // Storage 0 342 7 0 House Fan
301 Vice Principals Office 0 Yes 629 14 14 House Fan
302 Classroom 0 Yes 735 16 16 House Fan
303 Classroom 0 Yes 789 17 17 House Fan
304 Classroom 0 Yes 734 16 16 House Fan
305 Classroom 0 Yes 789 17 17 House Fan
306 Classroom 0 1170 26 0 House Fan
307 Classroom 0 Yes 936 21 21 House Fan
308 Classroom 0 Yes 735 16 16 House Fan
309 Classroom 0 952 21 0 House Fan
310 Classroom 0 Yes 840 19 19 House Fan
311 Classroom 0 836 19 0 House Fan
312 Classroom 0 792 18 0 House Fan
313 Classroom 0 920 20 0 House Fan
314 Classroom 0 713 16 0 House Fan
315 Classroom 0 667 15 0 House Fan
316 Classroom 0 713 16 0 House Fan
317 Classroom 0 638 14 0 House Fan
318 Classroom 0 868 19 0 House Fan
319 Classroom 0 Yes 868 19 19 House Fan
320 Classroom 0 Yes 868 19 19 House Fan
324A Counselor, School Police 0 342 7 0 House Fan
324B Counselor, School Police 0 342 7 0 House Fan
324C Counselor, School Police 0 342 7 0 House Fan
322 Classroom 0 Yes 868 19 19 House Fan
321 Classroom 0 Yes 861 19 19 House Fan
Sheet Last Modified: 04-26-2021    
School:  William Rowen Elementary School
Vendor: EMCOR EMCOR Part 2 Devine
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Auditorium 0 0 4256 96 0 House Fan
- Cafeteria/Gym 0 0 Yes 5220 118 118 Univent
- Library 328 21 1456 33 21 Univent
101 Classroom 457 30 1128 25 25 Univent
102 Classroom 545 36 1128 25 25 Univent
103 Classroom 42 2 Yes 266 6 6 Univent
104 Classroom 0 0 Yes 816 18 18 Univent
105 Classroom 304 20 816 18 18 Univent
106 Classroom 0 0 Yes 816 18 18 Univent
107 Classroom 299 19 816 18 18 Univent
108 Classroom 0 0 Yes 720 16 16 Univent
109 Classroom 234 15 720 16 15 Univent
110 Classroom 399 26 720 16 16 Univent
111 Classroom 440 29 720 16 16 Univent
112 Classroom 68 4 720 16 4 Univent
113 Classroom 235 15 720 16 15 Univent
- Nurse's Office 235 15 192 4 4 Univent
201 Classroom 373 24 920 20 20 Univent
202 Classroom 396 26 920 20 20 Univent
203 Classroom 307 20 442 10 10 Univent
204 Classroom 299 19 384 8 8 Univent
205 Classroom 309 20 720 16 16 Univent
206 Classroom 230 15 720 16 15 Univent
207 Classroom 327 21 720 16 16 Univent
208 Classroom 272 18 720 16 16 Univent
209 Classroom 324 21 720 16 16 Univent
210 Classroom 276 18 720 16 16 Univent
211 Classroom 336 22 720 16 16 Univent
212 Classroom 272 18 720 16 16 Univent
213 Classroom 284 18 720 16 16 Univent
214 Classroom 271 18 720 16 16 Univent
215 Classroom 280 18 720 16 16 Univent
216 Classroom 300 20 744 16 16 Univent
- Main Office 0 Yes 552 12 12
- Principal 0 Yes 270 6 6
Sheet Last Modified: 04-23-2021    
School:  Roxborough High School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
114 Classroom 0 0 857 19 0 Univent
115 Classroom 30 2 870 19 2 Univent
116 Classroom 45 3 690 15 3 Univent
117 Weight Room 30 2 814 18 2 Univent
118 Classroom 55 3 702 15 3 Univent
119 Classroom 270 18 877 19 18 Univent
120 Classroom 85 5 694 15 5 Univent
121 Classroom 40 2 1207 27 2 Univent
124A-1 Classroom 55 3 621 14 3 Univent
124B-1 Classroom 30 2 672 15 2 Univent
126 Classroom 0 0 1841 41 0 Univent
128 Classroom 50 3 1501 34 3 Univent
203 Classroom 0 Yes 682 15 15
205 Classroom 0 Yes 682 15 15
215 Classroom 0 0 829 18 0 Univent
216 Classroom 50 3 834 18 3 Univent
217 Classroom 0 0 686 15 0 Univent
218 Classroom 0 0 724 16 0 Univent
219 Classroom 55 3 842 19 3 Univent
220 Classroom 60 4 616 14 4 Univent
221 Classroom 35 2 845 19 2 Univent
223 Classroom 55 3 1072 24 3 Univent
224 Classroom 55 3 1010 22 3 Univent
235 Classroom 0 Yes 839 19 19
309 Classroom 0 Yes 997 22 22
312 Classroom 0 Yes 1071 24 24
319 Classroom 40 2 644 14 2 Univent
320 Classroom 40 2 721 16 2 Univent
321 Classroom 55 3 924 21 3 Univent
322 Classroom 30 2 723 16 2 Univent
323 Classroom 60 4 777 17 4 Univent
324 Classroom 55 3 942 21 3 Univent
325 Classroom 45 3 Yes 325 7 7 Univent
326 Classroom 55 3 1000 22 3 Univent
- Gymnasium 740 49 11475 260 49 Air Handling Unit
- Library 2,335.00 155 2622 59 59 Air Handling Unit
East Office Office 75 5 0 0
West Office Office 110 7 0 0 Air Handling Unit
- Alumni Room 255 17 377 8 8 Air Handling Unit
- Computer Lab 1,285.00 85 870 19 19 Air Handling Unit
Sheet Last Modified: 03-18-2021      
School:  Arts Academy @ Benjamin Rush High School
Vendor: Goldner Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
103 Lab Classroom 465 31 748 17 17 Univent & Air Handling Unit
103 Lab Classroom 465 31 0 0 Univent & Air Handling Unit
104 GraphicArts Classroom 928 61 1,840 41 41 Univent & Air Handling Unit
104 Graphic Arts Classroom 946 63 0 0 Univent & Air Handling Unit
105 IMC Classroom 2,959.00 197 0 0 Air Handling Unit
105D Student Property Office 281 18 0 0 Air Handling Unit
105E IMC Copy Office 960 64 0 0 Air Handling Unit
105F Cart Storage 368 24 0 0 Air Handling Unit
105G Tech Equip Office 255 17 0 0 Air Handling Unit
105H IMC Office 201 13 0 0 Air Handling Unit
105J IMC Storage room 252 16 0 0 Air Handling Unit
105K IMC Conference Rm 312 20 0 0 Air Handling Unit
106 Art Studio Classroom 1,326.00 88 1,020 23 23 Air Handling Unit
107 storage room 275 18 280 6 6 Air Handling Unit
122 Art Studio Classroom 1,689.00 112 1,496 34 34 Air Handling Unit
123 Production Studio Classroom 2,228.00 148 1,254 28 28 Air Handling Unit
126A Boys Locker Room 0 0 0 0
127A Girls Locker Room 0 0 0 0
129 Production Booth Classroom 842 56 264 6 6 Air Handling Unit
131A Changing Room Classroom 238 15 72 1 1 Air Handling Unit
131B Changing Room Classroom 175 11 192 4 4 Air Handling Unit
133 Storage Room 428 28 580 13 13 Air Handling Unit
134 Music Classroom 1,076.00 71 748 17 17 Air Handling Unit
135 Music Classroom 1,097.00 73 748 17 17 Air Handling Unit
136 Practice Classroom 113 7 36 0 0 Air Handling Unit
137 Practice Classroom 116 7 36 0 0 Air Handling Unit
138 Library 88 5 0 0 Air Handling Unit
140 Vocal Music Classroom 3,597.00 239 0 0 Air Handling Unit
141 Scene Shop Classroom 994 66 0 0 Univent & Air Handling Unit
142 Vocal Theory Classroom 347 23 748 17 17 Univent & Air Handling Unit
143 Music Theory Classroom 963 64 748 17 17 Univent & Air Handling Unit
144 Music Tech Lab Classroom 699 46 748 17 17 Univent & Air Handling Unit
145A Clerical Office 362 24 720 16 16 Air Handling Unit
145B Roster Office 161 10 80 1 1 Air Handling Unit
145D Copier Office 219 14 75 1 1 Air Handling Unit
145E Conference Office 341 22 128 2 2 Air Handling Unit
145F Principal Office 328 21 247 5 5 Air Handling Unit
145J Asset Princ.Office 114 7 272 6 6 Air Handling Unit
145K Asset Princ.Office 67 4 180 4 4 Air Handling Unit
146A Clinic Office 45 3 120 2 2 Air Handling Unit
146B ClinicWaitingoffice 506 33 221 5 5 Air Handling Unit
146D Exam Room 328 21 60 1 1 Air Handling Unit
147 Counselor Waiting Area 450 30 288 6 6 Air Handling Unit
147B Counselor Office 149 9 221 5 5 Air Handling Unit
147D Counselor's Office 283 18 60 1 1 Air Handling Unit
147E Counselor Office 157 10 120 2 2 Air Handling Unit
147F Counselor Conference Office 311 20 169 3 3 Air Handling Unit
147G Counselor's Office 383 25 180 4 4 Air Handling Unit
148A Camera office 565 37 120 2 2 Air Handling Unit
148B Storage Room 121 8 0 0 Air Handling Unit
148C Records Office 118 7 0 0 Air Handling Unit
148D Security Office 125 8 0 0 Air Handling Unit
148E Operations Office 372 24 0 0 Air Handling Unit
200 General Classroom 649 43 748 17 17 Univent & Air Handling Unit
201 General Classroom 532 35 748 17 17 Univent & Air Handling Unit
202 General Classroom 692 46 748 17 17 Univent & Air Handling Unit
204 General Classroom 447 29 748 17 17 Univent & Air Handling Unit
205 General Classroom 566 37 748 17 17 Univent & Air Handling Unit
209 Social Ed. Classroom 779 51 748 17 17 Univent & Air Handling Unit
210 General Classroom 662 44 748 17 17 Univent & Air Handling Unit
211 General Classroom 562 37 748 17 17 Univent & Air Handling Unit
212 General Classroom 423 28 748 17 17 Univent & Air Handling Unit
213 General Classroom 597 39 748 17 17 Univent & Air Handling Unit
214 General Classroom 868 57 748 17 17 Univent & Air Handling Unit
215 General Classroom 442 29 0 0 Fan Coil Unit & Air Handling Unit
216 Physical Science Classroom 970 64 1,344 30 30 Fan Coil Unit & Air Handling Unit
217 Prep Classroom 299 19 0 0 Fan Coil Unit & Air Handling Unit
219 Physics Classroom 630 42 1,344 30 30 Fan Coil Unit & Air Handling Unit
220 Storage room 418 27 0 0 Air Handling Unit
221 General Classroom 324 21 0 0 Fan Coil Unit & Air Handling Unit
221B Storage Room 135 9 0 0 Air Handling Unit
221C Storage Room 130 8 0 0 Air Handling Unit
222 Biology Classroom 633 42 1,764 40 40 Fan Coil Unit & Air Handling Unit
223 Prep Classroom 322 21 312 7 7 Fan Coil Unit & Air Handling Unit
224 Chemistry Classroom 616 41 1,716 39 39 Fan Coil Unit & Air Handling Unit
224A Storage Room 135 9 0 0 Air Handling Unit
225 Instructional Room 483 32 0 0 Fan Coil Unit & Air Handling Unit
234 Lab Classroom 1,107.00 73 850 19 19 Fan Coil Unit & Air Handling Unit
235 Lab Classroom 595 39 0 0 Fan Coil Unit & Air Handling Unit
235 Lab Classroom 465 31 0 0 Univent & Air Handling Unit
236 Multipurpose Classroom 636 42 1,156 26 26 Fan Coil Unit & Air Handling Unit
237 Foreign Language Classroom 613 40 1,156 26 26 Fan Coil Unit & Air Handling Unit
240 Commercial Art Classroom 845 56 0 0 Fan Coil Unit & Air Handling Unit
241 General Classroom 664 44 0 0 Fan Coil Unit & Air Handling Unit
242 Instructional Room 551 36 0 0 Fan Coil Unit & Air Handling Unit
243 General Classroom 518 34 0 0 Fan Coil Unit & Air Handling Unit
244 General Classroom 737 49 748 17 17 Univent & Air Handling Unit
245 General Classroom 586 39 748 17 17 Univent & Air Handling Unit
246 General Classroom 719 47 748 17 17 Univent & Air Handling Unit
247 General Classroom 705 47 748 17 17 Univent & Air Handling Unit
248 General Classroom 909 60 748 17 17 Univent & Air Handling Unit
249 General Classroom 779 51 748 17 17 Univent & Air Handling Unit
251 General Classroom 671 44 748 17 17 Univent & Air Handling Unit
252 General Classroom 876 58 748 17 17 Univent & Air Handling Unit
253 General Classroom 608 40 748 17 17 Univent & Air Handling Unit
254 General Classroom 633 42 748 17 17 Univent & Air Handling Unit
255 General Classroom 738 49 748 17 17 Univent & Air Handling Unit
256 General Classroom 684 45 748 17 17 Univent & Air Handling Unit
- Auditorium 18,527.00 1235 0 0 Air Handling Unit
- Cafeteria 10,458.00 697 0 0 Air Handling Unit
- Studios Area and Assoc. Corridors, fresh air vent in rooms 18,369.00 1224 0 0 Air Handling Unit
- Instrumental Music Area 14,678.00 978 0 0 Air Handling Unit
- Gym 8,904 593 0 0 Air Handling Unit
- ICM Classroom Area 11,044.00 736 0 0 Air Handling Unit
Sheet Last Modified: 04-27-2021    
School:  Walter Biddle Saul High School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
A1 A1 732 48 864 19 19 Air Handling Unit
A1/A2 Storage 288 19 255 5 5 Air Handling Unit
A2 A2 703 46 864 19 19 Air Handling Unit
A3 A3 395 26 792 18 18 Univent
A5 A5 1,123 74 740 16 16 Univent
A21 A21 0 0 570 12 0 Air Handling Unit
A22 A22 487 32 620 14 14 Univent
A23 A23 699 46 888 20 20 Univent
A24 A24 1,147 76 888 20 20 Univent
A25 A25 878 58 888 20 20 Univent
A26 A26 449 29 888 20 20 Univent
A29 A29 0 Yes 864 19 19
1 1 240 16 864 19 19 Univent
2 2 70 4 551 12 12 Univent
3 3 900 60 1134 25 25 Univent
4 4 0 0 896 20 0 Univent
100 100 215 14 620 14 14 Univent
102 102 342 22 620 14 14 Univent
103 103 206 13 780 17 17 Univent
104 104 265 17 640 14 14 Univent
200 200 258 17 620 14 14 Univent
201 201 244 16 620 14 14 Univent
202 202 251 16 620 14 14 Univent
203 203 173 11 620 14 14 Univent
204 204 226 15 620 14 14 Univent
205 205 468 31 660 15 15 Univent
206 206 560 37 110 2 2 Univent
208 208 232 15 600 13 13 Univent
210 210 244 16 465 10 10 Univent
Food Science Laboratory 0 560 12 12
- Nurse 316 21 260 5 5 Univent
- Staff Lounge 0 0 384 8 0 Univent
Sheet Last Modified: 05-03-2021    
School:  William L. Sayre High School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 518.0 34 720 16 16 Univent
102 Lounge 229.0 15 408 9 9 Univent
103 Music 327.0 21 1260 28 28 Univent
104 Office 0 0 360 8 0 Univent
105 Classroom 375 25 1504 34 34 Univent
106 Classroom 389 25 768 17 17 Univent
107 Classroom 517 34 1408 32 32 Univent
108 Classroom 0 0 768 17 0 Univent
109 Classroom 0 0 Yes 1120 25 25 Univent
110 Classroom 351 23 768 17 17 Univent
111 Classroom 638 42 1363 30 30 Univent
115 Classroom 369 24 896 20 20 Univent
117 Classroom 0 0 Yes 756 17 17 Univent
119 Classroom 192 12 868 19 19 Univent
131 Classroom 402 26 729 16 16 Univent
133 Office 357 23 288 6 6 Univent
135 Boy's Infirmary 287 19 132 3 3 Univent
137 Girl's Infirmary 142 9 285 6 6 Univent
139 Classroom 202 13 1024 23 23 Univent
141 Classroom 384 25 1188 27 27 Univent
200 Youth Court 693 46 744 16 16 Univent
200 Classroom 410 27 592 13 13 Univent
203 Classroom 808 53 1504 34 34 Univent
204 Classroom 294 19 744 16 16 Univent
205 Classroom 762 50 1504 34 34 Univent
206 Classroom 473 31 696 15 15 Univent
207 Classroom 702 46 1280 29 29 Univent
208 Classroom 548 36 744 16 16 Univent
210 Classroom 246 16 744 16 16 Univent
211 Classroom 835 55 1344 30 30 Univent
212 Classroom 367 24 744 16 16 Univent
215 Classroom 0 0 621 14 0 Univent
216 Classroom 731 48 864 19 19 Univent
217 Classroom 81 5 990 22 22 Univent
219 Classroom 0 0 1008 22 0 Univent
220 Classroom 301 20 744 16 16 Univent
221 Classroom 92 6 987 22 22 Univent
222 Classroom 623 41 744 16 16 Univent
223 Classroom 0 0 902 20 0 Univent
224 Classroom 419 27 744 16 16 Univent
225 Classroom 264 17 725 16 16 Univent
226 Classroom 0 0 744 16 0 Univent
228 Classroom 202 13 840 19 19 Univent
229 Classroom 401 26 1458 33 33 Univent
230 Classroom 797 53 792 18 18 Univent
231 Classroom 509 33 999 22 22 Univent
232 Classroom 1571 104 960 21 21 Univent
234 Classroom 1041 69 816 18 18 Univent
235 Classroom 778 51 1400 31 31 Univent
236 Classroom 809 53 744 16 16 Univent
240 Classroom 683 45 696 15 15 Univent
242 Classroom 274 18 912 20 20 Univent
244 Classroom 0 0 768 17 0 Univent
246 Classroom 415 27 936 21 21 Univent
248 Classroom 0 0 666 15 0 Univent
- Auditorium 0 0 10250 232 0 House Fan
- Cafeteria 0 0 10540 239 0 House Fan
- Counseling Office 234 15 187 4 4 Univent
- Girls Gym 0 0 Yes 7630 173 173 House Fan
- Boys Gym 0 0 Yes 7630 173 173 House Fan
- Handball Court 0 0 800 18 0 Air Handling Unit
- Library 0 0 3432 78 0 Univent
- IMC Computer 0 0 744 16 0 Univent
- Kitchen Cooler room 0 0 182 4 0 Univent
- Locker room 0 0 180 4 0 Air Handling Unit & Univent
- Boys Locker Rm 0 0 7470 169 0 Whole House
 Return Air Fan & Air Handling Unit
- Girls Locker Rm 0 0 7470 169 0 Whole House
 Return Air Fan & Air Handling Unit
- Main Office 153 10 1128 25 25 Univent
- Office 0 0 198 4 0 Univent
- Rec Room 0 0 9780 222 0 House Fan
Sheet Last Modified: 03-18-2021    
School:  High School of the Future
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Auditorium 4,278.00 285 4935 112 112 Air Handling Unit
10 Mens Room 139 9 205 4 4 Air Handling Unit
12 Womens Room 88 5 215 4 4 Air Handling Unit
14 Storage 26 1 275 6 6 Air Handling Unit
16 IDF 15 1 165 3 3 Air Handling Unit
17 Electrical room 40 2 75 1 1 Air Handling Unit
19 Music Library 30 2 120 2 2 Air Handling Unit
21 Instrument stroage 96 6 370 8 8 Air Handling Unit
22 Uniform Room 49 3 100 2 2 Air Handling Unit
23 Practice room 41 2 100 2 2 Air Handling Unit
24 Practice room 42 2 100 2 2 Air Handling Unit
25 Practice room 43 2 100 2 2 Air Handling Unit
26 Vocal Music Room 184 12 1400 31 31 Air Handling Unit
27 Practice Room 27 1 100 2 2 Air Handling Unit
28 Practice Room 36 2 100 2 2 Air Handling Unit
29 Practice Room 41 2 100 2 2 Air Handling Unit
30 Dressing Room 45 3 1300 29 29 Air Handling Unit
31 Music Intrrument room 966 64 1800 40 40 Air Handling Unit
32 Dressing Room 104 6 900 20 20 Air Handling Unit
33 Dressing Room 45 3 300 6 6 Air Handling Unit
34 Scene shop 537 35 1200 27 27 Air Handling Unit
58 Kitchen 0 0 0 Air Handling Unit
101 Vestibule 102.0 6 555 12 12 Air Handling Unit
103 Camera Room 49.0 3 100 2 2 Air Handling Unit
104 Security Room 59.0 3 200 4 4 Air Handling Unit
105 Corridor  0 50 1 1 Air Handling Unit
106 Electric room 63.0 4 135 3 3 Air Handling Unit
107 Equipment room 55.0 3 205 4 4 Air Handling Unit
110 waiting room 101.0 6 200 4 4 Air Handling Unit
112 clerical office  315.0 21 635 14 14 Air Handling Unit
113 work/ conf room 97.0 6 200 4 4 Air Handling Unit
114 Admin conf room 81.0 5 200 4 4 Air Handling Unit
115 Principal office  80.0 5 255 5 5 Air Handling Unit
115A Principal bathroom  8.0 0 60 1 1 Air Handling Unit
117 Operations office 24.0 1 120 2 2 Air Handling Unit
118 vault room 25.0 1 200 4 4 Air Handling Unit
119 supply room 12.0 0 120 2 2 Air Handling Unit
121 Nurse 38.0 2 95 2 2 Air Handling Unit
121 Waiting room  17.0 1 95 2 2 Air Handling Unit
123 Nurse office  14.0 0 0 0 Air Handling Unit
125 Exam room B 14.0 0 100 2 2 Air Handling Unit
125 Exam room A 13.0 0 100 2 2 Air Handling Unit
130 Parent volunteer room 13.0 0 480 10 10 Air Handling Unit
130 Parent volunteer room 13.0 0 480 10 10 Air Handling Unit
131 Plasma screen room 9.0 0 45 1 1 Air Handling Unit
131 Janitor closet  0 30 0 0 Air Handling Unit
132 Womens room 25.0 1 220 5 5 Air Handling Unit
132 Womens Room 20.0 1 220 5 5 Air Handling Unit
132 Womens room 0 220 5 5 Air Handling Unit
132 Womens room 0 220 5 5 Air Handling Unit
133 Mens room 49.0 3 245 5 5 Air Handling Unit
133 Mens room 38.0 2 245 5 5 Air Handling Unit
135 Mens Room 0 245 5 5 Air Handling Unit
135 Mens Room 0 245 5 5 Air Handling Unit
139 Mens locker 14.0 0 375 8 8 Air Handling Unit
139 Mens Locker 14.0 0 375 8 8 Air Handling Unit
139 Mens Locker 15.0 1 375 8 8 Air Handling Unit
139 Mens Locker 15.0 1 375 8 8 Air Handling Unit
139 Mens Locker room 0 375 8 8 Air Handling Unit
139 Mens locaker room 0 375 8 8 Air Handling Unit
140 office  48.0 3 300 6 6 Air Handling Unit
140 office  0 300 6 6 Air Handling Unit
141 toilet room 9.0 0 90 2 2 Air Handling Unit
141 toilet room 0 90 2 2 Air Handling Unit
142 Training room 20.0 1 375 8 8 Air Handling Unit
142 Training room 22.0 1 375 8 8 Air Handling Unit
142 training room 0 375 8 8 Air Handling Unit
143 Womens Locker 14.0 0 750 17 14 Air Handling Unit
143 Womens Locker 14.0 0 750 17 14 Air Handling Unit
143 Womens  Locker 15.0 1 750 17 15 Air Handling Unit
143 Womens LOcker 16.0 1 750 17 16 Air Handling Unit
143 Womens locker room 0 750 17 17 Air Handling Unit
143 Womens locker room 0 750 17 17 Air Handling Unit
144 Office  44.0 2 300 6 6 Air Handling Unit
144 office  0 300 6 6 Air Handling Unit
145 Toilet Room 9.0 0 65 1 1 Air Handling Unit
145 toilet room 0 65 1 1 Air Handling Unit
146 Corridor  6.0 0 150 3 3 Air Handling Unit
146 corridor  0 150 3 3 Air Handling Unit
147 Fitness center 44.0 2 1545 35 35 Air Handling Unit
147 Fitness center 62.0 4 1545 35 35 Air Handling Unit
147 Fitness center 47.0 3 1545 35 35 Air Handling Unit
147 Fitness center 0 1545 35 35 Air Handling Unit
147 Fitness center 0 1545 35 35 Air Handling Unit
147 Fitness center 0 1545 35 35 Air Handling Unit
148 Visitor locker room 39.0 2 485 11 11 Air Handling Unit
148 Visitor locker room 44.0 2 485 11 11 Air Handling Unit
148 visitor locaker room 0 485 11 11 Air Handling Unit
148 Visitor locaker room 0 485 11 11 Air Handling Unit
148 visitor locker room 0 485 11 11 Air Handling Unit
149 IDF 15.0 1 50 1 1 Air Handling Unit
149 IDF 0 50 1 1 Air Handling Unit
150 work shop  0 155 3 3 Air Handling Unit
151 Custodial office 0 155 3 3 Air Handling Unit
152 Corridor  34.0 2 2055 46 34 Air Handling Unit
152 Corridor  28.0 1 2055 46 28 Air Handling Unit
152 Corridor  28.0 1 2055 46 28 Air Handling Unit
155 Corridor 0 145 3 3 Air Handling Unit
156 Locker room 0 60 1 1 Air Handling Unit
158 Kitchen  0 1485 33 33 Air Handling Unit
158 Kitchen 0 1485 33 33 Air Handling Unit
158 Kitchen 0 1485 33 33 Air Handling Unit
158 Kitchen 0 1485 33 33 Air Handling Unit
158 Kitchen 0 1485 33 33 Air Handling Unit
158 Kitchen 0 1485 33 33 Air Handling Unit
158 Kitchen 0 1485 33 33 Air Handling Unit
158 Kitchen 0 1485 33 33 Air Handling Unit
158 Kitchen  0 1485 33 33 Air Handling Unit
158 Dishwashing 0 390 8 8 Air Handling Unit
158 Kitchen  0 1485 33 33 Air Handling Unit
160 Dishwashing 0 390 8 8 Air Handling Unit
161 Serving  0 695 15 15 Air Handling Unit
161 Serving  0 695 15 15 Air Handling Unit
161 Serving  0 695 15 15 Air Handling Unit
162 Kitchen office  0 80 1 1 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria  0 7850 178 178 Air Handling Unit
163 Cafeteria 0 7850 178 178 Air Handling Unit
164 Faculty dining  0 610 13 13 Air Handling Unit
164 Faculty dining  0 610 13 13 Air Handling Unit
166 Mens Room 71.0 4 220 5 5 Air Handling Unit
167 Womens Room  50.0 3 245 5 5 Air Handling Unit
170 Special Education  24.0 1 1205 27 24 Air Handling Unit
170 Special Education  21.0 1 1205 27 21 Air Handling Unit
170 Special Education  31.0 2 1205 27 27 Air Handling Unit
170 Special Education  30.0 2 1205 27 27 Air Handling Unit
173 Driver education lab  70.0 4 1200 27 27 Air Handling Unit
173 Driver education lab  70.0 4 1200 27 27 Air Handling Unit
173 Driver education lab  69.0 4 1200 27 27 Air Handling Unit
173 Driver education lab  65.0 4 1200 27 27 Air Handling Unit
174 Science Prep  59.0 3 200 4 4 Air Handling Unit
175 Science Lab  55.0 3 1505 34 34 Air Handling Unit
175 Science LAB  54.0 3 1505 34 34 Air Handling Unit
175 science lab  47.0 3 1505 34 34 Air Handling Unit
175 science lab  41.0 2 1505 34 34 Air Handling Unit
175 science lab  59.0 3 1505 34 34 Air Handling Unit
175 science lab  63.0 4 1505 34 34 Air Handling Unit
177 table storage  0.0 0 610 13 0 Air Handling Unit
177 table storage  0.0 0 610 13 0 Air Handling Unit
178 teacher storage  0.0 0 125 2 0 Air Handling Unit
179 services room 0.0 0 160 3 0 Air Handling Unit
180 IDF closet 0.0 0 155 3 0 Air Handling Unit
181 School store  0.0 0 200 4 0 Air Handling Unit
183 Computer lab 0 900 20 20 Air Handling Unit
183 Computer lab 374.0 24 900 20 20 Air Handling Unit
183 Computer lab 362.0 24 900 20 20 Air Handling Unit
183 Computer lab 477.0 31 900 20 20 Air Handling Unit
183 Computer lab 477.0 31 900 20 20 Air Handling Unit
184 Interactive learning center 667.0 44 2800 63 63 Air Handling Unit
184 Interactive learning center 473.0 31 2800 63 63 Air Handling Unit
184 Interactive learning center 570.0 38 2800 63 63 Air Handling Unit
184 Interactive learning center 536.0 35 2800 63 63 Air Handling Unit
184 Interactive learning center 417.0 27 2800 63 63 Air Handling Unit
185 Individual reading  37.0 2 390 8 8 Air Handling Unit
185 Individual reading  32.0 2 390 8 8 Air Handling Unit
185 Individual reading  27.0 1 390 8 8 Air Handling Unit
185 Individual reading  31.0 2 390 8 8 Air Handling Unit
186 Literacy Nook 35.0 2 900 20 20 Air Handling Unit
186 Literacy Nook 28.0 1 900 20 20 Air Handling Unit
186 Literacy Nook 20.0 1 900 20 20 Air Handling Unit
186 Literacy Nook 20.0 1 900 20 20 Air Handling Unit
186 Literacy Nook 20.0 1 900 20 20 Air Handling Unit
186 Literacy Nook 20.0 1 900 20 20 Air Handling Unit
186 Literacy Nook 30.0 2 900 20 20 Air Handling Unit
186 Literacy Nook 14.0 0 900 20 14 Air Handling Unit
187 Copy Room 111.0 7 250 5 5 Air Handling Unit
187 Copy Room 86.0 5 250 5 5 Air Handling Unit
188 Conference room  87.0 5 200 4 4 Air Handling Unit
188 Conferenceroom 90.0 6 200 4 4 Air Handling Unit
189 Visitor room  165.0 11 605 13 13 Air Handling Unit
189 Visitor room  202.0 13 605 13 13 Air Handling Unit
189 Visitor room  177.0 11 605 13 13 Air Handling Unit
190 ILC office  120.0 8 135 3 3 Air Handling Unit
191 storage  112.0 7 170 3 3 Air Handling Unit
192 1,210.0 1,210 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
192 School street 0 9910 225 225 Air Handling Unit
201 Computer tech 0 1200 27 27 Air Handling Unit
201 Computer tech 0 1200 27 27 Air Handling Unit
201 Computer tech 0 1200 27 27 Air Handling Unit
203 Teachers Copy center 0 300 6 6 Air Handling Unit
204 IT Web Design  0 1190 27 27 Air Handling Unit
204 IT Web Design  0 1190 27 27 Air Handling Unit
204 IT Web Design  0 1190 27 27 Air Handling Unit
204 IT Web Design  0 1190 27 27 Air Handling Unit
204 IT Web Design  0 1190 27 27 Air Handling Unit
204 IT Web Design  0 1190 27 27 Air Handling Unit
205 Storage 0 150 3 3 Air Handling Unit
207 Clerical 0 100 2 2 Air Handling Unit
207 Clerical  0 100 2 2 Air Handling Unit
208 Office 0 120 2 2 Air Handling Unit
209 Roster Room 0 120 2 2 Air Handling Unit
210 200 0 Air Handling Unit
211 200 0 Air Handling Unit
212 Staff Room 0 120 2 2 Air Handling Unit
213 Staff Room 0 120 2 2 Air Handling Unit
214 Assistant Principle office 0 120 2 2 Air Handling Unit
215 120 0 Air Handling Unit
216 Rest Room 0 50 1 1 Air Handling Unit
217 Records 0 300 6 6 Air Handling Unit
218 120 0 Air Handling Unit
219 PE Director 0 150 3 3 Air Handling Unit
220 150 0 Air Handling Unit
221 120 0 Air Handling Unit
222 120 0 Air Handling Unit
223 Counselor office  0 120 2 2 Air Handling Unit
224 Success center 0 900 20 20 Air Handling Unit
224 Success center 0 900 20 20 Air Handling Unit
224 Success center 0 900 20 20 Air Handling Unit
224 Success center 0 900 20 20 Air Handling Unit
225 450 0 Air Handling Unit
225 450 0 Air Handling Unit
226 Computer flex lab 0 1200 27 27 Air Handling Unit
226 Computer flex lab 0 1200 27 27 Air Handling Unit
226 Computer flex lab 0 1200 27 27 Air Handling Unit
226 Computer flex lab 0 1200 27 27 Air Handling Unit
227 General classroom 0 900 20 20 Air Handling Unit
227 General Classroom 0 900 20 20 Air Handling Unit
227 General Classroom 0 900 20 20 Air Handling Unit
227 General Classroom 0 900 20 20 Air Handling Unit
228 Art Storage 0 200 4 4 Air Handling Unit
229 0 Air Handling Unit
230 Art room 0 1800 40 40 Air Handling Unit
230 Art room 0 1800 40 40 Air Handling Unit
230 Art room 0 1800 40 40 Air Handling Unit
230 Art room 0 1800 40 40 Air Handling Unit
230 Art room 0 1800 40 40 Air Handling Unit
230 Art room 0 1800 40 40 Air Handling Unit
231A 0 Air Handling Unit
231A 0 Air Handling Unit
231B Special education 0 900 20 20 Air Handling Unit
231B Special education 0 900 20 20 Air Handling Unit
237 Mens Room  57.0 3 250 5 5 Air Handling Unit
240 Womens Room  76.0 5 255 5 5 Air Handling Unit
241 Storage 0.0 0 900 20 0 Air Handling Unit
241 Storage 0.0 0 900 20 0 Air Handling Unit
241 Storage 0.0 0 900 20 0 Air Handling Unit
241 Storage 0.0 0 900 20 0 Air Handling Unit
242 chemistry classroom 53.0 3 1500 34 34 Air Handling Unit
242 chemistry classroom 47.0 3 1500 34 34 Air Handling Unit
242 chemistry classroom 51.0 3 1500 34 34 Air Handling Unit
242 chemistry classroom 56.0 3 1500 34 34 Air Handling Unit
242 chemistry classroom 56.0 3 1500 34 34 Air Handling Unit
242 chemistry classroom 41.0 2 1500 34 34 Air Handling Unit
243 Storage  84.0 5 200 4 4 Air Handling Unit
244 Planning  72.0 4 290 6 6 Air Handling Unit
245 Biology class 97.0 6 245 5 5 Air Handling Unit
245 Biology class 97.0 6 1290 29 29 Air Handling Unit
245 Biology class 78.0 5 1290 29 29 Air Handling Unit
245 Biology class 83.0 5 1290 29 29 Air Handling Unit
245 Biology class 93.0 6 1290 29 29 Air Handling Unit
245 Biology class 51.0 3 1290 29 29 Air Handling Unit
246 General classroom 67.0 4 900 20 20 Air Handling Unit
246 General classroom 50.0 3 900 20 20 Air Handling Unit
246 General classroom 66.0 4 900 20 20 Air Handling Unit
246 General classroom 63.0 4 900 20 20 Air Handling Unit
247 General classroom 68.0 4 900 20 20 Air Handling Unit
247 General classroom 72.0 4 900 20 20 Air Handling Unit
247 General classroom 69.0 4 900 20 20 Air Handling Unit
247 General classroom 81.0 5 900 20 20 Air Handling Unit
248 N/A 107.0 7 135 3 3 Air Handling Unit
249 General classroom 59.0 3 745 16 16 Air Handling Unit
249 General classroom 62.0 4 745 16 16 Air Handling Unit
249 General classroom 90.0 6 745 16 16 Air Handling Unit
249 General classroom 77.0 5 745 16 16 Air Handling Unit
250 General classroom 68.0 4 795 18 18 Air Handling Unit
250 General classroom 60.0 4 795 18 18 Air Handling Unit
250 General classroom 80.0 5 795 18 18 Air Handling Unit
250 General classroom 83.0 5 795 18 18 Air Handling Unit
251 N/A 173.0 11 0 0 Air Handling Unit
252 General classroom 57.0 3 800 18 18 Air Handling Unit
252 General classroom 56.0 3 800 18 18 Air Handling Unit
252 General classroom 88.0 5 800 18 18 Air Handling Unit
252 General classroom 79.0 5 800 18 18 Air Handling Unit
253 Corridor  26.0 1 6010 136 26 Air Handling Unit
253 Corridor  25.0 1 6010 136 25 Air Handling Unit
253 Corridor  28.0 1 6010 136 28 Air Handling Unit
254 Corridor  0 0 0 Air Handling Unit
254 Corridor  0 0 0 Air Handling Unit
254 Corridor  0 0 0 Air Handling Unit
254 Corridor  0 0 0 Air Handling Unit
254 Corridor 0 0 0 Air Handling Unit
301 General classroom 0 825 18 18 Air Handling Unit
301 General classroom 0 825 18 18 Air Handling Unit
301 General classroom 0 825 18 18 Air Handling Unit
301 General classroom 0 825 18 18 Air Handling Unit
302 SPR 0 135 3 3 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
303 General classroom 0 800 18 18 Air Handling Unit
305 SPR 0 135 3 3 Air Handling Unit
307 Multi purpose classroom 0 1500 34 34 Air Handling Unit
307 Multi purpose classroom 0 1500 34 34 Air Handling Unit
307 Multi purpose classroom 0 1500 34 34 Air Handling Unit
307 Multi purpose classroom 0 1500 34 34 Air Handling Unit
307 Multi purpose classroom 0 1500 34 34 Air Handling Unit
307 Multi purpose classroom 0 1500 34 34 Air Handling Unit
308 Teacher storage  0 90 2 2 Air Handling Unit
309 Resource room 0 645 14 14 Air Handling Unit
309 Resource room 0 645 14 14 Air Handling Unit
309 Resource room 0 645 14 14 Air Handling Unit
309 Resource room 0 645 14 14 Air Handling Unit
315 Electrical room 27.0 1 120 2 2 Air Handling Unit
316 IDF closet 29.0 1 170 3 3 Air Handling Unit
317 Deans Office  32.0 2 140 3 3 Air Handling Unit
318 Mens room 107.0 7 245 5 5 Air Handling Unit
321 Womens Room  110.0 7 250 5 5 Air Handling Unit
322 General classroom 102.0 6 815 18 18 Air Handling Unit
322 General classroom 105.0 7 815 18 18 Air Handling Unit
322 General classroom 65.0 4 815 18 18 Air Handling Unit
322 General classroom 73.0 4 815 18 18 Air Handling Unit
323 Physics classroom 0.0 0 1575 35 0 Air Handling Unit
323 Physics classroom 0.0 0 1575 35 0 Air Handling Unit
323 Physics classroom 0.0 0 1575 35 0 Air Handling Unit
323 Physics classroom 0.0 0 1575 35 0 Air Handling Unit
323 Physics classroom 0.0 0 1575 35 0 Air Handling Unit
323 Physics classroom 0.0 0 1575 35 0 Air Handling Unit
324 Science Prep  54.0 3 200 4 4 Air Handling Unit
324 Science Prep  53.0 3 200 4 4 Air Handling Unit
325 Physics classroom 16.0 1 1505 34 16 Air Handling Unit
325 Physics classroom 116.0 7 1505 34 34 Air Handling Unit
325 Physics classroom 14.0 0 1505 34 14 Air Handling Unit
325 Physics classroom 13.0 0 1505 34 13 Air Handling Unit
325 Physics classroom 13.0 0 1505 34 13 Air Handling Unit
325 Physics classroom 14.0 0 1505 34 14 Air Handling Unit
326 General classroom 86.0 5 825 18 18 Air Handling Unit
326 General classroom 85.0 5 825 18 18 Air Handling Unit
326 General classroom 99.0 6 825 18 18 Air Handling Unit
326 General classroom 47.0 3 825 18 18 Air Handling Unit
327 General classroom 64.0 4 795 18 18 Air Handling Unit
327 General classroom 58.0 3 795 18 18 Air Handling Unit
327 General classroom 62.0 4 795 18 18 Air Handling Unit
327 General classroom 43.0 2 795 18 18 Air Handling Unit
328 N/A 159.0 10 135 3 3 Air Handling Unit
329 General classroom 64.0 4 800 18 18 Air Handling Unit
329 General classroom 59.0 3 800 18 18 Air Handling Unit
329 General classroom 65.0 4 135 3 3 Air Handling Unit
329 General classroom 68.0 4 800 18 18 Air Handling Unit
330 General classroom 70.0 4 795 18 18 Air Handling Unit
330 General classroom 64.0 4 795 18 18 Air Handling Unit
330 General classroom 74.0 4 795 18 18 Air Handling Unit
330 General classroom 81.0 5 795 18 18 Air Handling Unit
331 General classroom 62.0 4 135 3 3 Air Handling Unit
331 General classroom 69.0 4 135 3 3 Air Handling Unit
331 General classroom 73.0 4 135 3 3 Air Handling Unit
331 General classroom 73.0 4 135 3 3 Air Handling Unit
333 Corridor  79.0 5 5535 125 79 Air Handling Unit
333 Corridor  66.0 4 5535 125 66 Air Handling Unit
333 Corridor  81.0 5 5535 125 81 Air Handling Unit
360 Corridor 0 0 0 Air Handling Unit
360 Corridor 0 0 0 Air Handling Unit
360 Corridor 0 0 0 Air Handling Unit
- Corridor  9.0 0 0 0 Air Handling Unit
- Vending machines 0 0 0 Air Handling Unit
- Corridor 0 0 0 Air Handling Unit
- Corridor 0 0 0 Air Handling Unit
- Corridor 28.0 1 0 0 Air Handling Unit
- Corridor 11.0 0 0 0 Air Handling Unit
- Kitchen storage 0 0 0 Air Handling Unit
- Gymnasium 5,058.0 337 0 0 Air Handling Unit
- Storage 0 0 0 Air Handling Unit
- Corridor  0 0 0 Air Handling Unit
- Corridor  0 0 0 Air Handling Unit
- Corridor  0 0 0 Air Handling Unit
- Corridor  0 0 0 Air Handling Unit
- Fitness center 0 0 0 Air Handling Unit
- Fitness center 0 0 0 Air Handling Unit
Sheet Last Modified: 4/22/21        
School:  George W. Sharswood Elementary School House fan Abated
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Building Engineer 0.0 0 1288 29 0 House Fan
- Cafeteria 0 0 Yes 2000 45 45 House Fan
- Kitchen Storage 0 0 121 2 0 House Fan
- Art Room 1817 121 1242 28 28 House Fan
B9A & B9B Classroom 2,017.0 134 1242 28 28 House Fan
- Gym 2,219.0 147 2160 49 49 House Fan
- Main Office 0 0 Yes 552 12 12 House Fan
- Nurse Office 0 0 Yes 550 12 12 House Fan
- Nurse Exam 0 0 Yes 299 6 6 House Fan
- Principal's Office 0 0 Yes 288 6 6 House Fan
101 Classroom 1018 67 550 12 12 House Fan
102 Classroom 932 62 550 12 12 House Fan
103 Classroom 484 32 550 12 12 House Fan
104 Classroom 0 Yes 276 6 6 House Fan
105 Classroom 0 0 Yes 840 19 19 House Fan
106 Classroom 0 0 Yes 728 16 16 House Fan
107 Classroom 0 0 Yes 728 16 16 House Fan
108 Classroom 0 0 Yes 728 16 16 House Fan
109 Classroom 0 0 Yes 713 16 16 House Fan
114 Classroom 0 0 Yes 748 17 17 House Fan
- Auditorium 0 0 2350 53 0 House Fan
216 Music Rm 0 0 Yes 1500 34 34 House Fan
- Teacher's Lounge 0.0 0 440 10 0 House Fan
217 Classroom 0 0 Yes 644 14 14 House Fan
219 Classroom 0 0 Yes 744 16 16 House Fan
223 Classroom 0 0 Yes 713 16 16 House Fan
224 Classroom 0 0 Yes 684 15 15 House Fan
225 Classroom 695.0 46 684 15 15 House Fan
226 Classroom 881.0 58 684 15 15 House Fan
227 Classroom 429.0 28 684 15 15 House Fan
228 Classroom 0.0 0 Yes 682 15 15 House Fan
329 Classroom 281.0 18 696 15 15 House Fan
329A Office 0 0 Yes 120 2 2 House Fan
330 Classroom 811.0 54 696 15 15 House Fan
331 Classroom 276 18 696 15 15 House Fan
332 Classroom 0 0 Yes 576 13 13 House Fan
333 Classroom 0 0 Yes 775 17 17 House Fan
334 Classroom 0 0 Yes 783 17 17 House Fan
335 Classroom 0.0 0 Yes 783 17 17 House Fan
336 Classroom 0.0 0 Yes 783 17 17 House Fan
337 Classroom 0.0 0 Yes 768 17 17 House Fan
338 Classroom 0.0 0 Yes 552 12 12 House Fan
339 Classroom 368.0 24 672 15 15 House Fan
340 Classroom 326.0 21 576 13 13 House Fan
341 Classroom 156.0 10 576 13 10 House Fan
341A Classroom 0.0 0 120 2 0 House Fan
342A Classroom 0.0 0 288 6 0 House Fan
342B Classroom 0.0 0 Yes 432 9 9 House Fan
Sheet Last Modified: 04-26-2021    
School:  Shawmont Elementary-Middle School
Vendor: EMCOR Fluidics Retest 2nd Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 CLASS 0 0 Yes 1033 23 23 Univent
103 CLASS 323 21 687 15 15 Univent
104 CLASS 337 22 568 12 12 Univent
105 Office 0 0 Yes 359 8 8
106 CLASS 336 22 687 15 15 Univent
107 CLASS 327 21 705 16 16 Univent
108 CLASS 308 20 750 17 17 Univent
201 CLASS 312 20 670 15 15 Univent
202 CLASS 323 21 536 12 12 Univent
203 CLASS 372 24 794 18 18 Univent
204 CLASS 273 18 794 18 18 Univent
205 Therapy 340 22 370 8 8 Univent
206 CLASS 325 21 670 15 15 Univent
207 CLASS 222 14 Yes 675 15 15 Univent
208 CLASS 272 18 675 15 15 Univent
209 CLASS 252 16 670 15 15 Univent
300 CLASS 281 18 503 11 11 Univent
301 CLASS 312 20 690 15 15 Univent
302 CLASS 287 19 704 16 16 Univent
303 CLASS 276 18 695 15 15 Univent
304 CLASS 371 24 797 18 18 Univent
305 Office 96 6 Yes 448 10 10 Univent
305-A Classroom 313 20 814 18 18 Univent
306 CLASS 296 19 675 15 15 Univent
307 CLASS 279 18 675 15 15 Univent
308 CLASS 0 0 Yes 695 15 15 Univent
309 CLASS 370 24 690 15 15 Univent
310 CLASS 275 18 Yes 1103 25 25 Univent
311 CLASS 292 19 935 21 19 Univent
312 CLASS 0 0 Yes 1039 23 23 Univent
313 CLASS 0 0 Yes 1036 23 23 Univent
314 CLASS 433 28 1012 23 23 Univent
315 CLASS 388 25 1184 26 25 Univent
- AUDITORIUM 1331 88 3193 72 72 Air Handling Unit
- BAND RM 0 0 Yes 934 21 21 Univent
- COMPUTER LAB 0 0 Yes 1103 25 25 Univent
- GYM 5749 383 Yes 2610 59 59 Air Handling Unit
- LIBRARY 750 50 1804 41 41 Univent
B-1 Strings Room 343 22 641 14 14 Univent
B-2 Music Room 0 0 Yes 518 11 11 Univent
B-3 Band Room 396 26 153 3 3 Univent
B-4 Band Room 281 18 940 21 18 Univent
B-6 Classroom 395 26 803 18 18 Univent
- Cafeteria 1132 75 4090 92 75 Univent
- Staff Lounge 0 0 Yes 364 8 8 Univent
- Nurse 0 Yes 287 6 6
- Principal's Office 0 Yes 210 4 4
- Main Office 0 Yes 379 8 8
Sheet Last Modified: 04-06-2021    
School:  Isaac A. Sheppard Elementary School
Vendor: EMCOR Fluidics Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 661 44 768 17 17 House Fan
101 Classroom 894 59 682 15 15 House Fan
102 Classroom 910 60 682 15 15 House Fan
103 Classroom 578 38 682 15 15 House Fan
200 Classroom 665 44 704 16 16 House Fan
201 Classroom 595 39 704 16 16 House Fan
202 Classroom 1,004 66 682 15 15 House Fan
203 Classroom 951 63 682 15 15 House Fan
204 Classroom 949 63 682 15 15 House Fan
205 Classroom 661 44 682 15 15 House Fan
206 Classroom 844 56 704 16 16 House Fan
300 Classroom 840 56 875 19 19 House Fan
301 Classroom 717 47 875 19 19 House Fan
302 Classroom 963 64 836 19 19 House Fan
303 Classroom 762 50 836 19 19 House Fan
304 Classroom 998 66 704 16 16 House Fan
305 Classroom 847 56 704 16 16 House Fan
306 Classroom 636 42 704 16 16 House Fan
- Auditorium 1,843 122 1176 26 26 House Fan
Main Office Office 0 Yes 255 5 5 Air Purifier
Nurse Office Office 0 Yes 122 2 2 Air Purifier
Principal Office Office 0 Yes 183 4 4 Air Purifier
- Library 1,317 87 851 19 19 House Fan
- Lunch Room/Cafeteria 1,498 99 1311 29 29 House Fan
- Server Room 0 0 0 0 0 Minisplit Air Handling Unit
Sheet Last Modified: 04-07-2021    
School:  Philip Sheridan Elementary School
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Room 0 0 Yes 768 17 17 House Fan
102 Room 1116 74 768 17 17 House Fan
103 Room 921 61 768 17 17 House Fan
104 Room 749 49 720 16 16 House Fan
105 Room 693 46 720 16 16 House Fan
106 Classroom 1006 67 768 17 17 House Fan
107 Classroom 0 0 Yes 768 17 17 House Fan
108 Classroom 0 0 Yes 768 17 17 House Fan
109 Classroom 861 57 768 17 17 House Fan
110 Classroom 376 25 768 17 17 House Fan
Main Office Office 0 Yes 448 10 10 House Fan
110 Principal office  597 39 216 4 4 House Fan
111 Nurse 0 0 Yes 312 7 7 House Fan
201 Classroom 0 0 Yes 768 17 17 House Fan
202 Classroom 877 58 768 17 17 House Fan
203 Classroom 981 65 720 16 16 House Fan
204 Classroom 760 50 720 16 16 House Fan
205 Classroom 737 49 720 16 16 House Fan
206 Classroom 999 66 768 17 17 House Fan
207 Classroom 0 0 Yes 768 17 17 House Fan
208 Classroom 0 0 Yes 768 17 17 House Fan
209 Classroom 1162 77 768 17 17 House Fan
209 1/2 Office 0 Yes 220 5 5 House Fan
210 Classroom 926 61 768 17 17 House Fan
210 1/2 Office 0 220 5 0 House Fan
211 Classroom 0 0 Yes 768 17 17 House Fan
301 Classroom 0 0 768 17 0 House Fan
302 Classroom 1253 83 768 17 17 House Fan
303 Classroom 1038 69 720 16 16 House Fan
304 Classroom 746 49 720 16 16 House Fan
305 Classroom 811 54 720 16 16 House Fan
306 Classroom 1007 67 768 17 17 House Fan
307 Classroom 0 0 768 17 0 House Fan
308 Classroom 0 0 768 17 0 House Fan
309 Classroom 894 59 768 17 17 House Fan
310 Classroom 1334 88 768 17 17 House Fan
311 Classroom 0 0 768 17 0 House Fan
- Basement East Side 0 567 12 0 House Fan
- Basement West Side 0 567 12 0 House Fan
Sheet Last Modified: 04-19-2021    
School:  SLA @ Beeber
   
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 0 1,200 27 0
101 Classroom 0 1,150 26 0
102 Classroom 0 925 21 0
102A Classroom 0 720 16 0
103 Classroom 0 1,636 37 0
104 Classroom 0 875 19 0
105 Classroom  0 909 20 0
106 Classroom  0 Yes 966 21 21
106A Classroom 0 Yes 610 13 13
107 Classroom  0 912 20 0
107A Classroom 0 720 16 0
107B Classroom 0 360 8 0
108 Classroom 0 912 20 0
109 Classroom 0 700 15 0
200 Classroom 0 Yes 638 14 14
201 Office 0 Yes 187 4 4
202 Classroom 0 Yes 1,128 25 25
203 Classroom 0 1,128 25 0
203A Classroom 0 Yes 720 16 16
203B Classroom 0 Yes 360 8 8
204 Classroom 0 Yes 664 15 15
204A Nurse office  0 187 4 0
205 Office 0 Yes 360 8 8
206-208 Office 0 996 22 0
- Main Office 0 Yes 335 7 7
- Principal Office 0 660 15 0
Secretary Office 0 Yes 0 0
Conference Room Conference Room 0 Yes 0 0
Cafeteria Cafeteria 0 7,014 159 0
209-210 Library 0 Yes 1,872 42 42
211 Classroom 0 984 22 0
212 Classroom  0 720 16 0
213-214 Classroom 0 1,518 34 0
214A-B Classroom 0 1,021 23 0
215 Office 0 187 4 0
216 Classroom 0 638 14 0
217 Classroom 0 816 18 0
218 Classroom 0 Yes 744 16 16
219 Classroom 0 Yes 768 17 17
220 Classroom 0 Yes 768 17 17
221 Classroom 0 Yes 768 17 17
222 Classroom 0 Yes 816 18 18
223 Classroom 0 Yes 0 0
224 Classroom 0 Yes 0 0
316 Office 0 187 4 0
317 Classroom 0 665 15 0
318 Classroom  0 836 19 0
319-320 Classroom 0 1,488 33 0
321 Classroom  0 749 17 0
322 Classroom 0 766 17 0
323 Classroom 0 808 18 0
324 Classroom 0 668 15 0
300 Office 0 187 4 0
301-303 Classroom  0 Yes 2,072 47 47
302 Classroom 0 Yes 720 16 16
303A-B Classroom  0 Yes 1,072 24 24
304 Classroom 0 Yes 1,009 22 22
305 Classroom 0 989 22 0
306 Classroom 0 1,001 22 0
307 Classroom 0 1,361 30 0
308 Office 0 200 4 0
309-310 Classroom 0 Yes 2,085 47 47
311 Office 0 Yes 651 14 14
312 Office 0 300 6 0
313-315 Classroom  0 2,227 50 0
314A Classroom 0 1,126 25 0
Sheet Last Modified: 4/23/2021      
School:  Solis-Cohen Elementary School  
Vendor: Chadwick Main Exhaust Main Exhaust Part 2
School:  Solis-Cohen Elementary School- Little School House  
Vendor: Chadwick Chadwick Part 2 Chadwick Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Solis-Cohen Main Building
- Main Office 0 120 2 0 N/A
1 classroom  0 914 20 0 N/A
2 classroom 0 914 20 0 N/A
3 Classroom 0 914 20 0 N/A
4 classroom  0 914 20 0 N/A
5 classroom  0 914 20 0 N/A
6 classroom  0 731 16 0 N/A
7 classroom  0 731 16 0 N/A
8 classroom  0 731 16 0 N/A
9 classroom  0 731 16 0 N/A
9A classroom  0 731 16 0 N/A
10 classroom  0 731 16 0 N/A
11 classroom  0 731 16 0 N/A
12 classroom  0 731 16 0 N/A
13 classroom  0 731 16 0 N/A
14 classroom  0 731 16 0 N/A
26 Classroom  0 914 20 0 N/A
27 Classroom 0 914 20 0 N/A
- Esol Room  0 806 18 0 N/A
- Nurses Office  0 1,116 25 0 N/A
- Gym 0 5,355 121 0 N/A
- Cafeteria 0 2,660 60 0 N/A
- Auditorium 0 5,036 114 0 N/A
- Counselors Office A 0 352 8 0 N/A
- Counselors Office B 0 352 8 0 N/A
Solis-Cohen LSH
100B Lobby 88.0 5 196 4 4 Air Handling Unit
101A Reception Office 30.0 2 256 5 2 Air Handling Unit
101B Clerical Office 56.0 3 336 7 3 Air Handling Unit
101C Asst. Principals Office 32.0 2 598 13 2 Air Handling Unit
101D Nurses Office 32.0 2 256 5 2 Air Handling Unit
102 Classroom  287.0 19 858 19 19 Univent
103 Classroom  276.0 18 858 19 18 Univent
104 Classroom  276.0 18 858 19 18 Univent
105 Classroom  292.0 19 858 19 19 Univent
106 Classroom  280.0 18 858 19 18 Univent
107 Classroom  274.0 18 858 19 18 Univent
108 Classroom  275.0 18 858 19 18 Univent
110 Faculty Dining 45.0 3 640 14 3 Air Handling Unit
121 Classroom  282.0 18 1092 24 18 Univent
122 Classroom  289.0 19 1092 24 19 Univent
123 Classroom  290.0 19 1092 24 19 Univent
124 Classroom  292.0 19 1092 24 19 Univent
125 Classroom  320.0 21 598 13 13 Univent
126 Classroom  287.0 19 1092 24 19 Univent
- Lunch Room  0 Yes 2160 49 49 Air Handling Unit
Sheet Last Modified: 04-30-2021    
School:  South Philly HS
Vendor: Meehan (Auditoriums) EMCOR (School) Chadwick Retest
Vendor: EMCOR (Gym) EMCOR Retest 2 EMCOR Retest 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Pre Engineering Shop Class A 0 0 0 0 Nesbitt Unit Ventilator
- Pre Engineering Shop Class B 281 18 0 0 Nesbitt Unit Ventilator
- Computer Lab 296 19 0 0 Nesbitt Unit Ventilator
004A Engineering Tech.  308 20 1716 39 20 Nesbitt Unit Ventilator
004B Engineering Tech.  0 0 880 20 0 Nesbitt Unit Ventilator
004C Engineering Tech.  313 20 2640 60 20 Nesbitt Unit Ventilator
- Cafeteria 7225 481 11200 254 254 Nesbitt Unit Ventilator
- Cafeteria 5887 392 0 0 Air Handling Unit
- Culinary Kitchen Hood MAU 0 0 0 0 Make-up Air Unit
- Cafeteria Kitchen Hood 4929 328 0 0 Cafeteria Kitchen Hood
005A Room 0 0 2204 50 0 Nesbitt Unit Ventilator
005B Room 0 0 984 22 0 Nesbitt Unit Ventilator
- General Office A 461 30 0 0 Nesbitt Unit Ventilator
- General Office B 394 26 0 0 Nesbitt Unit Ventilator
100 Room 384 25 1100 25 25 Nesbitt Unit Ventilator
101 Room 345 23 690 15 15 Nesbitt Unit Ventilator
104 Room 276 18 620 14 14 Nesbitt Unit Ventilator
105A Room 0 0 2709 61 0 Nesbitt Unit Ventilator
105B Room 207 13 260 5 5 Nesbitt Unit Ventilator
106 Room 400 26 667 15 15 Nesbitt Unit Ventilator
108A Room 0 0 2280 51 0 Nesbitt Unit Ventilator
108B Room 386 25 528 12 12 Nesbitt Unit Ventilator
108C Room 417 27 276 6 6 Nesbitt Unit Ventilator
109 Room 0 0 812 18 0 Nesbitt Unit Ventilator
- Studio 1 308 20 0 0 Nesbitt Unit Ventilator
- Studio 2 419 27 0 0 Nesbitt Unit Ventilator
- Community Closet 352 23 899 20 20 Nesbitt Unit Ventilator
200 Room 371 24 840 19 19
201 Room 363 24 1008 22 22 Nesbitt Unit Ventilator
202 Room 465 31 1247 28 28 Nesbitt Unit Ventilator
203 Room 278 18 579 13 13 Nesbitt Unit Ventilator
204 Room 549 36 690 15 15 Nesbitt Unit Ventilator
205A Room 0 0 86.25 1 0 Nesbitt Unit Ventilator
205B Room 415 27 150 3 3 Nesbitt Unit Ventilator
206 Room 479 31 705 16 16 Nesbitt Unit Ventilator
207 Room 426 28 690 15 15 Nesbitt Unit Ventilator
208 Room 373 24 690 15 15 Nesbitt Unit Ventilator
209 Room 419 27 242 5 5 Nesbitt Unit Ventilator
210 Room 297 19 900 20 19 Nesbitt Unit Ventilator
211 Room 320 21 690 15 15 Nesbitt Unit Ventilator
214A Music Room 350 23 2142 48 23 Nesbitt Unit Ventilator
214B Music Room 323 21 170 3 3 Nesbitt Unit Ventilator
217A Room 382 25 2560 58 25 Nesbitt Unit Ventilator
217B Room 411 27 1312 29 27 Nesbitt Unit Ventilator
219A Room 367 24 899 20 20 Nesbitt Unit Ventilator
220 Room 380 25 667 15 15 Nesbitt Unit Ventilator
221A Room 320 21 1984 45 21 Nesbitt Unit Ventilator
221B Room 279 18 127.5 2 2 Nesbitt Unit Ventilator
222A Room 329 21 1705 38 21 Nesbitt Unit Ventilator
222B Room 286 19 110.5 2 2 Nesbitt Unit Ventilator
223A Room 259 17 1519 34 17 Nesbitt Unit Ventilator
223B Room 217 14 0 0 Nesbitt Unit Ventilator
- Culinary Arts A 0 0 130.5 2 0 Nesbitt Unit Ventilator
- Culinary Arts B 0 0 215 4 0 Nesbitt Unit Ventilator
300A Room 0 0 112 2 0 Nesbitt Unit Ventilator
300B Room 367 24 149 3 3 Nesbitt Unit Ventilator
301 Room 416 27 1207 27 27 Nesbitt Unit Ventilator
302 Room 393 26 1167 26 26 Nesbitt Unit Ventilator
303 Room 338 22 875 19 19 Nesbitt Unit Ventilator
304A Room 413 27 193 4 4 Nesbitt Unit Ventilator
304B Room 427 28 1027 23 23 Nesbitt Unit Ventilator
305A Room 371 24 259 5 5 Nesbitt Unit Ventilator
305B Room 365 24 140 3 3 Nesbitt Unit Ventilator
306A Room 358 23 193 4 4 Nesbitt Unit Ventilator
306B Room 310 20 948 21 20 Nesbitt Unit Ventilator
307A Room 298 19 959 21 19 Nesbitt Unit Ventilator
308 Library A 322 21 6124 139 21 Nesbitt Unit Ventilator
308 Library B 429 28 0 0 Nesbitt Unit Ventilator
308 Library C 381 25 0 0 Nesbitt Unit Ventilator
308 Library Office 361 24 84 1 1 Nesbitt Unit Ventilator
308 Library Archive Room 0 0 360 8 0 Nesbitt Unit Ventilator
311A Room 347 23 973 22 22 Nesbitt Unit Ventilator
311B Room 374 24 1054 23 23 Nesbitt Unit Ventilator
313B Room 0 0 526 11 0 Nesbitt Unit Ventilator
316 Room 686 45 722 16 16 Nesbitt Unit Ventilator
400A Room 314 20 203 4 4 Nesbitt Unit Ventilator
400B Room 208 13 1092 24 13 Nesbitt Unit Ventilator
401A Room 342 22 878 19 19 Nesbitt Unit Ventilator
401B Room 318 21 0 0 Nesbitt Unit Ventilator
402A Room 0 0 894 20 0 Nesbitt Unit Ventilator
402B Room 296 19 0 0 Nesbitt Unit Ventilator
403A Room 0 0 994 22 0 Nesbitt Unit Ventilator
403B Room 307 20 458 10 10
404A Room 0 0 952 21 0 Nesbitt Unit Ventilator
404B Room 297 19 0 0 Nesbitt Unit Ventilator
405A Room 306 20 893 20 20 Nesbitt Unit Ventilator
405B Room 0 0 0 0 Nesbitt Unit Ventilator
406 Room 339 22 708 16 16 Nesbitt Unit Ventilator
407 Room 298 19 715 16 16 Nesbitt Unit Ventilator
408 Room 321 21 708 16 16 Nesbitt Unit Ventilator
409 Room 278 18 675 15 15 Nesbitt Unit Ventilator
410 Room 288 19 694 15 15 Nesbitt Unit Ventilator
411 Room 333 22 707 16 16 Nesbitt Unit Ventilator
412 Room 276 18 701 15 15 Nesbitt Unit Ventilator
412A Room 222 14 471 10 10 Nesbitt Unit Ventilator
413 Room 284 18 711 16 16 Nesbitt Unit Ventilator
414 Room 0 0 580 13 0 Nesbitt Unit Ventilator
415 Room 416 27 691 15 15 Nesbitt Unit Ventilator
416 Room 337 22 660 15 15 Nesbitt Unit Ventilator
417 Room 349 23 694 15 15 Nesbitt Unit Ventilator
418 Room 343 22 698 15 15 Nesbitt Unit Ventilator
418A Room 277 18 341 7 7 Nesbitt Unit Ventilator
419A Room 0 0 1126 25 0 Nesbitt Unit Ventilator
419B Room 0 0 135 3 0 Nesbitt Unit Ventilator
420A Room 322 21 1082 24 21 Nesbitt Unit Ventilator
420B Room 337 22 85 1 1 Nesbitt Unit Ventilator
421 Room 328 21 673 15 15 Nesbitt Unit Ventilator
422 Room 343 22 673 15 15 Nesbitt Unit Ventilator
423 Room 322 21 673 15 15 Nesbitt Unit Ventilator
424 Room 272 18 705 16 16 Nesbitt Unit Ventilator
425 Room 310 20 706 16 16 Nesbitt Unit Ventilator
426 Room 285 19 681 15 15 Nesbitt Unit Ventilator
427 Room 295 19 670 15 15 Nesbitt Unit Ventilator
428 Room 400 26 681 15 15 Nesbitt Unit Ventilator
429 Room 309 20 716 16 16 Nesbitt Unit Ventilator
432 Room 972 64 664 15 15 Nesbitt Unit Ventilator
433 Room 401 26 705 16 16 Nesbitt Unit Ventilator
434 Room 544 36 677 15 15 Nesbitt Unit Ventilator
435 Room 503 33 705 16 16 Nesbitt Unit Ventilator
500 Classroom 0.0 0 937 21 0 Nesbitt Unit Ventilator
500A Classroom 0.0 0 36 0 0 Univent
500B Classroom 158 10 0 0 Univent
501 A Classroom 0 0 845 19 0 Univent
501 B Classroom 351 23 0 0 Univent
502 A Classroom 208 13 969 22 13 Univent
502 B Classroom 266 17 0 0 Univent
503 A Classroom 157 10 1035 23 10 Univent
503 B Classroom 67 4 200 4 4 Univent
504 A Classroom 330 22 982 22 22 Univent
504 B Classroom 160 10 0 0 Univent
505 A Classroom 0 942 21 0 Univent
505 B Classroom 0 0 0 Univent
506 Classroom 320 21 690 15 15 Univent
507 Classroom 212 14 690 15 14 Univent
508 Classroom 0 0 690 15 0 Univent
509 Classroom 192 12 690 15 12 Univent
510 A Classroom 183 12 990 22 12 Univent
510 B Classroom 353 23 102 2 2 Univent
511 Classroom 286 19 690 15 15 Univent
512 Classroom 159 10 690 15 10 Univent
513 Classroom 183 12 690 15 12 Univent
514 Classroom 182 12 690 15 12 Univent
515 Classroom 205 13 690 15 13 Univent
516 Classroom 65 4 713 16 4 Univent
517 Classroom 334 22 552 12 12 Univent
518 Classroom 0 0 713 16 0 Univent
519 Classroom 177 11 616 14 11 Univent
520 Classroom 196 13 616 14 13 Univent
521 Classroom 155 10 616 14 10 Univent
522 Classroom 0 0 616 14 0 Univent
523 Classroom 153 10 705 16 10 Univent
524 Classroom 63 4 690 15 4 Univent
525 Classroom 76 5 690 15 5 Univent
526 Classroom 0 0 690 15 0 Univent
527 Classroom 167 11 690 15 11 Univent
528 Classroom 223 14 690 15 14 Univent
529 Classroom 0 0 690 15 0 Univent
530 Classroom 0 0 690 15 0 Univent
531 Classroom 4 0 690 15 0 Univent
532 Classroom 0 0 705 16 0 Univent
533 Classroom 163 10 705 16 10 Univent
534 Classroom 0 0 705 16 0 Univent
535 Classroom 380 25 705 16 16 Univent
- Auditorium 10,918 727 11,536 262 262 Nesbitt Unit Ventilator
- Gym 24,019 1601 20,384 463 463 Air Handling Unit
Sheet Last Modified: 05-03-2021    
School:  Southwark Elementary School
Vendor: Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B4 Office 0 0 Yes 952 21 21 House Fan
B5 Music Room 1,241 82 1800 40 40 House Fan
B20 Basement 584 38 960 21 21 House Fan
B21 Basement 515 34 1728 39 34 House Fan
102 First Floor 532 35 528 12 12 House Fan
103 First Floor 268 17 660 15 15 House Fan
107 First Floor 739 49 704 16 16 House Fan
112 Classroom 579 38 864 19 19 House Fan
113 First Floor 679 45 704 16 16 House Fan
114 Classroom 716 47 864 19 19 House Fan
115 First Floor 417 27 792 18 18 House Fan
116 Classroom 575 38 864 19 19 House Fan
117 Classroom 0 Yes 414 9 9 House Fan
201 Second Floor 772 51 748 17 17 House Fan
202 Classroom 486 32 864 19 19 House Fan
203 Classroom 297 19 704 16 16 House Fan
204 Library 0 Yes 696 15 15 House Fan
205 Library 0 Yes 696 15 15 House Fan
206 Second Floor 615 41 704 16 16 House Fan
207 Classroom 633 42 864 19 19 House Fan
208 Second Floor 332 22 792 18 18 House Fan
209 Classroom 990 66 864 19 19 House Fan
210 Second Floor 236 15 660 15 15 House Fan
211 Classroom 0 Yes 792 18 18 House Fan
212 Classroom 1,033 68 864 19 19 House Fan
213 Second Floor 675 45 792 18 18 House Fan
214 Classroom 453 30 864 19 19 House Fan
215 Second Floor 532 35 748 17 17 House Fan
216 Classroom 562 37 864 19 19 House Fan
217 Room 0 Yes 272 6 6 House Fan
300 Classroom 0 Yes 480 10 10 House Fan
301 Classroom 0 Yes 800 18 18 House Fan
302 Third Floor 415 27 748 17 17 House Fan
303 Classroom 291 19 864 19 19 House Fan
304 Room 0 Yes 336 7 7 House Fan
305 Third Floor 589 39 704 16 16 House Fan
306 Classroom 276 18 864 19 18 House Fan
307 Classroom 0 Yes 480 10 10 House Fan
308 Classroom 0 Yes 720 16 16 House Fan
309 Third Floor 98 6 Yes 704 16 16 House Fan
310 Classroom 0 Yes 720 16 16 House Fan
311 Classroom 0 Yes 720 16 16 House Fan
312 Classroom 0 Yes 720 16 16 House Fan
313 Third Floor 66 4 Yes 704 16 16 House Fan
314 Classroom 0 Yes 800 18 18 House Fan
315 Classroom 214 14 Yes 864 19 19 House Fan
316 Classroom 0 Yes 768 17 17 House Fan
- Auditorium 1,586 105 1584 36 36 House Fan
- Boy's Bathroom 541 36 792 18 18 House Fan
- Girl's Bathroom 582 38 704 16 16 House Fan
- Music Room 1,241 82 1496 34 34 House Fan
- Nurses 1,184 78 150 3 3 House Fan
- Gym 1,915 127 1560 35 35 House Fan
- Main Office 0 0 Yes 416 9 9 House Fan
- Principal's Office 0 Yes 294 6 6 House Fan
- Cafeteria 0 Yes 1890 42 42 House Fan
Sheet Last Modified: 04-26-2021          
School:  Spring Garden      
         
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 Yes 475 10 10
102 Classroom 0 Yes 494 11 11
103 Classroom 0 Yes 494 11 11
104A storage 0 50 1 0
104B office 0 Yes 80 1 1
104C office 0 Yes 110 2 2
104D office 0 Yes 99 2 2
105A Classroom 0 Yes 483 10 10
105B Classroom 0 Yes 420 9 9
201 Classroom 0 Yes 494 11 11
202 Classroom 0 Yes 494 11 11
203 Classroom 0 Yes 494 11 11
204 Classroom 0 Yes 494 11 11
205 Classroom 0 Yes 494 11 11
206 Classroom 0 Yes 483 10 10
207 Classroom 0 Yes 572 13 13
301 Classroom 0 Yes 741 16 16
303 Classroom 0 Yes 532 12 12
304 Classroom 0 Yes 578 13 13
305 Classroom 0 Yes 720 16 16
306 Classroom 0 Yes 494 11 11
307 Classroom 0 Yes 608 13 13
308 IMC 0 Yes 874 19 19
310 Classroom 0 Yes 380 8 8
- Auditorium 0 Yes 2,265 51 51
- Gym 0 Yes 1,800 40 40
- Lunchroom 0 Yes 1,520 34 34
- Main office 0 Yes 231 5 5
- Nurses Office 0 Yes 189 4 4
- Principal Office 0 Yes 210 4 4
- Staff lounge 0 Yes 168 3 3
- Teachers lounge 0 Yes 195 4 4
Sheet Last Modified: 04-19-2021          
School:  Gilbert Spruance Elementary School    
Vendor: EMCOR    
School:  Gilbert Spruance Little School House    
Vendor: EMCOR Chadwick    
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Spruance Main Building
100 Room 108 7 728 16 7 Unit Ventilator
101 & 101B Room 208 13 1180 26 13 Unit Ventilator
102 Room 112 7 756 17 7 Unit Ventilator
Outside 102 Hallway 0 0 370 8 0 Unit Ventilator
103 Room 188 12 756 17 12 Unit Ventilator
104 Room 101 6 756 17 6 Unit Ventilator
105 Room 83 5 756 17 5 Unit Ventilator
106 Room 106 7 756 17 7 Unit Ventilator
107 Room 119 7 Yes 756 17 17 Unit Ventilator
108 Room 115 7 756 17 7 Unit Ventilator
109 Room 160 10 756 17 10 Unit Ventilator
110 Room 97 6 756 17 6 Unit Ventilator
111 Room 145 9 996 22 9 Unit Ventilator
112 Room 208 13 996 22 13 Unit Ventilator
113 Room 110 7 996 22 7 Unit Ventilator
Outside of 113 Hallway 0 0 3700 84 0 Unit Ventilator
114 Room 240 16 996 22 16 Unit Ventilator
115 Room 150 10 996 22 10 Unit Ventilator
116 Room 334 22 719 16 16 Unit Ventilator
117 Room 240 16 736 16 16 Unit Ventilator
118 Room 145 9 1075 24 9 Unit Ventilator
118A Room 183 12 486 11 11 Unit Ventilator
119 Room 241 16 736 16 16 Unit Ventilator
120 Room 225 15 1062 24 15 Unit Ventilator
122 Room 248 16 851 19 16 Unit Ventilator
124 Room 58 3 Yes 756 17 17 Unit Ventilator
- Auditorium/Gym 0 0 4620 105 0 Unit Ventilator
- Adjustment Room 73 4 435 9 4 Unit Ventilator
200 Room 148 9 756 17 9 Unit Ventilator
201 Room 136 9 756 17 9 Unit Ventilator
202 Room 179 11 690 15 11 Unit Ventilator
Outside of 202 Hallway 0 0 3700 84 0 Unit Ventilator
203 Room 134 8 756 17 8 Unit Ventilator
204 Room 114 7 756 17 7 Unit Ventilator
205 Room 97 6 756 17 6 Unit Ventilator
206 Room 83 5 756 17 5 Unit Ventilator
207 Room 102 6 756 17 6 Unit Ventilator
208 Room 139 9 756 17 9 Unit Ventilator
209 Room 121 8 756 17 8 Unit Ventilator
210 Room 90 6 756 17 6 Unit Ventilator
211 Room 199 13 756 17 13 Unit Ventilator
212 Room 134 8 756 17 8 Unit Ventilator
213A Room 103 6 420 9 6 Unit Ventilator
Outside of Room 213A Hallway 0 0 756 17 0 Unit Ventilator
213B Room 267 17 548 12 12 Unit Ventilator
214 Room 114 7 755 17 7 Unit Ventilator
214A Room 0 0 756 17 0 Unit Ventilator
215 Room 53 3 756 17 3 Unit Ventilator
216 Room 122 8 756 17 8 Unit Ventilator
217 Room 83 5 756 17 5 Unit Ventilator
Outside of Room 217 Hallway 0 0 1850 42 0 Unit Ventilator
218 Room 139 9 718 16 9 Unit Ventilator
220 Room 131 8 724 16 8 Unit Ventilator
- Cafeteria 263 17 Yes 4550 103 103 Unit Ventilator
- Main Office 315 21 456 10 10
- Principal 240 16 241 5 5
- Nurse 374 24 374 8 8
- Main Entrance Lobby 1498 99 1498 34 34 Unit Ventilator
Little School House
1 Room 1072 71 1056 24 24 Air Handling Unit
2 Room 938 62 1056 24 24 Air Handling Unit
3 Room 741 49 1056 24 24 Air Handling Unit
4 Room 1188 79 1056 24 24 Air Handling Unit
5 Room 682 45 1056 24 24 Air Handling Unit
6 Room 713 47 1056 24 24 Air Handling Unit
7 Room 554 36 1056 24 24 Air Handling Unit
8 Room 690 46 1056 24 24 Air Handling Unit
9 Room 1558 103 1056 24 24 Air Handling Unit
10 Room 853 56 1056 24 24 Air Handling Unit
11 Room 1512 100 1056 24 24 Air Handling Unit
12 Room 946 63 1056 24 24 Air Handling Unit
- CLI Office 159 10 120 2 2 Air Handling Unit
- Entrance/Lobby 0 0 210 4 0 Air Handling Unit
- Hallway 0 0 1950 44 0 Air Handling Unit
- Main Office 165 11 315 7 7 Air Handling Unit
- Office 158 10 126 2 2 Air Handling Unit
- Storage 0 0 215 4 0 Air Handling Unit
- Teachers Lounge 331 22 72 1 1 Air Handling Unit
- Therapy Room 0 0 72 1 0 Air Handling Unit
- Girl's RR 0 0 272 6 0 Air Handling Unit
- Boy's RR 0 0 272 6 0 Air Handling Unit
- Men's RR 0 0 77 1 0 Air Handling Unit
- Women's RR 0 0 131 2 0 Air Handling Unit
- Multi-purpose Room 2808 187 1998 45 45 Fan Coil Unit
Sheet Last Modified: 04-29-2021    
School: Edwin M. Stanton Elementary School
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Main Office 0 0 Yes 375 8 8 House Fan
101 Classroom 829.0 55 870 19 19 House Fan
102 Classroom 598.0 39 870 19 19 House Fan
103 Classroom 630.0 42 899 20 20 House Fan
104 Classroom 635.0 42 864 19 19 House Fan
105 Classroom 639.0 42 870 19 19 House Fan
106 Classroom 764.0 50 870 19 19 House Fan
107 Classroom 836.0 55 1450 32 32 House Fan
201 Classroom 697.0 46 870 19 19 House Fan
202 Classroom 500.0 33 870 19 19 House Fan
203 Classroom 526.0 35 870 19 19 House Fan
204 Classroom 527.0 35 870 19 19 House Fan
205 Library  907.0 60 1363 30 30 House Fan
206 Classroom 531.0 35 870 19 19 House Fan
207 Classroom 706.0 47 870 19 19 House Fan
208 Classroom 806.0 53 870 19 19 House Fan
301 Gym 61.0 4 870 19 4 House Fan
302 Gym 432.0 28 870 19 19 House Fan
302 Classroom 560.0 37 870 19 19 House Fan
304 Classroom 715.0 47 870 19 19 House Fan
305 Classroom 833.0 55 1316 29 29 House Fan
306 Classroom 525.0 35 870 19 19 House Fan
307 Classroom 988.0 65 870 19 19 House Fan
308 Classroom 230.0 15 870 19 15 House Fan
Counselor Office 0 Yes 240 5 5 House Fan
- Cafeteria 0.0 0 Yes 2400 54 54 House Fan
- Nurse Office 0.0 0 Yes 200 4 4 House Fan
- Principal Office 0 0 Yes 256 5 5 House Fan
Sheet Last Modified: 04-15-2021    
School:  Allen M. Stearne Elementary School
Vendor: EMCOR EMCOR Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 classroom 529 35 730 16 16 Perimeter Heater
100A First Floor 30 2 222 5 2 Perimeter Heater
101 classroom 316 21 1197 27 21 Perimeter Heater
102 classroom 452 30 753 17 17 Perimeter Heater
102A First Floor 284 18 401 9 9 Perimeter Heater
103 classroom 569 37 1175 26 26 Perimeter Heater
104 classroom 224 14 716 16 14 Perimeter Heater
105 Classroom 0 319 7 0 Perimeter Heater
106 classroom 189 12 730 16 12 Perimeter Heater
108A First Floor 276 18 810 18 18 Perimeter Heater
108B First Floor 59 3 129 2 2 Perimeter Heater
108C First Floor 109 7 146 3 3 Perimeter Heater
108D First Floor 54 3 86 1 1 Perimeter Heater
108E First Floor 87 5 75 1 1 Perimeter Heater
108F First Floor 62 4 94 2 2 Perimeter Heater
200 classroom 274 18 740 16 16 Perimeter Heater
201 classroom 322 21 717 16 16 Perimeter Heater
202 classroom 313 20 705 16 16 Perimeter Heater
203 classroom 337 22 739 16 16 Perimeter Heater
204 classroom 329 21 737 16 16 Perimeter Heater
205 classroom 325 21 756 17 17 Perimeter Heater
206 classroom 334 22 745 16 16 Perimeter Heater
207 classroom 0 0 Yes 386 8 8 Perimeter Heater
208 classroom 328 21 882 20 20 Perimeter Heater
209 classroom 109 7 Yes 639 14 14 Perimeter Heater
209A classroom 80 5 152 3 3 Perimeter Heater
209B classroom 0 0 125 2 0 Perimeter Heater
210 classroom 549 36 1185 26 26 Perimeter Heater
211 classroom 845 56 728 16 16 Perimeter Heater
212 classroom 116 7 434 9 7 Perimeter Heater
213 classroom 131 8 224 5 5 Perimeter Heater
300 classroom 532 35 763 17 17 Perimeter Heater
300A classroom 395 26 224 5 5 Perimeter Heater
301 classroom 350 23 755 17 17 Perimeter Heater
302 classroom 289 19 746 16 16 Perimeter Heater
303 classroom 447 29 722 16 16 Perimeter Heater
304 classroom 434 28 745 16 16 Perimeter Heater
305 classroom 360 24 747 16 16 Perimeter Heater
306 classroom 534 35 715 16 16 Perimeter Heater
307 Classroom 0 790 17 0 Perimeter Heater
308 classroom 278 18 717 16 16 Perimeter Heater
- Auditorium 0 0 2919 66 0 AHU
- Cafeteria/Gym 0 0 Yes 3719 84 84 AHU
- Dean's Office (Temple) 72 4 106 2 2 Perimter Heater
- Health Office 274 18 294 6 6 Perimter Heater
- Office 300 20 984 22 20 Perimter Heater
- Principal 187 12 321 7 7 Perimter Heater
Sheet Last Modified: 04-27-2021    
School:  Edward Steel Elementary School
Vendor: EMCORE Fluidics Exhaust Report
  2-15-2021 Retest 2-22-21 Retest 4-12-21 Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Storeroom 0 0 Yes 323 7 7 Air Coil Unit
101A - C Office 0 0 Yes 356 8 8 Air Coil Unit
102 Main Office- open office 0 0 Yes 512 11 11 Air Coil Unit
102 Main Office- admin ofc 0 0 121 2 0 Air Coil Unit
102 Main Office- asst principals ofc 0 0 Yes 121 2 2 Air Coil Unit
102 Main Office- principals ofc 0 0 Yes 143 3 3 Air Coil Unit
102 Main Office- conf rm 0 0 Yes 204 4 4 Air Coil Unit
103 Lounge 0 0 Yes 676 15 15 Air Coil Unit
104 counselors ofc 0 0 Yes 385 8 8 Air Coil Unit
105 Classroom 46 3 Yes 660 15 15 Air Handling Unit
106 data room 0 0 Yes 1364 31 31 Air Coil Unit
107 Classroom 363 24 Yes 1364 31 31 Air Handling Unit
109 Classroom 257 17 Yes 1364 31 31 Air Handling Unit
110 nurse str 0 0 Yes 886 20 20 Air Coil Unit
- Nurse Waiting Area 0 Yes 208 4 4  
111 Classroom 450 30 Yes 1364 31 31 Air Handling Unit
113 Classroom 338 22 Yes 1364 31 31 Air Handling Unit
- AUDITORIUM 475 31 Yes 2482 56 56 Air Coil Unit
- CAFETERIA 0 0 Yes 3478 79 79 Air Coil Unit
- Cafeteria Office   0 Yes 300 6 6  
- IMC 2021 134 3283 74 74 Air Coil Unit
201 Classroom 163 10 Yes 1330 30 30 Air Handling Unit
202 Classroom 250 16 Yes 1330 30 30 Air Handling Unit
203 Classroom 188 12 Yes 1147 26 26 Air Handling Unit
204 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
205 Classroom 194 12 Yes 1147 26 26 Air Handling Unit
206 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
207 Classroom 144 9 Yes 1147 26 26 Air Handling Unit
208 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
209 Classroom 186 12 Yes 1147 26 26 Air Handling Unit
210 Classroom 196 13 Yes 1147 26 26 Air Coil Unit
211 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
212 Classroom 287 19 Yes 1130 25 25 Air Coil Unit
213 Classroom 0 0 Yes 870 19 19 Air Coil Unit
214 Classroom 0 Yes 870 19 19 Air Coil Unit
215 Office  0 0 Yes 345 7 7 Air Coil Unit
216 Classroom 0 0 Yes 588 13 13 Air Coil Unit
219 Classroom 0 Yes 462 10 10 Air Coil Unit
220 team office 0 0 Yes 462 10 10 Air Coil Unit
301 Classroom 0 0 Yes 1330 30 30 Air Coil Unit
302 Classroom 0 0 Yes 1330 30 30 Air Coil Unit
303 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
304 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
305 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
306 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
307 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
308 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
309 Classroom 0 0 Yes 1155 26 26 Air Coil Unit
310 Classroom 0 0 Yes 1147 26 26 Air Coil Unit
311 Classroom 0 0 Yes 1330 30 30 Air Coil Unit
312 Classroom 482 32 1330 30 30 Air Coil Unit
313 Classroom 0 0 Yes 870 19 19 Air Coil Unit
314 Classroom 0 0 Yes 870 19 19 Air Coil Unit
315 Staff Lounge 0 Yes 330 7 7 Air Coil Unit
319 Classroom 0 Yes 462 10 10 Air Coil Unit
320 team office 0 Yes 462 10 10 Air Coil Unit
- imc office 105 7 Yes 3283 74 74 Air Coil Unit
- imc storage 70 4 255 5 4 Air Coil Unit
- material production 210 14 Yes 625 14 14 Air Coil Unit
- open library 1180 78 3360 76 76 Air Coil Unit
- Gym Office 0 Yes 168 3 3
- Gym 7824 521 4860 110 110
Sheet Last Modified: 03-18-2021      
School:  Parkway Center City Middle College @ Stoddart Fleisher
       
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- kitchen 0 837 19 0
- lunchroom 0 3,822 86 0
- art room 0 782 17 0
506 art room 0 851 19 0
505B office 0 528 12 0
505 classroom 0 1,078 24 0
504 classroom 0 1,144 26 0
503A office 0 96 2 0
503B shop 0 252 5 0
- teacher's lounge 0 621 14 0
502 classroom 0 552 12 0
501 classroom 0 640 14 0
411 classroom 0 770 17 0
410 classroom 0 805 18 0
409 classroom 0 713 16 0
408 classroom 0 716 16 0
407 classroom 0 748 17 0
406 classroom 0 704 16 0
405B counselor 0 135 3 0
405A  VP office 0 506 11 0
404 classroom 0 644 14 0
403 classroom 0 621 14 0
402 classroom 0 598 13 0
401 classroom 0 640 14 0
310 classroom 0 704 16 0
309 weight room 0 920 20 0
308 classroom 0 897 20 0
307 classroom 0 858 19 0
306 storage room 0 682 15 0
305 classroom 0 660 15 0
304 classroom 0 726 16 0
303A office 0 161 3 0
303 classroom 0 713 16 0
302 classroom 0 682 15 0
301A computer office 0 184 4 0
301 classroom 0 640 14 0
-  Boys locker room 0 360 8 0
- Gym 0 3,300 75 0
- Girls Locker room 0 324 7 0
- Nurses office 0 240 5 0
- Exam Room 0 150 3 0
208 classroom 0 598 13 0
207 classroom 0 598 13 0
206 classroom 0 644 14 0
205 Library 0 1,081 24 0
- Main Office Area 0 285 6 0
- Main Office Waiting area 0 150 3 0
- Principal's office  0 280 6 0
204 classroom 0 616 14 0
203 classroom 0 621 14 0
202 classroom 0 598 13 0
201 counselor's  Sitting area 0 200 4 0
201A counselor's A 0 96 2 0
201B counselor's B 0 132 3 0
201C counselor's C 0 121 2 0
201D counsel's D 0 121 2 0
105 conferance room 0 598 13 0
104A classroom 0 247 5 0
104B office 0 117 2 0
104C office 0 112 2 0
104D office 0 90 2 0
104E office 0 99 2 0
- Regional office 0 No Access 0 0
- Data room 0 484 11 0
102A classroom 0 693 15 0
102C office 0 195 4 0
102E classroom 0 513 11 0
102D office 0 635 14 0
102B office 0 195 4 0
101 counselor 0 306 6 0
- Auditorium 0 4,539 103 0
Sheet Last Modified: 03-18-2021    
School:  Strawberry Mansion High School
School:  Leslie P. Hill Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Strawberry Mansion
101 Music Rm. 0 0 1288 29 0 Heating Unit Ventilator
102 Classroom 542 36 768 17 17 Univent
103 Music Rm. 78 5 1288 29 5 Heating Unit Ventilator
104 Classroom 427 28 888 20 20 Univent
108 Classroom 0 0 888 20 0 Univent
109A & 109B Classroom 620 41 1288 29 29 Heating Unit Ventilator
110 Classroom 695 46 888 20 20 Univent
111 Classroom 444 29 288 6 6 Univent
112 Classroom 0 0 888 20 0 Univent
200 Classroom 0 0 1056 24 0 Univent
201 Classroom 416 27 805 18 18 Univent
202 Classroom 357 23 1152 26 23 Univent
203 Classroom 607 40 782 17 17 Univent
206 Classroom 0 0 805 18 0 Univent
207 Classroom 0 0 851 19 0 Univent
208 Classroom 512 34 1104 25 25 Univent
209 Computer Lab 859 57 1012 23 23 Air Handling Unit
212 Classroom 382 25 851 19 19 Univent
214 Classroom 301 20 851 19 19 Univent
216 Classroom 350 23 851 19 19 Univent
217 Classroom 516 34 1012 23 23 Univent
219 Classroom 0 0 960 21 0 Univent
220 Classroom 0 0 851 19 0 Univent
222 Classroom 0 0 851 19 0 Univent
224 Classroom 0 0 782 17 0 Univent
300 Classroom 464 30 782 17 17 Univent
301 Classroom 0 0 805 18 0 Univent
302 Classroom 401 26 782 17 17 Univent
303 Classroom 0 0 805 18 0 Univent
304 Classroom 0 0 851 19 0 Univent
306 Classroom 0 0 851 19 0 Univent
307 Classroom 442 29 851 19 19 Univent
308 Classroom 0 0 851 19 0 Univent
309 Classroom 335 22 851 19 19 Univent
310 Classroom 430 28 851 19 19 Univent
311 Classroom 0 0 851 19 0 Univent
312 Classroom 0 0 851 19 0 Univent
314 Classroom 446 29 851 19 19 Univent
315 Classroom 0 0 851 19 0 Univent
316 Classroom 0 0 851 19 0 Univent
317 Classroom 0 0 851 19 0 Univent
319 Classroom 0 0 851 19 0 Univent
320 Classroom 0 0 851 19 0 Univent
322 Classroom 459 30 851 19 19 Univent
323 Classroom 601 40 851 19 19 Univent
324 Classroom 466 31 782 17 17 Univent
325 Classroom 0 0 851 19 0 Univent
 400A&B Classroom 0 0 598 13 0 Univent
401A Classroom 488 32 345 7 7 Univent
402 Classroom 465 31 1288 29 29 Univent
403 Classroom 250 16 299 6 6 Univent
404 Classroom 434 28 1196 27 27 Univent
405 Classroom 503 33 987 22 22 Univent
406 Classroom 239 15 666 15 15 Univent
407 Classroom 236 15 375 8 8 Univent
408 Classroom 456 30 851 19 19 Univent
409 Classroom 0 0 1288 29 0 Univent
410 Classroom 0 0 851 19 0 Univent
412 Classroom 431 28 851 19 19 Univent
413 Classroom 0 0 851 19 0 Univent
414 Classroom 467 31 851 19 19 Univent
415 Classroom 0 0 851 19 0 Univent
417 Classroom 0 0 851 19 0 Univent
418 Classroom 0 0 851 19 0 Univent
420 Classroom 0 0 851 19 0 Univent
421 Classroom 0 0 851 19 0 Univent
422 Classroom 0 0 782 17 0 Univent
423 Classroom 0 0 851 19 0 Univent
500 Classroom 280 18 800 18 18 Univent
 500B Classroom 264 17 375 8 8 Univent
502 Classroom 442 29 300 6 6 Univent
505 Classroom 0 0 1300 29 0 Univent
506 Classroom 0 0 925 21 0 Univent
507 Classroom 0 0 425 9 0 Univent
508 Classroom 487 32 1250 28 28 Univent
509 Classroom 0 0 1100 25 0 Univent
513 Classroom 489 32 325 7 7 Univent
516 Classroom 0 0 1327 30 0 Univent
517 Classroom 0 0 1162 26 0 Univent
518 Classroom 0 0 1375 31 0 Univent
519 Classroom 292 19 570 12 12 Univent
520 Classroom 683 45 1447 32 32 Univent
522 Classroom 0 0 1471 33 0 Univent
- Library 1,247 83 1863 42 42 Air Handling Unit
- Culinary Arts area 1,077 71 6536 148 71 Air Handling Unit
- Book Strg. Rm. Security office 0 0 1733 39 0 Air Handling Unit
- DOS office 0 0 0 0 Univent
- EST office 513 34 0 0 Univent
Serves unknown 0 0 0 0 Heating Unit Ventilator
- Auditorium 7,054 470 9936 225 225 Heating Unit Ventilator
- Cafeteria 1,912 127 10725 243 127 Heating Unit Ventilator
- Aud. Stage 2,999 199 2668 60 60 Heating Unit Ventilator
- Unknown location and what it serves 0 0 0 Heating Unit Ventilator
- Maintenance office, Lobby 317 21 0 0 Heating Unit Ventilator
- Girls Locker Room 1,759 117 0 0 Heating Unit Ventilator
- Girls Gym 885 59 5808 132 59 Heating Unit Ventilator
- Boys Locker Room 126 8 0 0 Heating Unit Ventilator
- Boys Gym 6,081 405 5808 132 132 Heating Unit Ventilator
- Unknown location and what it serves 0 0 0 Heating Unit Ventilator
- Music Prac. Rms. & Office 607 40 0 0 Heating Unit Ventilator
- Nurses area, Admin areas 796 53 0 0 Heating Unit Ventilator
- Unknown 0 0 0 Heating Unit Ventilator
- Unknown 0 0 0 Heating Unit Ventilator
LP Hill Building
1 Office 0 0 870.365 19 0 Vertical ACU
4 Office 0 0 409.462 9 0 Vertical Air Coil Unit and Univent
5 Classroom 0 0 0 0 Vertical Air Coil Unit and Univent
7 Classroom 0 0 0 0 Vertical Air Coil Unit and Univent
7 Conference Rm. 0 0 1111.66 25 0 Vertical Air Coil Unit and Univent
10 Storage Room 0 0 454.88 10 0 Vertical Air Coil Unit
12 Truency Court 0 0 988.792 22 0 Vertical Air Coil Unit
14 Truency Court 0 0 715.596 16 0 Univent
15 General Room 0 0 734.479 16 0 Vertical Air Coil Unit and Univent
100 Classroom 0 0 982.127 22 0 Vertical Air Coil Unit and Univent
101 Classroom 0 0 1041.52 23 0 Vertical Air Coil Unit and Univent
102 Classroom 0 0 973.903 22 0 Univent
103 Classroom 0 0 1054.8 23 0 Vertical Air Coil Unit and Univent
104 Classroom 0 0 1022.271 23 0 Univent
105 Classroom 0 0 875 19 0 Univent
106 Classroom 160 10 933.66 21 10 Univent
107 Classroom 15 1 1492.29 33 1 Univent
108 Classroom 224 14 1492.29 33 14 Univent
200 Office 0 0 917.724 20 0 Univent
202 Office 294 19 1,034 23 19 Univent
203 Office 0 0 833.94 18 0 Univent
204 Office 50 3 1,034 23 3 Univent
205 Office 0 0 1033.59 23 0 Univent
206 Office 0 0 951.5 21 0 Univent
207 Office 31 2 1033.59 23 2 Univent
209 Office 119 7 1031.06 23 7 Univent
210 Office 0 0 1009.73 22 0 Univent
212 Office 169 11 882.972 20 11 Univent
213 Office 0 0 940.62 21 0 Univent
214 Waiting area 0 0 912.502 20 0 Univent
215 Waiting area 0 0 1025.81 23 0 Univent
300 Classroom 216 14 922.898 20 14 Univent
301 Classroom 0 0 921.33 20 0 Univent
302 Classroom 0 0 1010.47 22 0 Univent
303 Classroom 0 0 912.38 20 0 Univent
304 Classroom 0 0 986.631 22 0 Univent
305 Classroom 25 1 618.57 14 1 Univent
306 Classroom 0 0 932.119 21 0 Univent
307 Classroom 0 0 0 0 Univent
309 Classroom 0 0 0 0 Univent
310 Classroom 280 18 1009.5 22 18 Univent
312 Classroom 0 0 992.166 22 0 Univent
313 Classroom 0 0 978.97 22 0 Univent
314 Classroom 0 0 911.255 20 0 Univent
315 Classroom 0 863.91 19 0 Univent
400 Classroom 0 0 0 0 Univent
401 Classroom 0 0 0 0 Univent
402 Classroom 0 0 0 0 Univent
403 Classroom 194 12 0 0 Univent
404 Classroom 0 0 0 0 Univent
405 Classroom 92 6 0 0 Univent
406 Classroom 0 0 0 0 Univent
407 Classroom 131 8 0 0 Univent
409 Classroom 0 0 0 0 Univent
410 Classroom 0 0 0 0 Univent
411/413 Classroom 0 0 0 0 Univent
412 Classroom 0 0 0 0 Univent
414 Classroom 0 0 0 0 Univent
415 Classroom 0 0 0 0 Univent
- Faculty Rm. 0 0 0 0 Univent
- Main office 0 0 1107.41 25 0 Univent
- Princ. Office 682 45 355.756 8 8 Univent
Sheet Last Modified: 04-27-2021    
School:  James J. Sullivan Elementary School
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B7 Classroom  0 Yes 610 13 13 House Fan
B2 Classroom  0 Yes 736 16 16 House Fan
- Library 0 Yes 968 22 22 House Fan
B9 Classroom  0 506 11 0 House Fan
- Kitchen 0 704 16 0 House Fan
101 Classroom  0 Yes 920 20 20 House Fan
102 Classroom  0 Yes 690 15 15 House Fan
103 Classroom  0 736 16 0 House Fan
104 Classroom  0 Yes 690 15 15 House Fan
105 Classroom  0 Yes 690 15 15 House Fan
106 Classroom  0 Yes 690 15 15 House Fan
107 Classroom 0 Yes 275 6 6
107a office 0 Yes 115 2 2 House Fan
107b office 0 Yes 115 2 2 House Fan
107c office 0 Yes 115 2 2 House Fan
108 Classroom  0 Yes 736 16 16 House Fan
109 Classroom  0 690 15 0 House Fan
110 Classroom  0 Yes 736 16 16 House Fan
- Main Office 0 Yes 336 7 7 House Fan
- Principal's Office 0 Yes 210 4 4 House Fan
201 Classroom  0 Yes 736 16 16 House Fan
202 Classroom  0 Yes 690 15 15 House Fan
203 Classroom  0 Yes 736 16 16 House Fan
204 Classroom  0 Yes 690 15 15 House Fan
205 Classroom  0 Yes 690 15 15 House Fan
206 Classroom  0 Yes 690 15 15 House Fan
207 Classroom  0 Yes 690 15 15 House Fan
208 Classroom  0 Yes 736 16 16 House Fan
209 Classroom  0 Yes 690 15 15 House Fan
210 Classroom  0 Yes 736 16 16 House Fan
211 Classroom  0 Yes 192 4 4 House Fan
214 Classroom  0 Yes 384 8 8 House Fan
215 Office 0 Yes 195 4 4 House Fan
- Nurses Office 0 Yes 264 6 6 House Fan
300 Classroom  0 Yes 720 16 16 House Fan
301 Classroom  0 Yes 736 16 16 House Fan
302 Classroom  0 Yes 690 15 15 House Fan
303 Classroom  0 Yes 736 16 16 House Fan
304 Classroom  0 Yes 690 15 15 House Fan
305 Classroom  0 Yes 690 15 15 House Fan
306 Classroom  0 Yes 690 15 15 House Fan
307 Classroom  0 Yes 690 15 15 House Fan
307B Classroom 0 Yes 119 2 2
308 Classroom  0 Yes 736 16 16 House Fan
309 Computer Room 0 690 15 0 House Fan
310 Classroom  0 Yes 736 16 16 House Fan
311 Office 0 Yes 192 4 4 House Fan
- Cafe/Gym 0 Yes 3,432 78 78 Hydroxyl Unit
Sheet Last Modified: 4-27-21    
School:  Parkway West High School @ Sulzberger
Vendor:  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 - 0 483 10 0
101 - 0 575 13 0
102 - 0 851 19 0
106 - 0 920 20 0
107 - 0 Yes 943 21 21
108 - 0 Yes 874 19 19
109 - 0 920 20 0
201 - 0 682 15 0
202 - 0 660 15 0
203 - 0 Yes 528 12 12
203A - 0 Yes 660 15 15
204 Nurses Office 0 Yes 460 10 10
205 - 0 Yes 660 15 15
206 Counselors Office 0 Yes 690 15 15
Principal Office 0 Yes 322 7 7
208 Main Office 0 Yes 825 18 18
210 - 0 836 19 0
211 - 0 Yes 864 19 19
212 - 0 Yes 660 15 15
212A - 0 Yes 660 15 15
213 - 0 Yes 682 15 15
215 - 0 816 18 0
216 - 0 Yes 748 17 17
217 - 0 Yes 736 16 16
218 - 0 Yes 704 16 16
219 - 0 Yes 704 16 16
220 - 0 Yes 704 16 16
221 - 0 805 18 0
222 - 0 690 15 0
301-302 - 0 Yes 1,012 23 23
303 - 0 Yes 1,176 26 26
304 - 0 Yes 966 21 21
305 - 0 858 19 0
306 - 0 Yes 770 17 17
307 - 0 770 17 0
308 - 0 Yes 900 20 20
309 - 0 880 20 0
310 - 0 880 20 0
311 - 0 924 21 0
312 - 0 Yes 682 15 15
313 - 0 Yes 660 15 15
314 - 0 Yes 682 15 15
315 - 0 330 7 0
316 - 0 Yes 660 15 15
317 - 0 748 17 0
318 - 0 Yes 736 16 16
319 - 0 Yes 616 14 14
320 - 0 Yes 616 14 14
321 - 0 704 16 0
322 - 0 Yes 748 17 17
323 - 0 638 14 0
- 3rd Flr. Computer Lab 0 1,035 23 0
- Auditorium 0 3,390 77 0
- North Caf. 0 2,680 60 0
- South Caf. 0 Yes 2,720 61 61
- South Gym 0 4,186 95 0
Sheet Last Modified: 4-30-21    
School:  Swenson Arts & Technology High School
Vendor: Goldner
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
49 Classroom 0 Yes 308 7 7
50 Classroom 0 308 7 0
51 Classroom 0 Yes 308 7 7
53 Classroom 0 Yes 616 14 14
4 Classroom 0 Yes 532 12 12
5 Classroom 0 Yes 528 12 12
6 Classroom 0 132 3 0
100 Classroom 242 16 1278 29 16 Rooftop Unit
101 Classroom 143 9 228 5 5 Rooftop Unit
102 Classroom 76 5 149 3 3 Rooftop Unit
103 Classroom 82 5 151 3 3 Rooftop Unit
104 Classroom 116 7 144 3 3 Rooftop Unit
105 Classroom 40 2 110 2 2 Rooftop Unit
105 Classroom 55 3 200 4 3 Rooftop Unit
106 Classroom 75 5 178 4 4 Rooftop Unit
109 Classroom 93 6 306 6 6 Rooftop Unit
110 Classroom 70 4 159 3 3 Rooftop Unit
111 Classroom 42 2 146 3 2 Rooftop Unit
112 Classroom 24 1 100 2 1 Rooftop Unit
113 Classroom 21 1 Yes 105 2 2 Rooftop Unit
114 Classroom 135 9 602 13 9 Rooftop Unit
128 Classroom 612 40 1275 28 28 Rooftop Unit
129 Classroom 39 2 144 3 2 Rooftop Unit
130 Classroom 536 35 960 21 21 Rooftop Unit
138 Classroom 305 20 Yes 1125 25 25 Rooftop Unit
140 Classroom 675 45 1085 24 24 Rooftop Unit
144 Classroom 1497 99 1734 39 39 Rooftop Unit
146 Classroom 650 43 700 15 15 Rooftop Unit
150 Classroom 618 41 308 7 7 Rooftop Unit
164 Classroom 305 20 899 20 20 Rooftop Unit
170 Classroom 188 12 351 7 7 Rooftop Unit
171 Classroom 526 35 1461 33 33 Rooftop Unit
172 Classroom 0 Yes 126 2 2
176 Classroom 0 Yes 452 10 10
180 Classroom 93 6 209 4 4 Rooftop Unit
182 Classroom 251 16 Yes 1059 24 24 Rooftop Unit
184 Classroom 228 15 Yes 1628 37 37 Rooftop Unit
195 Classroom 439 29 1566 35 29 Rooftop Unit
196 Classroom 68 4 272 6 4 Rooftop Unit
200 Classroom 344 22 1624 36 22 Rooftop Unit
201 & 201A Classroom 211 14 Yes 660 15 15 Rooftop Unit
202 Classroom 181 12 Yes 836 19 19 Rooftop Unit
203 Classroom 190 12 760 17 12 Rooftop Unit
204 Classroom 0 Yes 1584 36 36 Rooftop Unit
205 Classroom 328 21 Yes 1925 43 43 Rooftop Unit
207 Classroom 994 66 2300 52 52 Rooftop Unit
210 Classroom 1278 85 1020 23 23 Rooftop Unit
213 Classroom 0 Yes 748 17 17 Rooftop Unit
214 Classroom 0 Yes 126 2 2
216 Classroom 410 27 1597 36 27 Rooftop Unit
216 Classroom 1578 105 1597 36 36 Rooftop Unit
227 Classroom 225 15 Yes 840 19 19 Rooftop Unit
228 Classroom 135 9 Yes 930 21 21 Rooftop Unit
229 Classroom 174 11 Yes 1008 22 22 Rooftop Unit
230/231 Classroom 87 5 Yes 522 11 11 Rooftop Unit
231 Classroom 43 2 100 2 2 Rooftop Unit
232 Classroom 0 Yes 968 22 22
232B Classroom 46 3 Yes 348 7 7 Rooftop Unit
234 Classroom 192 12 Yes 900 20 20 Rooftop Unit
236 Classroom 293 19 1240 28 19 Rooftop Unit
237 Classroom 186 12 Yes 969 22 22 Rooftop Unit
238 Classroom 442 29 888 20 20 Rooftop Unit
245 Classroom 281 18 675 15 15 Rooftop Unit
247 Classroom 140 9 448 10 9 Rooftop Unit
249 & 249 A-B Classroom 520 34 414 9 9 Rooftop Unit
250 Classroom 303 20 900 20 20 Rooftop Unit
253 Classroom 655 43 186 4 4 Rooftop Unit
257 Classroom 341 22 756 17 17 Rooftop Unit
258 Classroom 357 23 1050 23 23 Rooftop Unit
259 Classroom 242 16 1225 27 16 Rooftop Unit
260 and 260 A-C Classroom 579 38 561 12 12 Rooftop Unit
261 Classroom 375 25 1050 23 23 Rooftop Unit
262 Classroom 678 45 2373 53 45 Rooftop Unit
263 Classroom 0 Yes 2373 53 53
264 Classroom 333 22 870 19 19 Rooftop Unit
265 Classroom 307 20 928 21 20 Rooftop Unit
1750b Room 108 7 374 8 7 Rooftop Unit
1775A - 0 Yes 528 12 12
- Baking Room 525 34 1981 45 34 Rooftop Unit
- Dark Room 59 3 104 2 2 Rooftop Unit
- Corridor 109 7 355 8 7 Rooftop Unit
- Hallway 640 42 730 16 16 Rooftop Unit
- Corridor 54 3 162 3 3 Rooftop Unit
- Corridor 53 3 152 3 3 Rooftop Unit
- Corridor 167 11 286 6 6 Rooftop Unit
- Corridor 70 4 344 7 4 Rooftop Unit
- Hallway Diffuser s31 25 1 258 5 1 Rooftop Unit
- Kitchen 1391 92 205 4 4 Rooftop Unit
- Nurse's Office/Medical 165 11 591 13 11 Rooftop Unit
- Office 35 2 287 6 2 Rooftop Unit
- Office 77 5 1435 32 5 Rooftop Unit
- Office 54 3 157 3 3 Rooftop Unit
- Office 598 39 94 2 2 Rooftop Unit
- Classroom 313 20 1769 40 20 Rooftop Unit
S1 Classroom 309 20 336 7 7 Rooftop Unit
S2 Classroom 318 21 336 7 7 Rooftop Unit
S3 Classroom 52 3 336 7 3 Rooftop Unit
S3 Office 232 15 306 6 6 Rooftop Unit
S4 Office 14 0 20 0 0 Rooftop Unit
S5 Storage 33 2 270 6 2 Rooftop Unit
S6 School Police 207 13 515 11 11 Rooftop Unit
S8 Classroom 104 6 560 12 6 Rooftop Unit
- School Store 386 25 455 10 10 Rooftop Unit
- Second Floor Hallway 95 6 1846 41 6 Rooftop Unit
- Storage 33 2 590 13 2 Rooftop Unit
- Storage 107 7 35 0 0 Rooftop Unit
- Storage 73 4 134 3 3 Rooftop Unit
- Storage 44 2 94 2 2 Rooftop Unit
- Storage 45 3 91 2 2 Rooftop Unit
- Storage/Closet 237 15 50 1 1 Rooftop Unit
Sheet Last Modified: 04-23-2021    
School:  John H. Taggart Elementary-Middle School
Vendor:  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 0 638 14 0
102-A Classroom 0 372 8 0
102-B Classroom 0 230 5 0
103 Classroom 0 506 11 0
104 Classroom 0 Yes 594 13 13
107 Classroom 0 Yes 682 15 15
108 Nurse's Office 0 Yes 176 4 4
- 2nd Floor Dean of Student's Office 0 144 3 0
200 Classroom 0 Yes 667 15 15
201 Classroom 0 Yes 667 15 15
202 Classroom 0 Yes 667 15 15
203 Classroom 0 136 3 0
204 Computer Lab 0 Yes 924 21 21
205 Classroom  0 414 9 0
206 Classroom  0 Yes 736 16 16
207 Classroom 0 Yes 667 15 15
208 Classroom 0 Yes 638 14 14
209 Classroom 0 Yes 638 14 14
- 3rd Floor Men's Room 0 56 1 0
300 Classroom 0 Yes 638 14 14
301 Classroom 0 Yes 667 15 15
302 Classroom 0 Yes 667 15 15
303 Classroom 0 Yes 616 14 14
304 Classroom 0 Yes 594 13 13
305-306 Library 0 Yes 1,320 30 30
307 Classroom 0 Yes 638 14 14
308 Classroom 0 Yes 660 15 15
309 Classroom 0 638 14 0
400 Classroom 0 Yes 667 15 15
401 Classroom 0 Yes 667 15 15
402 Classroom 0 Yes 667 15 15
403 Classroom 0 Yes 638 14 14
404 Classroom 0 Yes 667 15 15
405 Classroom 0 Yes 667 15 15
406 Classroom 0 Yes 667 15 15
407 Classroom 0 Yes 667 15 15
408 Classroom 0 Yes 638 14 14
409 Classroom 0 Yes 667 15 15
410 Classroom 0 Yes 638 14 14
500 Classroom 0 Yes 132 3 3
- Gym 0 Yes 3,555 80 80 Hydroxyl Unit
- Building Engineer's Office 0 286 6 0
- Main Office 0 Yes 286 6 6
- Principal's Office 0 Yes 154 3 3
- Teacher's Lounge 0 322 7 0
Sheet Last Modified: 3/18/21      
School:  Bayard Taylor Elementary School
Vendor: EMCOR Main Building Test 10-29-20
Vendor: Devine Main Building Retest 2-7-21
School:  Bayard Taylor Annex (Our Lady of Pompeii)
Vendor: EMCOR EMCOR Retest 2-18-21
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Taylor Main Building
B1 Classroom 210 14 780 17 14 Univent
B1B and B1B North & South. B1 and B1 North & South. 325 21 760 17 17 Univent
B2A & B2B Classroom 0 0 600 13 0 Univent
B4 Classroom 299 19 1444 32 19 Univent
B5 Classroom 316 21 1410 32 21 Univent
101 Classroom 362 24 1159 26 24 Univent
102 Classroom 0 Yes 1148 26 26 Univent
103 Classroom 328 21 1149 26 21 Univent
104 Classroom 387 25 1107 25 25 Univent
105 Classroom 387 25 1394 31 25 Univent
201 Classroom 342 22 1101 25 22 Univent
202 Classroom 423 28 1097 24 24 Univent
203 Classroom 0 Yes 1163 26 26 Univent
204 Classroom 444 29 1099 24 24 Univent
205 Classroom 470 31 1098 24 24 Univent
206 Classroom 408 27 1052 23 23 Univent
301 Classroom 0 Yes 1066 24 24 Univent
302 Classroom 299 19 1065 24 19 Univent
303 Classroom 317 21 1127 25 21 Univent
304 Classroom 344 22 1133 25 22 Univent
305 Classroom 73 4 Yes 1109 25 25 Univent
306 Classroom 483 32 1107 25 25 Univent
- IMC Library 353 23 1641 37 23 Univent
- Music Classroom 162 10 780 17 10 Univent
- Main Office 303 20 889 20 20 Univent
- Principal 359 23 479 10 10 Univent
- Lounge 232 15 300 6 6 Univent
- Nurse 148 9 300 6 6 Univent
- Art Classroom 123 8 1107 25 8 Univent
Taylor Annex
222 Classroom 0 750 17 0 N/A
223 Classroom 0 625 14 0 N/A
224 Classroom 0 675 15 0 N/A
231 Classroom 0 700 15 0 N/A
331 Classroom 0 700 15 0 N/A
332 Classroom 0 750 17 0 N/A
333 Classroom 0 675 15 0 N/A
334 Classroom 0 625 14 0 N/A
- Auditorium/Gym/Ca 0 2,516 57 0 N/A
Sheet Last Modified: 4-30-21        
School:  Tilden Middle School
Vendor:  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 0 576 13 0 House Fan
101 Classroom 0 624 14 0 House Fan
103 Classroom 0 Yes 960 21 21 House Fan
104 Classroom 0 1,248 28 0 House Fan
105 Classroom 0 Yes 1,248 28 28 House Fan
106 Classroom 0 Yes 864 19 19 House Fan
107 Classroom 0 Yes 792 18 18 House Fan
109 Classroom 0 Yes 792 18 18 House Fan
109A Classroom 0 704 16 0 House Fan
110 Classroom 0 Yes 616 14 14 House Fan
202 Classroom 0 Yes 768 17 17 House Fan
203 Classroom 0 Yes 672 15 15 House Fan
203A Classroom 0 Yes 1,056 24 24 House Fan
204 Classroom 0 Yes 672 15 15 House Fan
205 Nurse's office 0 Yes 384 8 8 House Fan
207A Principal's Office 0 Yes 560 12 12 House Fan
207C Counselor's Suite 0 120 2 0 House Fan
207D Counselor's Suite 0 Yes 120 2 2 House Fan
207F Counselor's Suite 0 Yes 120 2 2 House Fan
207G Counselor's Suite 0 Yes 120 2 2 House Fan
207H Counselor's Suite 0 120 2 0 House Fan
208 Main Office 0 Yes 560 12 12 House Fan
209 IMC 0 Yes 1,728 39 39 House Fan
211 Classroom 0 Yes 968 22 22 House Fan
212 Classroom 0 Yes 1,152 26 26 House Fan
213 Classroom 0 616 14 0 House Fan
214 Classroom 0 Yes 672 15 15 House Fan
214A Classroom 0 Yes 864 19 19 House Fan
215 Classroom 0 Yes 576 13 13 House Fan
301 Classroom 0 576 13 0 House Fan
302 Carson Valley 0 288 6 0 House Fan
303 Classroom 0 Yes 672 15 15 House Fan
303A Classroom 0 Yes 672 15 15 House Fan
304 Classroom 0 Yes 672 15 15 House Fan
305 Classroom 0 672 15 0 House Fan
306 Classroom 0 616 14 0 House Fan
307 Classroom 0 672 15 0 House Fan
308 Classroom 0 672 15 0 House Fan
310 Classroom 0 480 10 0 House Fan
311 Classroom 0 768 17 0 House Fan
312 Classroom 0 672 15 0 House Fan
313 Classroom 0 672 15 0 House Fan
314 Classroom 0 672 15 0 House Fan
315 Dean of Students 0 Yes 216 4 4 House Fan
316 Classroom 0 Yes 768 17 17 House Fan
318 Classroom 0 792 18 0 House Fan
319 Classroom 0 832 18 0 House Fan
401 Classroom 0 Yes 625 14 14 House Fan
403A Faculty Lounge 0 Yes 792 18 18 House Fan
404 Classroom 0 Yes 1,056 24 24 House Fan
404A Classroom 0 Yes 120 2 2 House Fan
405 Classroom 0 Yes 1,056 24 24 House Fan
406 Classroom 0 Yes 1,056 24 24 House Fan
407 Classroom 0 Yes 1,056 24 24 House Fan
408 Classroom 0 Yes 792 18 18 House Fan
410B Staff Conference 0 Yes 1,232 28 28 House Fan
411 Classroom 0 Yes 769 17 17 House Fan
412 Classroom 0 Yes 968 22 22 House Fan
414 Classroom 0 Yes 968 22 22 House Fan
415 Classroom 0 Yes 672 15 15 House Fan
416 Classroom 0 Yes 392 8 8 House Fan
- Cafeteria 0 Yes 5150 117 117 House Fan
Sheet Last Modified: 03-30-2021    
School:  Trinidad Center
Vendor: Devine Brothers
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
- Adult Restroom 13 0 0 0 Air Handling Unit
- Assistant Director's Office 16 1 0 0 Air Handling Unit
- Boy's Restroom 16 1 0 0 Air Handling Unit
- Computer Room 31 2 0 0 Air Handling Unit
- Corridor 0 0 0 Air Handling Unit
- Front Entrance 34 2 0 0 Air Handling Unit
- Girl's Restroom 18 1 0 0 Air Handling Unit
- Gym 0 0 0 Air Handling Unit
- Hallway 0 0 0 Air Handling Unit
- Head Receptionist's Office 21 1 0 0 Air Handling Unit
- Kitchen 50 3 0 0 Air Handling Unit
- Library 0 0 0 Air Handling Unit
- Main Corridor (Hallway) 0 0 0 0 Air Handling Unit
- Maintenance Office 22 1 0 0 Air Handling Unit
- Rear Entrance 19 1 0 0 Air Handling Unit
1 Classroom 101 6 Yes 610 13 13 Air Handling Unit
2 Classroom 95 6 Yes 610 13 13 Air Handling Unit
3 Classroom 100 6 Yes 575 13 13 Air Handling Unit
4 Classroom 112 7 Yes 575 13 13 Air Handling Unit
5 Classroom 132 8 590 13 8 Air Handling Unit
6 Classroom 0 Yes 629 14 14 Air Handling Unit
7 Storage 0 Yes 609 13 13 Air Handling Unit
8 Storage 0 0 0 Air Handling Unit
9 Storage 0 0 0 Air Handling Unit
10 Roof Access 0 0 0 Air Handling Unit
- Stairway 0 0 0 Air Handling Unit
Sheet Last Modified: 03-18-2021    
School:  The U School at Ferguson
Vendor: EMCOR Fluidics
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
B10 Classroom 0.0 0 886 20 0 Unit Ventilator
B11 Classroom 0.0 0 886 20 0 Unit Ventilator
B12 Classroom 0.0 0 886 20 0 Unit Ventilator
110 Classroom 0.0 0 886 20 0 Unit Ventilator
111 Classroom 0.0 0 886 20 0 Unit Ventilator
112 Classroom 0.0 0 886 20 0 Unit Ventilator
113 Classroom 0.0 0 884 20 0 Unit Ventilator
114 Classroom 0.0 0 884 20 0 Unit Ventilator
115 Classroom 0.0 0 884 20 0 Unit Ventilator
210 Classroom 0.0 0 886 20 0 Unit Ventilator
211 Classroom 0.0 0 886 20 0 Unit Ventilator
212 Classroom 0.0 0 886 20 0 Unit Ventilator
213 Classroom 0.0 0 884 20 0 Unit Ventilator
214 Classroom 0.0 0 884 20 0 Unit Ventilator
215 Classroom 0.0 0 884 20 0 Unit Ventilator
310 Classroom 0.0 0 886 20 0 Unit Ventilator
311 Classroom 0.0 0 886 20 0 Unit Ventilator
312 Classroom 0.0 0 886 20 0 Unit Ventilator
313 Classroom 0.0 0 884 20 0 Unit Ventilator
314 Classroom 0.0 0 442 10 0 Unit Ventilator
315 Classroom 0.0 0 884 20 0 Unit Ventilator
Sheet Last Modified: 04-06-2021    
School:  Vare-Washington Elementary School
Vendor: EMCOR Fluidics EMCOR Retest Devine Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 classroom 478 31 1040 23 23 Unit Ventilator
102 classroom 251 16 Yes 936 21 21 Unit Ventilator
103 classroom 267 17 780 17 17 Unit Ventilator
104 classroom 331 22 780 17 17 Unit Ventilator
105 classroom 297 19 936 21 19 Unit Ventilator
106 classroom 390 26 1040 23 23 Unit Ventilator
107 classroom 210 14 Yes 780 17 17 Unit Ventilator
108 classroom 319 21 767 17 17 Unit Ventilator
109 classroom 313 20 767 17 17 Unit Ventilator
110 classroom 594 39 1482 33 33 Unit Ventilator
201 Counselor 380 25 684 15 15 Unit Ventilator
202 classroom 326 21 832 18 18 Unit Ventilator
203 4-6 Autistic Supp. 316 21 832 18 18 Unit Ventilator
204 classroom 310 20 832 18 18 Unit Ventilator
205 K-2 Autistic Supp. 210 14 Yes 832 18 18 Unit Ventilator
206 classroom 417 27 832 18 18 Unit Ventilator
207 classroom 227 15 832 18 15 Unit Ventilator
208A 3-4 Autistic Supp. 293 19 832 18 18 Unit Ventilator
208B K-2 Emotional Support 297 19 725 16 16 Unit Ventilator
210 ESOL 234 15 575 13 13 Unit Ventilator
211 ESOL/SBTL 251 16 628 14 14 Unit Ventilator
213 classroom 405 27 1092 24 24 Unit Ventilator
214 classroom 322 21 468 10 10 Unit Ventilator
301 classroom 258 17 780 17 17 Unit Ventilator
302 classroom 291 19 780 17 17 Unit Ventilator
303 classroom 217 14 Yes 780 17 17 Unit Ventilator
304 classroom 234 15 780 17 15 Unit Ventilator
305 classroom 287 19 780 17 17 Unit Ventilator
306 classroom 323 21 690 15 15 Unit Ventilator
307 classroom 217 14 Yes 780 17 17 Unit Ventilator
308 classroom 269 17 988 22 17 Unit Ventilator
309 Psychologist / Climate Liaison 185 12 598 13 12 Unit Ventilator
310 Math Interventionist 211 14 624 14 14 Unit Ventilator
311 classroom 189 12 Yes 624 14 14 Unit Ventilator
312A classroom 295 19 1014 23 19 Unit Ventilator
313 classroom 166 11 494 11 11 Unit Ventilator
- Gym 305 20 4352 98 20 Unit Ventilator
- Library 208 13 578 13 13 Unit Ventilator
- Lunch Room 146 9 Yes 1292 29 29 Unit Ventilator
- Music 748 49 1098 24 24 Unit Ventilator
- Main Office 0 Yes 396 9 9 Active Pure Unit
- Princpal's Office 0 Yes 350 7 7 Active Pure Unit
- Nurse's Office 0 Yes 264 6 6 Active Pure Unit
Sheet Last Modified: 3/12/21    
School:  EH Vare
Vendor:  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
109 - 0 0 0
110 - 0 0 0
 
 
 
   
   
   
   
   
   
         
   
   
   
   
 
 
 
 
Sheet Last Modified: 04-21-2021    
School:  General Louis Wagner Middle School
Vendor: EMCOR Fluidics Exhaust Report
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101A classroom 312 20 552 12 12 Air Handling Unit
101B classroom 376 25 506 11 11 Air Handling Unit
102 classroom 644 42 888 20 20 Air Handling Unit
103A classroom 1,312 87 1,344 30 30 Air Handling Unit
105 classroom 527 35 878 19 19 Air Handling Unit
106 classroom 713 47 883 20 20 Air Handling Unit
107 classroom 635 42 705 16 16 Air Handling Unit
108 classroom 586 39 916 20 20 Air Handling Unit
111 classroom 536 35 360 8 8 Air Handling Unit
112 classroom 585 39 720 16 16 Air Handling Unit
201 classroom 973 64 711 16 16 Air Handling Unit
202 classroom 907 60 677 15 15 Air Handling Unit
203 classroom 306 20 697 15 15 Air Handling Unit
204 classroom 600 40 657 14 14 Air Handling Unit
205A Counselor Office 597 39 306 6 6 Air Handling Unit
205B Counselor Office 690 46 306 6 6 Air Handling Unit
209A classroom 496 33 2,064 46 33 Air Handling Unit
209B classroom 763 50 336 7 7 Air Handling Unit
209C classroom 995 66 336 7 7 Air Handling Unit
212 classroom 1,030 68 859 19 19 Air Handling Unit
213 classroom 870 58 656 14 14 Air Handling Unit
214 classroom 446 29 714 16 16 Air Handling Unit
215 classroom 240 16 659 14 14 Air Handling Unit
216 classroom 2,170 144 777 17 17 Air Handling Unit
217 classroom 1,626 108 743 16 16 Air Handling Unit
218 classroom 197 13 645 14 13 Air Handling Unit
219 classroom 1,463 97 643 14 14 Air Handling Unit
220 classroom 731 48 563 12 12 Air Handling Unit
221 classroom 1,653 110 779 17 17 Air Handling Unit
222 classroom 667 44 670 15 15 Air Handling Unit
225 Dean 272 18 348 7 7 Air Handling Unit
226 classroom 671 44 654 14 14 Air Handling Unit
301 classroom 1,282 85 714 16 16 Air Handling Unit
302 classroom 2,224 148 670 15 15 Air Handling Unit
303 classroom 2,929 195 671 15 15 Air Handling Unit
304A classroom 1,335 89 984 22 22 Air Handling Unit
305 classroom 3,981 265 956 21 21 Air Handling Unit
306 classroom 3,461 230 783 17 17 Air Handling Unit
307 classroom 996 66 912 20 20 Air Handling Unit
308 classroom 1,202 80 928 21 21 Air Handling Unit
309 classroom 2,171 144 847 19 19 Air Handling Unit
310 classroom 2,047 136 881 20 20 Air Handling Unit
311A classroom 990 66 929 21 21 Air Handling Unit
312 classroom 211 14 716 16 14 Air Handling Unit
313 classroom 868 57 672 15 15 Air Handling Unit
314 classroom 350 23 719 16 16 Air Handling Unit
315 classroom 83 5 662 15 5 Air Handling Unit
316 classroom 1,078 71 778 17 17 Air Handling Unit
317 classroom 1,382 92 604 13 13 Air Handling Unit
318 classroom 1,811 120 610 13 13 Air Handling Unit
319 classroom 3,185 212 644 14 14 Air Handling Unit
320 classroom 4,504 300 738 16 16 Air Handling Unit
321 classroom 3,538 235 786 17 17 Air Handling Unit
322 classroom 82 5 660 15 5 Air Handling Unit
323 classroom 1,074 71 324 7 7 Air Handling Unit
324 classroom 909 60 659 14 14 Air Handling Unit
325 classroom 1,021 68 346 7 7 Air Handling Unit
326 classroom 481 32 659 14 14 Air Handling Unit
326 Counselor Office 513 34 306 6 6 Air Handling Unit
- Auditorium 0 0 5,460 124 0 Air Handling Unit
- Boy's Gym 14,624 974 4,350 98 98 Air Handling Unit
- Cafeteria 498 33 408 9 9 Air Handling Unit
- Computer Lab 446 29 657 14 14 Air Handling Unit
- Conf. Room 884 58 336 7 7 Air Handling Unit
- Kitchen 5,749 383 816 18 18 Air Handling Unit
- Kitchen- Freezer/Cooler Condenser Fan 0 0 144 3 0 Air Handling Unit
- Lunch Room 175 11 2,040 46 11 Air Handling Unit
- Main Office 632 42 531 12 12 Air Handling Unit
Principal Office 0 Yes 259 5 5
Nurse Office 0 Yes 249 5 5
- MEDIA LAB A 304 20 60 1 1 Air Handling Unit
- MEDIA LAB B 564 37 60 1 1 Air Handling Unit
- Staff Lounge 421 28 657 14 14 Air Handling Unit
- VP Office 1,325 88 232 5 5 Air Handling Unit
- Gym- Weight Room A 1,230 82 181 4 4 Air Handling Unit
- Gym- Weight Room B 1,164 77 181 4 4 Air Handling Unit
Sheet Last Modified: 04-26-2021    
School:  Laura W. Waring Elementary School
Vendor: EMCOR Fluidics EMCOR Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 188 12 Yes 430 9 9 Nesbitt Unit Ventilator
102 Classroom 118 7 Yes 872 19 19 Nesbitt Unit Ventilator
103 Classroom 150 10 Yes 872 19 19 Nesbitt Unit Ventilator
105 Classroom 180 12 Yes 789 17 17 Nesbitt Unit Ventilator
106 Classroom 171 11 Yes 850 19 19 Nesbitt Unit Ventilator
107 Classroom 226 15 850 19 15 Nesbitt Unit Ventilator
108 Classroom 165 11 Yes 750 17 17 Nesbitt Unit Ventilator
200 Counselor's Room 0 0 300 6 0 Nesbitt Unit Ventilator
201 Computer Room 0 0 Yes 925 21 21 Nesbitt Unit Ventilator
202 Classroom 87 5 Yes 888 20 20 Nesbitt Unit Ventilator
203 Classroom 274 18 888 20 18 Nesbitt Unit Ventilator
204 Classroom 276 18 888 20 18 Nesbitt Unit Ventilator
205 Classroom 311 20 850 19 19 Nesbitt Unit Ventilator
206 Classroom 193 12 Yes 850 19 19 Nesbitt Unit Ventilator
207 Classroom 152 10 Yes 850 19 19 Nesbitt Unit Ventilator
208 Classroom 209 13 Yes 750 17 17 Nesbitt Unit Ventilator
300 Classroom 0 0 Yes 888 20 20 Nesbitt Unit Ventilator
301 Classroom 212 14 Yes 888 20 20 Nesbitt Unit Ventilator
302 Classroom 105 7 Yes 888 20 20 Nesbitt Unit Ventilator
303 Classroom 133 8 Yes 888 20 20 Nesbitt Unit Ventilator
304 Classroom 255 17 888 20 17 Nesbitt Unit Ventilator
305 Classroom 93 6 Yes 888 20 20 Nesbitt Unit Ventilator
306/307 Classroom 266 17 1850 42 17 Nesbitt Unit Ventilator
308 Classroom 220 14 Yes 896 20 20 Nesbitt Unit Ventilator
311 Dining Room 120 8 242 5 5 Nesbitt Unit Ventilator
- Cafeteria 0 0 3477 79 0 Nesbitt Unit Ventilator
- Vestibule left of office 0 0 96 2 0 Nesbitt Unit Ventilator
- Nurse 0 231 5 0 Nesbitt Unit Ventilator
- Faculty Lounge 57 3 228 5 3 Nesbitt Unit Ventilator
- Health Office 0 0 Yes 231 5 5 Nesbitt Unit Ventilator
- Multi-Purpose Room 457 30 1820 41 30 Nesbitt Unit Ventilator
- Main Office 0 0 Yes 378 8 8 Nesbitt Unit Ventilator
- Principal's Office 69 4 Yes 381 8 8 Nesbitt Unit Ventilator
Sheet Last Modified: 04-30-2021    
School:  George Washington High School
Vendor: EMCOR Meehan (Auditorium)
School:  George Washington High School Annex
Vendor:      
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Main Building
1 - 370 24 768 17 17 Carrier / Perimeter Heater
2 - 0 0 0 0 Carrier / Perimeter Heater
3 - 0 0 768 17 0 Carrier / Perimeter Heater
4 - 0 0 0 0 Carrier / Perimeter Heater
5 - 0 0 768 17 0 Carrier / Perimeter Heater
6 - 0 0 0 0 Carrier / Perimeter Heater
7 - 348 23 768 17 17 Carrier / Perimeter Heater
8 - 0 0 0 0 Carrier / Perimeter Heater
9 - 412 27 768 17 17 Carrier / Perimeter Heater
10 - 0 0 0 0 Carrier / Perimeter Heater
11 - 451 30 768 17 17 Carrier / Perimeter Heater
12 - 0 0 775 17 0 Carrier / Perimeter Heater
13 - 414 27 1209 27 27 Carrier / Perimeter Heater
14 - 374 24 1209 27 24 Carrier / Perimeter Heater
15 - 403 26 1209 27 26 Carrier / Perimeter Heater
16 - 849 56 1911 43 43 Carrier / Perimeter Heater
17 - 0 0 1240 28 0 Carrier / Perimeter Heater
18 - 763 50 1911 43 43 Carrier / Perimeter Heater
19 - 0 0 1302 29 0 Carrier / Perimeter Heater
20 - 0 0 0 0 Carrier / Perimeter Heater
21 - 451 30 1240 28 28 Carrier / Perimeter Heater
22 - 421 28 1209 27 27 Carrier / Perimeter Heater
23 - 0 0 1240 28 0 Carrier / Perimeter Heater
24 - 0 0 0 0 Carrier / Perimeter Heater
25 - 419 27 912 20 20 Carrier / Perimeter Heater
26 - 0 0 0 0 Carrier / Perimeter Heater
27 - 0 0 912 20 0 Carrier / Perimeter Heater
28 - 0 0 0 0 Carrier / Perimeter Heater
29 - 355 23 768 17 17 Carrier / Perimeter Heater
30 - 0 0 0 0 Carrier / Perimeter Heater
31 - 413 27 768 17 17 Carrier / Perimeter Heater
32 - 0 0 0 0 Carrier / Perimeter Heater
33 - 338 22 768 17 17 Carrier / Perimeter Heater
34 - 0 0 0 0 Carrier / Perimeter Heater
35 - 0 0 768 17 0 Carrier / Perimeter Heater
36 - 0 0 0 0 Carrier / Perimeter Heater
37 - 0 0 768 17 0 Carrier / Perimeter Heater
38 - 0 0 0 0 Carrier / Perimeter Heater
39 - 403 26 768 17 17 Carrier / Perimeter Heater
100 - 334 22 768 17 17 Carrier / Perimeter Heater
102 - 335 22 768 17 17 Carrier / Perimeter Heater
104 Health Room 0 1488 33 0
107 - 495 33 0 0 Carrier / Perimeter Heater
108 - 0 0 0 0 Carrier / Perimeter Heater
109 - 357 23 744 16 16 Carrier / Perimeter Heater
110 - 413 27 0 0 Carrier / Perimeter Heater
111 - 370 24 768 17 17 Carrier / Perimeter Heater
112 - 398 26 768 17 17 Carrier / Perimeter Heater
113 - 0 0 0 0 Carrier / Perimeter Heater
114 - 427 28 768 17 17 Carrier / Perimeter Heater
115 - 0 0 0 0 Carrier / Perimeter Heater
116 - 368 24 768 17 17 Carrier / Perimeter Heater
117 - 0 0 0 0 Carrier / Perimeter Heater
118 - 0 0 768 17 0 Carrier / Perimeter Heater
119 - 368 24 0 0 Carrier / Perimeter Heater
120 - 0 0 768 17 0 Carrier / Perimeter Heater
121 - 381 25 768 17 17 Carrier / Perimeter Heater
122 - 408 27 792 18 18 Carrier / Perimeter Heater
123 - 465 31 768 17 17 Carrier / Perimeter Heater
124 - 436 29 768 17 17 Carrier / Perimeter Heater
125 - 0 0 0 0 Carrier / Perimeter Heater
126 - 336 22 768 17 17 Carrier / Perimeter Heater
127 - 416 27 1102 25 25 Carrier / Perimeter Heater
128 - 0 0 1280 29 0 Carrier / Perimeter Heater
129 - 366 24 1073 24 24 Carrier / Perimeter Heater
130 - 0 0 1280 29 0 Carrier / Perimeter Heater
131 - 388 25 1160 26 25 Carrier / Perimeter Heater
132 - 610 40 1092 24 24 Carrier / Perimeter Heater
133 - 0 0 0 0 Carrier / Perimeter Heater
134 - 732 48 1092 24 24 Carrier / Perimeter Heater
135 - 0 0 0 0 Carrier / Perimeter Heater
136 - 325 21 1092 24 21 Carrier / Perimeter Heater
137 - 0 0 0 0 Carrier / Perimeter Heater
138 - 408 27 0 0 Carrier / Perimeter Heater
139 - 0 0 0 0 Carrier / Perimeter Heater
140 - 424 28 0 0 Carrier / Perimeter Heater
141 - 0 0 0 0 Carrier / Perimeter Heater
142 - 865 57 0 0 Carrier / Perimeter Heater
143 - 0 0 0 0 Carrier / Perimeter Heater
144 - 308 20 832 18 18 Carrier / Perimeter Heater
145 - 0 0 0 0 Carrier / Perimeter Heater
146 - 0 0 775 17 0 Carrier / Perimeter Heater
147 - 0 0 0 0 Carrier / Perimeter Heater
148 - 242 16 775 17 16 Carrier / Perimeter Heater
149 -155 - 0 0 0 0 Carrier / Perimeter Heater
156 - 926 61 814 18 18 Carrier / Perimeter Heater
157 - 0 0 0 0 Carrier / Perimeter Heater
158 - 0 0 0 0 Carrier / Perimeter Heater
159 - 0 0 0 0 Carrier / Perimeter Heater
160 - 0 0 0 0 Carrier / Perimeter Heater
161 - 0 0 0 0 Carrier / Perimeter Heater
162 - 0 0 0 0 Carrier / Perimeter Heater
164 - 695 46 0 0 Carrier / Perimeter Heater
200 - 485 32 768 17 17 Carrier / Perimeter Heater
201 - 0 0 0 0 Carrier / Perimeter Heater
202 - 417 27 768 17 17 Carrier / Perimeter Heater
203 - 397 26 768 17 17 Carrier / Perimeter Heater
204 - 337 22 768 17 17 Carrier / Perimeter Heater
205 - 0 0 768 17 0 Carrier / Perimeter Heater
206 - 424 28 0 0 Carrier / Perimeter Heater
207 - 0 0 768 17 0 Carrier / Perimeter Heater
208 - 536 35 768 17 17 Carrier / Perimeter Heater
209 - 0 0 0 0 Carrier / Perimeter Heater
210 - 575 38 768 17 17 Carrier / Perimeter Heater
211 - 0 0 0 0 Carrier / Perimeter Heater
212 - 514 34 768 17 17 Carrier / Perimeter Heater
213 - 0 0 0 0 Carrier / Perimeter Heater
214 - 0 0 768 17 0 Carrier / Perimeter Heater
215 - 547 36 768 17 17 Carrier / Perimeter Heater
216 - 519 34 768 17 17 Carrier / Perimeter Heater
217 - 0 0 0 0 Carrier / Perimeter Heater
218 - 521 34 1536 34 34 Carrier / Perimeter Heater
219 - 0 0 1536 34 0 Carrier / Perimeter Heater
220 - 0 0 1536 34 0 Carrier / Perimeter Heater
221 - 0 0 768 17 0 Carrier / Perimeter Heater
222 - 569 37 768 17 17 Carrier / Perimeter Heater
223 - 0 0 0 0 Carrier / Perimeter Heater
224 - 533 35 792 18 18 Carrier / Perimeter Heater
225 - 0 0 0 0 Carrier / Perimeter Heater
226 - 536 35 792 18 18 Carrier / Perimeter Heater
227 - 0 0 0 0 Carrier / Perimeter Heater
228 - 543 36 792 18 18 Carrier / Perimeter Heater
229 - 508 33 792 18 18 Carrier / Perimeter Heater
230 - 563 37 792 18 18 Carrier / Perimeter Heater
231 - 492 32 792 18 18 Carrier / Perimeter Heater
232 - 563 37 792 18 18 Carrier / Perimeter Heater
233 - 0 0 0 0 Carrier / Perimeter Heater
234 - 539 35 792 18 18 Carrier / Perimeter Heater
235 - 0 0 0 0 Carrier / Perimeter Heater
236 - 544 36 792 18 18 Carrier / Perimeter Heater
237 - 0 0 0 0 Carrier / Perimeter Heater
238 - 399 26 792 18 18 Carrier / Perimeter Heater
239 - 0 0 0 0 Carrier / Perimeter Heater
240 - 0 0 768 17 0 Carrier / Perimeter Heater
241 - 344 22 792 18 18 Carrier / Perimeter Heater
242 - 450 30 768 17 17 Carrier / Perimeter Heater
243 - 455 30 792 18 18 Carrier / Perimeter Heater
244 - 428 28 792 18 18 Carrier / Perimeter Heater
245 - 0 0 0 0 Carrier / Perimeter Heater
246 - 423 28 792 18 18 Carrier / Perimeter Heater
300 - 0 0 0 0 Carrier / Perimeter Heater
301 - 0 0 0 0 Carrier / Perimeter Heater
302 - 542 36 792 18 18 Carrier / Perimeter Heater
303 - 539 35 792 18 18 Carrier / Perimeter Heater
304 - 591 39 792 18 18 Carrier / Perimeter Heater
305 - 556 37 792 18 18 Carrier / Perimeter Heater
306 - 561 37 792 18 18 Carrier / Perimeter Heater
307 - 592 39 792 18 18 Carrier / Perimeter Heater
308 - 263 17 792 18 17 Carrier / Perimeter Heater
309 - 0 0 0 0 Carrier / Perimeter Heater
310 - 602 40 792 18 18 Carrier / Perimeter Heater
311 - 0 0 0 0 Carrier / Perimeter Heater
312 - 599 39 792 18 18 Carrier / Perimeter Heater
313 - 0 0 0 0 Carrier / Perimeter Heater
314 - 539 35 792 18 18 Carrier / Perimeter Heater
315 - 530 35 792 18 18 Carrier / Perimeter Heater
316 - 557 37 792 18 18 Carrier / Perimeter Heater
317 - 0 0 0 0 Carrier / Perimeter Heater
318 - 580 38 768 17 17 Carrier / Perimeter Heater
319 - 0 0 0 0 Carrier / Perimeter Heater
320 - 610 40 768 17 17 Carrier / Perimeter Heater
321 - 551 36 792 18 18 Carrier / Perimeter Heater
322 - 554 36 792 18 18 Carrier / Perimeter Heater
323 - 0 0 0 0 Carrier / Perimeter Heater
324 - 591 39 960 21 21 Carrier / Perimeter Heater
325 - 0 0 0 0 Carrier / Perimeter Heater
326 - 533 35 960 21 21 Carrier / Perimeter Heater
327 - 554 36 960 21 21 Carrier / Perimeter Heater
328 - 561 37 960 21 21 Carrier / Perimeter Heater
329 - 0 0 0 0 Carrier / Perimeter Heater
330 - 572 38 960 21 21 Carrier / Perimeter Heater
331 - 0 0 0 0 Carrier / Perimeter Heater
332 - 576 38 792 18 18 Carrier / Perimeter Heater
333 - 0 0 0 0 Carrier / Perimeter Heater
334 - 506 33 960 21 21 Carrier / Perimeter Heater
335 - 605 40 0 0 Carrier / Perimeter Heater
336 - 559 37 960 21 21 Carrier / Perimeter Heater
337 - 0 0 792 18 0 Carrier / Perimeter Heater
338 - 0 0 792 18 0 Carrier / Perimeter Heater
339 - 0.0 0 792 18 0 Carrier / Perimeter Heater
Gymnasium Gymnasium 0 0 0
Auditorium Auditorium 17,891.0 1192 10800 245 245 Air Handling Unit
- Beacon Left 311 20 0 0 Carrier / Perimeter Heater
- Beacon Right 0 0 0 0 Carrier / Perimeter Heater
- Cafeteria 17015 1134 0 0 Air Handling Unit
Center - 438 29 0 0 Carrier / Perimeter Heater
Dean's Office - 437 29 0 0 Carrier / Perimeter Heater
Library Left - 0 0 0 0 Carrier / Perimeter Heater
Main Office - 394 26 2332 53 26 Carrier / Perimeter Heater
Principle - 0 0 615 13 0 Carrier / Perimeter Heater
Right - 0 0 0 0 Carrier / Perimeter Heater
- Roster 426 28 0 0 Carrier / Perimeter Heater
- Staff Cafeteria 1328 88 0 0 Make-up Air Unit
- Student Cafeteria 8507 567 12000 272 272 Make-up Air Unit
Annex
408 Annex Classroom 0 Yes 858 19 19 Air Handling Unit
409 Annex Classroom 0 Yes 858 19 19 Air Handling Unit
410 Annex Classroom 0 Yes 858 19 19 Air Handling Unit
412 Annex Classroom 0 Yes 0 0 Air Handling Unit
Kitchen Annex Kitchen 0 Yes 0 0 Air Handling Unit
Recceration room - 0 3780 85 85
Health Suite/ 11 rms - 0 77 1 1
Health Suite/ 2 rms - 0 80 1 1
Sheet Last Modified: 04-14-2021    
School:  Grover Washington Jr. Middle School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 CLASSROOM 288 19 700 15 15 Fan Coil Unit
101 CLASSROOM 207 13 Yes 700 15 15 Fan Coil Unit
102 CLASSROOM 164 10 Yes 698 15 15 Fan Coil Unit
102A CLASSROOM 185 12 160 3 3 Fan Coil Unit
103 CLASSROOM 476 31 858 19 19 Univent
104 CLASSROOM 595 39 783 17 17 Univent
105 CLASSROOM 935 62 726 16 16 Univent
106 CLASSROOM 421 28 726 16 16 Univent
107 CLASSROOM 274 18 858 19 18 Univent
108 CLASSROOM 395 26 858 19 19 Univent
109 CLASSROOM 573 38 858 19 19 Univent
110 CLASSROOM 310 20 858 19 19 Univent
112 CLASSROOM 377 25 858 19 19 Univent
113 CLASSROOM 392 26 312 7 7 Univent
114 CLASSROOM 361 24 858 19 19 Univent
115 CLASSROOM 292 19 726 16 16 Univent
116 CLASSROOM 749 49 726 16 16 Univent
117 CLASSROOM 763 50 726 16 16 Univent
118 CLASSROOM 757 50 726 16 16 Univent
119 CLASSROOM 396 26 858 19 19 Univent
120 CLASSROOM 304 20 858 19 19 Univent
121 CLASSROOM 370 24 858 19 19 Univent
122 CLASSROOM 314 20 858 19 19 Univent
201 2ND FLOOR C WING OFFICE 211 14 312 7 7 Univent
202 CLASSROOM 601 40 858 19 19 Univent
203 CLASSROOM 580 38 858 19 19 Univent
204 CLASSROOM 304 20 858 19 19 Univent
205 CLASSROOM 285 19 858 19 19 Univent
206 CLASSROOM 406 27 783 17 17 Univent
207 CLASSROOM 456 30 726 16 16 Univent
208 CLASSROOM 561 37 1584 36 36 Univent
209 CLASSROOM 320 21 858 19 19 Univent
210 CLASSROOM 388 25 858 19 19 Univent
211 CLASSROOM 348 23 858 19 19 Univent
212 CLASSROOM 318 21 858 19 19 Univent
213 CLASSROOM 307 20 1248 28 20 Univent
214 CLASSROOM 286 19 Yes 1144 26 26 Univent
215 CLASSROOM 693 46 1170 26 26 Univent
216 CLASSROOM 370 24 783 17 17 Univent
217 CLASSROOM 306 20 726 16 16 Univent
218 CLASSROOM 314 20 783 17 17 Univent
219 CLASSROOM 332 22 858 19 19 Univent
220 CLASSROOM 407 27 858 19 19 Univent
221 2ND FLOOR D WING OFFICE 181 12 312 7 7 Univent
301 CLASSROOM 112 7 Yes 858 19 19 Fan Coil Unit
302 CLASSROOM 339 22 858 19 19 Univent
303 CLASSROOM 0 0 Yes 858 19 19 Univent
304 CLASSROOM 231 15 858 19 15 Univent
305 CLASSROOM 385 25 858 19 19 Univent
306 CLASSROOM 353 23 783 17 17 Univent
307 CLASSROOM 316 21 726 16 16 Univent
308 CLASSROOM 306 20 1584 36 20 Univent
309 CLASSROOM 486 32 858 19 19 Univent
310 CLASSROOM 283 18 858 19 18 Univent
311 CLASSROOM 265 17 858 19 17 Univent
312 CLASSROOM 389 25 858 19 19 Univent
313 CLASSROOM 355 23 858 19 19 Univent
314 CLASSROOM 305 20 Yes 1144 26 26 Univent
315 CLASSROOM 1003 66 1170 26 26 Univent
316 CLASSROOM 363 24 783 17 17 Univent
317 CLASSROOM 81 5 Yes 858 19 19 Univent
318 CLASSROOM 510 34 Yes 858 19 19 Univent
319 CLASSROOM 463 30 858 19 19 Univent
320 CLASSROOM 0 0 Yes 858 19 19 Univent
- GYMNASIUM 900 60 6370 144 60 Rooftop Unit
- CAFETERIA 3339 222 5160 117 117 Rooftop Unit
- AUDITORIUM 2146 143 7008 159 143 Rooftop Unit
- KITCHEN HOOD 8665 577 1584 36 36 Rooftop Unit
- 1ST FLOOR BACK CORR. 255 17 800 18 17 Fan Coil Unit
- 1ST FLOOR CIRCLE HALL 220 14 1246 28 14 Fan Coil Unit
- 1ST FLOOR CORR INFRONT OF CAFÉ 209 13 1008 22 13 Fan Coil Unit
- 1ST FLOOR D WING OFFICE 149 9 312 7 7 Fan Coil Unit
- 1ST FLOOR ENTRANCE CORR. 360 24 1053 23 23 Fan Coil Unit
- 1ST FLOOR FRONT CORR. 1074 71 1008 22 22 Fan Coil Unit
- 1ST FLOOR FRONT HALL 562 37 1540 35 35 Fan Coil Unit
- 1ST FLOOR OFFICES 493 32 1888 42 32 Fan Coil Unit
- 2ND / 1ST FLOOR D WING CORR 380 25 1616 36 25 Fan Coil Unit
- 2ND FLOOR C WING CLUSTER OFFICE 1861 124 888 20 20 Fan Coil Unit
- 2ND FLOOR C WING CONF. ROOM 107 7 810 18 7 Fan Coil Unit
- 2ND FLOOR CIRCLE HALL 136 9 1246 28 9 Fan Coil Unit
- 2ND FLOOR D WING SHOP 97 6 408 9 6 Fan Coil Unit
- 3RD FLOOR C WING CORR. 660 44 1616 36 36 Fan Coil Unit
- 3RD FLOOR CIRCLE HALL 137 9 1246 28 9 Fan Coil Unit
- 3RD FLOOR D WING CORR. 501 33 1616 36 33 Fan Coil Unit
- 3RD FLOOR D WING OFFICE 167 11 312 7 7 Fan Coil Unit
- 3RD FLOOR SHOP 81 5 408 9 5 Fan Coil Unit
- BUILDING ENGINEER 79 5 156 3 3 Fan Coil Unit
- FACULTY BREAK ROOM 188 12 648 14 12 Fan Coil Unit
- GYM LOCKER ROOMS 254 16 532 12 12 Fan Coil Unit
- GYM TEACHER 144 9 280 6 6 Fan Coil Unit
- INSTRUMENT MUSIC 0 0 Yes 1147 26 26 Fan Coil Unit
- IT Room 268 17 396 9 9 Fan Coil Unit
- KITCHEN OFFICE 164 10 156 3 3 Fan Coil Unit
- LIBRARY 769 51 3864 87 51 Fan Coil Unit
- LIBRARY STORAGE 184 12 396 9 9 Fan Coil Unit
- MUSIC PRACTICE B 174 11 135 3 3 Fan Coil Unit
- MUSIC PRACTICE C 272 18 135 3 3 Fan Coil Unit
- MUSIC PRATICE A 126 8 135 3 3 Fan Coil Unit
- VOCAL MUSIC 0 0 Yes 1221 27 27 Fan Coil Unit
Sheet Last Modified: 03-22-2021    
School:  Martha Washington Elementary-Middle School
Vendor: Meehan
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 808 53 782 17 17 House Fan
102 Classroom 1564 104 920 20 20 House Fan
103 Classroom 540 36 667 15 15 House Fan
104 Classroom 250 16 667 15 15 House Fan
106 Classroom 529 35 667 15 15 House Fan
107 Classroom 370 24 690 15 15 House Fan
108 Classroom 279 18 667 15 15 House Fan
109 Classroom 525 35 667 15 15 House Fan
110 - 0 667 15 0 Univent
111 - 0 Yes 667 15 15 Univent
112 - 0 Yes 667 15 15 Univent
113 Classroom 0 Yes 667 15 15 Univent
201 Classroom 1290 86 667 15 15 House Fan
202 Classroom 990 66 667 15 15 House Fan
203 Classroom 425 28 759 17 17 House Fan
204 Classroom 442 29 713 16 16 House Fan
205 Classroom 345 23 621 14 14 House Fan
206 Classroom 829 55 667 15 15 House Fan
207 Classroom 479 31 660 15 15 House Fan
208 Classroom 489 32 667 15 15 House Fan
209 Classroom 394 26 667 15 15 House Fan
211 - 0 Yes 667 15 15 Univent
212 - 0 Yes 667 15 15 Univent
301 Classroom 551 36 667 15 15 House Fan
302 Classroom 850 56 667 15 15 House Fan
303 Classroom 453 30 667 15 15 House Fan
304 Classroom 236 15 1215 27 15 House Fan
305 Classroom 62 4 644 14 4 House Fan
306 Classroom 807 53 667 15 15 House Fan
307 Classroom 649 43 667 15 15 House Fan
308 Classroom 506 33 667 15 15 House Fan
309 Classroom 826 55 667 15 15 House Fan
310 Classroom 139 9 667 15 9 House Fan
- Main Office 0 Yes 420 9 9 Radiator
- Principal's Office 0 Yes 234 5 5 Radiator
- Nurse's Office 0 Yes 180 4 4 Radiator
- BE's Office 543 36 782 17 17 House Fan
- Lunch Room A 1542 102 792 18 18 House Fan
- Lunch Room B 1570 104 1540 35 35 House Fan
G2 - 0 Yes 667 15 15 Univent
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sheet Last Modified: 04-23-2021      
School:  John H. Webster Elementary School  
Vendor: Devine Brothers Devine Retest
School:  John H. Webster Elementary School- Little School House
Vendor: Devine Brothers  
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Webster Main Building
100 Classroom 1,169 77 656 14 14 Univent
101 Classroom 593 39 1,263 28 28 Univent
102 Classroom 435 29 721 16 16 Univent
103 Classroom 1,197 79 1,062 24 24 Univent
104 Classroom 251 16 897 20 16 Univent
105 Classroom 310 20 531 12 12 Univent
106 Classroom 477 31 949 21 21 Univent
108 Office 49 3 226 5 3 Air Handling Unit
110 Classroom 358 23 1,365 31 23 Air Handling Unit
111 Classroom 312 20 1,160 26 20 Air Handling Unit
112 STS Classroom 449 29 141 3 3 Air Handling Unit
113 Classroom 280 18 1,157 26 18 Air Handling Unit
114 Classroom 290 19 1,418 32 19 Air Handling Unit
200 Classroom 503 33 761 17 17 Univent
201 Classroom 369 24 597 13 13 Univent
202 Classroom 403 26 475 10 10 Univent
203 Classroom 444 29 772 17 17 Univent
204 Classroom 285 19 532 12 12 Univent
205 Classroom 329 21 823 18 18 Univent
206 Classroom 438 29 480 10 10 Univent
207 Classroom 108 7 Yes 648 14 14 Univent
208 Classroom 352 23 540 12 12 Univent
209 Classroom 387 25 537 12 12 Univent
300 Classroom 161 10 789 17 10 Univent
301 Classroom 313 20 729 16 16 Univent
302 Classroom 447 29 473 10 10 Univent
303 Classroom 137 9 Yes 690 15 15 Univent
304 Classroom 324 21 667 15 15 Univent
305 Classroom 321 21 794 18 18 Univent
306 Classroom 223 14 559 12 12 Univent
307 Classroom 171 11 790 17 11 Univent
308 Classroom 265 17 662 15 15 Univent
309 Classroom 360 24 567 12 12 Univent
311 Classroom 0 0 Yes 775 17 17 Univent
312 Classroom 397 26 573 13 13 Univent
- 2nd & 3rd corridors 251 16 0 0 Air Handling Unit
- Administration 637 42 244 5 5 Air Handling Unit
- Auditorium 2,708 180 3,216 73 73 Air Handling Unit
- Cafeteria 2,800 186 3,216 73 73 Air Handling Unit
- Child Care 1,704 113 1,115 25 25 Air Handling Unit
- Conference Office 98 6 236 5 5 Air Handling Unit
- Copy Room Office 44 2 178 4 2 Air Handling Unit
- Gym 0 0 4,403 100 0 Air Handling Unit
- IMC 0 Yes 1,363 30 30 Univent
- Kitchen Make Up 1,547 103 352 8 8 Air Handling Unit
- Main Office 201 13 244 5 5 Air Handling Unit
- Mrs. Freeland's Office 30 2 123 2 2 Air Handling Unit
- Music Room 1,406 93 696 15 15 Air Handling Unit
- Nurse's Office 87 5 412 9 5 Air Handling Unit
- Principal's Office 65 4 270 6 4 Air Handling Unit
- Vice Principal's Office 54 3 130 2 2 Air Handling Unit
Webster LSH
1 Classroom 441 29 971 22 22 Blower Coil Unit
2 Classroom 189 12 Yes 1,012 23 23 Blower Coil Unit
3 Classroom 449 29 1,016 23 23 Blower Coil Unit
4 Classroom 195 13 Yes 1,017 23 23 Blower Coil Unit
5 Classroom 0 Yes 914 20 20 Blower Coil Unit
6 Classroom 0 Yes 1,040 23 23 Blower Coil Unit
7 Classroom 0 Yes 1,003 22 22 Blower Coil Unit
8 Classroom 0 Yes 1,024 23 23 Blower Coil Unit
9 Classroom 162 10 Yes 975 22 22 Blower Coil Unit
10 Classroom 164 10 Yes 982 22 22 Blower Coil Unit
11 Classroom 188 12 Yes 1,012 23 23 Blower Coil Unit
- Student Toilets 171 11 292 6 6 Blower Coil Unit
- Custodial Closet 0 58 1 0 Fan Coil Unit
- Faculty Room 0 156 3 0 Fan Coil Unit
- Multi Purpose Room 2,361 157 1,714 38 38 Blower Coil Unit
- Office Area 409 27 274 6 6 Blower Coil Unit
- Staff Toilets 0 58 1 0 Blower Coil Unit
- Storage & Closet 0 200 4 0 Blower Coil Unit
Sheet Last Modified: 04-13-2021    
School:  John Welsh Elementary School
Vendor: Devine Brothers Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom   573.0 38 1122 25 25 Univent
102 Classroom   641.0 42 1030 23 23 Univent
103 Classroom   311.0 20 650 14 14 Univent
104 Faculty Lounge 774.0 51 750 17 17 Univent
105 Classroom   307.0 20 586 13 13 Univent
106 Classroom   674.0 44 760 17 17 Univent
200 Classroom   301.0 20 825 18 18 Univent
201 Classroom   336.0 22 825 18 18 Univent
202 Classroom   333.0 22 825 18 18 Univent
203 Classroom   574.0 38 825 18 18 Univent
204 Classroom   356.0 23 825 18 18 Univent
205 Classroom   380.0 25 825 18 18 Univent
206 Classroom   405.0 27 825 18 18 Univent
209 Classroom   330.0 22 825 18 18 Univent
210 Library 642.0 42 1218 27 27 Univent
211 Classroom   320.0 21 825 18 18 Univent
212 Classroom   610.0 40 825 18 18 Univent
300 Classroom   858.0 57 830 18 18 Univent
301A Classroom   341.0 22 393 8 8 Univent
301B Classroom   0 Yes 393 8 8 Univent
302 Classroom   887.0 59 830 18 18 Univent
303 Classroom   341.0 22 830 18 18 Univent
304 Classroom   790.0 52 830 18 18 Univent
305 Classroom   885.0 59 830 18 18 Univent
306 Classroom   590.0 39 423 9 9 Univent
308 Classroom   420.0 28 411 9 9 Univent
309 Classroom   454.0 30 830 18 18 Univent
310 Classroom   705.0 47 830 18 18 Univent
311 Classroom   890.0 59 830 18 18 Univent
312 Classroom   798.0 53 830 18 18 Univent
400 Classroom   346.0 23 825 18 18 Univent
401 Classroom   874 58 825 18 18 Univent
402 Classroom   801 53 825 18 18 Univent
403 Classroom   852 56 825 18 18 Univent
404 Classroom   368.0 24 825 18 18 Univent
405 Classroom   820.0 54 825 18 18 Univent
406 Classroom   328 21 425 9 9 Univent
408 Classroom   426 28 410 9 9 Univent
409 Classroom   417 27 825 18 18 Univent
410 Classroom   558 37 825 18 18 Univent
411 Classroom   897 59 825 18 18 Univent
412 Classroom   0.0 0 403 9 0 Univent
412A Classroom   820.0 54 403 9 9 Univent
- Main Office 438.0 29 1038 23 23 Univent
- Auditorium 0.0 0 3868 87 0 Air Handling Unit
- Gym 4,931.0 328 3509 79 79 Air Handling Unit
Sheet Last Modified: 04-30-2021    
School:  New West Philadelphia High School
Vendor: Chadwick
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
107 Nurse Office 0 264 6 0 Air Handing Unit
107A Nurse Exam Room 0 149 3 0 Air Handing Unit
107B Nurse Suite 0 100 2 0 Air Handing Unit
107C Nurse Suite 0 110 2 0 Air Handing Unit
101C Maker Room 0 Yes 1268 28 28 Air Handing Unit
200 - 145 9 875 19 9 Univent
201 Classroom 190 12 539 12 12 Univent
202 - 308 20 895 20 20 Univent
203 - 165 11 899 20 11 Univent
204 - 398 26 900 20 20 Univent
205 - 105 7 877 19 7 Univent
206 - 344 22 898 20 20 Univent
207 - 315 21 877 19 19 Univent
208 - 281 18 937 21 18 Univent
216 - 176 11 1330 30 11 Univent
300 - 210 14 878 19 14 Univent
301 - 0 0 544 12 0 Univent
302 - 470 31 898 20 20 Univent
303 - 205 13 900 20 13 Univent
304 - 235 15 900 20 15 Univent
305 - 0 874 19 0 Univent
306 - 190 12 896 20 12 Univent
307 Classroom 0 Yes 1387 31 31 Univent
308 - 230 15 897 20 15 Univent
309 Classroom 0 Yes 1357 30 30 Univent
310 - 115 7 898 20 7 Univent
311 - 0 900 20 0 Univent
312 - 625 41 872 19 19 Univent
313 - 0 877 19 0 Univent
315 - 425.0 28 876 19 19 Univent
316 - 190.0 12 399 9 9 Univent
317 - 205.0 13 902 20 13 Univent
318 - 365.0 24 1274 28 24 Univent
319 - 195.0 13 899 20 13 Univent
320 - 0 876 19 0 Univent
321 - 425.0 28 894 20 20 Univent
Gymnasium Gymnasium 0.0 0 6370 144 0 Univent
Gymnasium Gymnasium 0.0 0 Yes 10648 242 242 Univent
Sheet Last Modified: 04-13-2021    
School:  Widener Memorial Elementary School
Vendor: EMCOR
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
2 - 1,283.0 85 2800 63 63 Carrier / Perimeter Heater
3 - 500.0 33 1344 30 30 Carrier / Perimeter Heater
4 - 70.0 4 1332 30 4 Carrier / Perimeter Heater
5 - 146.0 9 527 11 9 Carrier / Perimeter Heater
6 - 38.0 2 744 16 2 Carrier / Perimeter Heater
7 - 70.0 4 912 20 4 Carrier / Perimeter Heater
8 - 317.0 21 460 10 10 Carrier / Perimeter Heater
9 - 311.0 20 480 10 10 Carrier / Perimeter Heater
10 - 291.0 19 504 11 11 Carrier / Perimeter Heater
11 - 290.0 19 504 11 11 Carrier / Perimeter Heater
12 - 292.0 19 744 16 16 Carrier / Perimeter Heater
13 - 210.0 14 759.5 17 14 Carrier / Perimeter Heater
14 - 244.0 16 759.5 17 16 Carrier / Perimeter Heater
15 - 224.0 14 759.5 17 14 Carrier / Perimeter Heater
16 - 225.0 15 759.5 17 15 Carrier / Perimeter Heater
17 - 260.0 17 759.5 17 17 Carrier / Perimeter Heater
18 - 304.0 20 759.5 17 17 Carrier / Perimeter Heater
19 - 0.0 0 Yes 759.5 17 17 Carrier / Perimeter Heater
20 - 356.0 23 759.5 17 17 Carrier / Perimeter Heater
21 - 271.0 18 759.5 17 17 Carrier / Perimeter Heater
22 - 282.0 18 759.5 17 17 Carrier / Perimeter Heater
23 - 275.0 18 759.5 17 17 Carrier / Perimeter Heater
24 - 0.0 0 Yes 759.5 17 17 Carrier / Perimeter Heater
25 - 192.0 12 1014 23 12 Carrier / Perimeter Heater
26 - 2,008.0 133 891 20 20 Air Handling Unit
27 - 416.0 27 619.5 14 14 Air Handling Unit
28 - 416.0 27 925 21 21 Air Handling Unit
31A - 0.0 0 Yes 190 4 4 Carrier / Perimeter Heater
31B Nurse's Office 0.0 0 Yes 196 4 4 Carrier / Perimeter Heater
32 - 0.0 0 272 6 0 Carrier / Perimeter Heater
33 - 396.0 26 1271 28 26 Carrier / Perimeter Heater
34 - 622.0 41 1470 33 33 Carrier / Perimeter Heater
35A - 265.0 17 720 16 16 Carrier / Perimeter Heater
35B - 222.0 14 1107 25 14 Carrier / Perimeter Heater
35C - 0.0 0 Yes 364 8 8 Carrier / Perimeter Heater
36 - 0.0 0 1288 29 0 Carrier / Perimeter Heater
37 - 235.0 15 600 13 13 Carrier / Perimeter Heater
38 - 257.0 17 600 13 13 Carrier / Perimeter Heater
39 - 88.0 5 462 10 5 Carrier / Perimeter Heater
40 - 115.0 7 472 10 7 Carrier / Perimeter Heater
41 - 235.0 15 702 15 15 Carrier / Perimeter Heater
46 Small Cafeteria 182.0 12 1347 30 12 Carrier / Perimeter Heater
47 - 75.0 5 Yes 315 7 7 Carrier / Perimeter Heater
48 - 90.0 6 817 18 6 Carrier / Perimeter Heater
103 - 290.0 19 840 19 19 Carrier / Perimeter Heater
104 - 310.0 20 840 19 19 Carrier / Perimeter Heater
105 - 410.0 27 810 18 18 Carrier / Perimeter Heater
106 - 300.0 20 868 19 19 Carrier / Perimeter Heater
107 - 530.0 35 850 19 19 Carrier / Perimeter Heater
108 - 489.0 32 840 19 19 Carrier / Perimeter Heater
109 - 40.0 2 Yes 840 19 19 Carrier / Perimeter Heater
110 - 550.0 36 840 19 19 Carrier / Perimeter Heater
101 - 430.0 28 1271 28 28 Carrier / Perimeter Heater
102A - 124.0 8 140 3 3 Carrier / Perimeter Heater
102B - 165.0 11 140 3 3 Carrier / Perimeter Heater
111A - 98.0 6 140 3 3 Carrier / Perimeter Heater
111B - 110.0 7 140 3 3 Carrier / Perimeter Heater
112 - 905.0 60 1271 28 28 Carrier / Perimeter Heater
- Auditorium 1,042.0 69 4087 92 69 Air Handling Unit
- Cafeteria 918.0 61 2720 61 61 Carrier / Perimeter Heater
- Computer Lab 320.0 21 Yes 943 21 21 Air Handling Unit
- Food Service "A & B" 0.0 0 1320 30 0 Carrier / Perimeter Heater
- Game Room 577.0 38 675 15 15 Carrier / Perimeter Heater
- GYM 174.0 11 3721 84 11 Air Handling Unit
- Kitchen 3,011.0 200 1191 27 27 Make-Up Air Unit
- Music Room 2,765.0 184 2040 46 46 Air Handling Unit
- Pool 0.0 0 7467 169 0 Air Handling Unit
Sheet Last Modified: 04-30-2021    
School: Frances E. Willard Elementary School
Vendor: Devine Main Building Retest
School: Willard Annex
Vendor: EMCOR Fluidics EMCOR Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
Willard Main Building
100A OFFICE 39 2 181 4 2 Air Handling Unit
100B OFFICE 31 2 121 2 2 Air Handling Unit
100C OFFICE 39 2 43 0 0 Air Handling Unit
100D OFFICE 37 2 121 2 2 Air Handling Unit
100E OFFICE 35 2 120 2 2 Air Handling Unit
100F OFFICE 51 3 345 7 3 Air Handling Unit
100G Conference 85 5 279 6 5 Air Handling Unit
100H BREAK ROOM 70 4 145 3 3 Air Handling Unit
100I OFFICE 76 5 210 4 4 Air Handling Unit
101 Classroom 310 20 984 22 20 Univent and Air Handling Unit
102 Classroom 304 20 1059 24 20 Univent and Air Handling Unit
103 Classroom 321 21 889 20 20 Univent and Air Handling Unit
104 Classroom 282 18 1086 24 18 Univent and Air Handling Unit
105 Classroom 295 19 677 15 15 Univent and Air Handling Unit
106 Classroom 331 22 800 18 18 Univent and Air Handling Unit
107 Nurse OFFICE 35 2 277 6 2 Fan Coil
107A OFFICE 45 3 161 3 3 Fan Coil
107C OFFICE 14 0 150 3 0 Air Handling Unit
107D OFFICE 26 1 103 2 1 Air Handling Unit
107G COMPUTER LAB 298 19 1033 23 19 Univent
109 Classroom 282 18 802 18 18 Univent and Air Handling Unit
110 Classroom 282 18 818 18 18 Univent and Air Handling Unit
111 Classroom 295 19 818 18 18 Univent and Air Handling Unit
112 Classroom 306 20 813 18 18 Univent and Air Handling Unit
113 Classroom 305 20 813 18 18 Univent and Air Handling Unit
114 Classroom 280 18 815 18 18 Univent and Air Handling Unit
115 Classroom 293 19 815 18 18 Univent and Air Handling Unit
116 Classroom 302 20 813 18 18 Univent and Air Handling Unit
117 Classroom 295 19 813 18 18 Univent and Air Handling Unit
121 Classroom 381 25 1059 24 24 Univent and Air Handling Unit
122 Music Room 328 21 1189 27 21 Univent
123 Classroom 392 26 1061 24 24 Univent and Air Handling Unit
126 Staff Lounge 397 26 419 9 9 Univent and Air Handling Unit
128 Workroom 154 10 285 6 6 Air Handling Unit
132 BE Office 78 5 135 3 3 Air Handling Unit
200E IMC 60 4 80 1 1 Air Handling Unit
200F CONF ROOM 325 21 352 8 8 Univent
201 Classsroom 425 28 814 18 18 Univent and Air Handling Unit
202 Classsroom 530 35 814 18 18 Univent and Air Handling Unit
203 Classsroom 394 26 814 18 18 Univent and Air Handling Unit
204 Classsroom 517 34 814 18 18 Univent and Air Handling Unit
205 Classsroom 432 28 810 18 18 Univent and Air Handling Unit
206 Classsroom 407 27 812 18 18 Univent and Air Handling Unit
207 Classsroom 368 24 685 15 15 Univent and Air Handling Unit
208 ART 479 31 1059 24 24 Univent
209 Classsroom 379 25 807 18 18 Univent and Air Handling Unit
210 Classsroom 382 25 820 18 18 Univent and Air Handling Unit
211 Classsroom 389 25 821 18 18 Univent and Air Handling Unit
212 Classsroom 375 25 814 18 18 Univent and Air Handling Unit
213 Classsroom 392 26 814 18 18 Univent and Air Handling Unit
214 Classsroom 382 25 811 18 18 Univent and Air Handling Unit
215 Classsroom 420 28 811 18 18 Univent and Air Handling Unit
216 Classsroom 301 20 811 18 18 Univent and Air Handling Unit
217 Classsroom 411 27 811 18 18 Univent and Air Handling Unit
221 Classroom 301 20 658 14 14 Univent
223 Classroom 357 23 887 20 20 Univent and Air Handling Unit
224 Classroom 585 39 1410 32 32 Univent and Air Handling Unit
225 Classroom 175 11 1267 28 11 Univent and Air Handling Unit
- Auditorium 3411 227 2755 62 62 Air Handling Unit
- Cafeteria 2559 170 5041 114 114 Air Handling Unit
- Gym 2627 175 5960 135 135 Air Handling Unit
- LIBRARY 514 34 2639 59 34 Air Handling Unit
- Lobby 1166 77 3402 77 77 Air Handling Unit
- Main Office 236 15 1165 26 15 Air Handling Unit
Willard Annex
#1 Classroom 334 22 828 18 18 Rooftop Unit
#2 Classroom 534 35 828 18 18 Rooftop Unit
#3 Classroom 667 44 828 18 18 Rooftop Unit
#4 Classroom 595 39 828 18 18 Rooftop Unit
#5 Classroom 453 30 828 18 18 Rooftop Unit
#6 Classroom 1118 74 828 18 18 Rooftop Unit
- Admin Desk/Office 402 26 180 4 4 Rooftop Unit
- Entrance Hallway 93 6 N/A 0 0 Rooftop Unit
- Kitchen 123 8 180 4 4 Rooftop Unit
- Office Space 29 1 200 4 1 Rooftop Unit
- Play Area 2452 163 1228 27 27 Rooftop Unit
- Principals Office 257 17 120 2 2 Rooftop Unit
- BE Office 362 24 195 4 4 Rooftop Unit
- Health/Teachers Lounge 0 0 240 5 0 Univent
Sheet Last Modified: 04-30-2021    
School:  Woodrow Wilson Middle School
Vendor: Capital
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Classroom 693 46 1080 24 24 Air Handling Unit
102 Classroom 429 28 853 19 19 Air Handling Unit
103 Classroom 962 64 672 15 15 Air Handling Unit
104 Room 0 616 14 0 Air Handling Unit
105 Classroom 540 36 1038 23 23 Air Handling Unit
107 Classroom 882 58 968 22 22 Air Handling Unit
108 Room 0 352 8 0 Air Handling Unit
109 Classroom 506 33 374 8 8 Air Handling Unit
110 Room 0 660 15 0 Air Handling Unit
111 Classroom 277 18 812 18 18 Air Handling Unit
112 Classroom 271 18 954 21 18 Air Handling Unit
116 Classroom 143 9 697 15 9 Air Handling Unit
117 Classroom 191 12 697 15 12 Air Handling Unit
118 Classroom 146 9 697 15 9 Air Handling Unit
119 Classroom 98 6 349 7 6 Air Handling Unit
201 Classroom 0 0 Yes 727 16 16 Air Handling Unit
202 Classroom 338 22 687 15 15 Air Handling Unit
203 Classroom 451 30 726 16 16 Air Handling Unit
204 Office 0 Yes 160 3 3 Air Handling Unit
205 Classroom 311 20 348 7 7 Air Handling Unit
206 Classroom 452 30 324 7 7 Air Handling Unit
207 Room 0 308 7 0 Air Handling Unit
208-C Main Office 0 572 13 0 Air Handling Unit
209 Classroom 765 51 901 20 20 Air Handling Unit
210 Classroom 394 26 1034 23 23 Air Handling Unit
211 Classroom 356 23 849 19 19 Air Handling Unit
212 Classroom 318 21 867 19 19 Air Handling Unit
213 Classroom 213 14 687 15 14 Air Handling Unit
214 Classroom 596 39 727 16 16 Air Handling Unit
215 Classroom 1059 70 668 15 15 Air Handling Unit
216 Classroom 1311 87 791 17 17 Air Handling Unit
217 Classroom 1097 73 682 15 15 Air Handling Unit
218 Classroom 810 54 702 15 15 Air Handling Unit
219 Classroom 1352 90 700 15 15 Air Handling Unit
220 Classroom 1207 80 682 15 15 Air Handling Unit
221 Classroom 897 59 791 17 17 Air Handling Unit
222 Classroom 608 40 668 15 15 Air Handling Unit
223 Classroom 305 20 347 7 7 Air Handling Unit
224 Room 0 308 7 0 Air Handling Unit
226 Classroom 86 5 216 4 4 Air Handling Unit
227 Classroom 163 10 347 7 7 Air Handling Unit
228 Classroom 208 13 694 15 13 Air Handling Unit
245 Room 0 Yes 87 1 1 Air Handling Unit
246 Room 0 Yes 82 1 1 Air Handling Unit
247 Room 0 Yes 110 2 2 Air Handling Unit
301 Classroom 813 54 727 16 16 Air Handling Unit
302 Classroom 439 29 684 15 15 Air Handling Unit
303 Classroom 605 40 697 15 15 Air Handling Unit
304 Classroom 552 36 972 22 22 Air Handling Unit
305 Classroom 518 34 914 20 20 Air Handling Unit
306 Classroom 497 33 898 20 20 Air Handling Unit
307 Classroom 781 52 965 21 21 Air Handling Unit
308 Classroom 466 31 833 18 18 Air Handling Unit
309 Classroom 735 49 894 20 20 Air Handling Unit
309-A Room 0 220 5 0 Air Handling Unit
310 Classroom 765 51 924 21 21 Air Handling Unit
311 Classroom 1322 88 958 21 21 Air Handling Unit
312 Classroom 660 44 728 16 16 Air Handling Unit
313 Classroom 403 26 313 7 7 Air Handling Unit
11-9 Classroom 1020 68 314 7 7 Air Handling Unit
315 Classroom 1082 72 668 15 15 Air Handling Unit
316 Classroom 1750 116 791 17 17 Air Handling Unit
317 Classroom 2057 137 685 15 15 Air Handling Unit
318 Classroom 1824 121 699 15 15 Air Handling Unit
319 Classroom 1263 84 699 15 15 Air Handling Unit
320 Classroom 642 42 684 15 15 Air Handling Unit
321 Classroom 658 43 791 17 17 Air Handling Unit
322 Classroom 508 33 668 15 15 Air Handling Unit
323 Classroom 282 18 347 7 7 Air Handling Unit
324 Classroom 127 8 694 15 8 Air Handling Unit
327 Room 0 264 6 0 Air Handling Unit
328 Classroom 107 7 694 15 7 Air Handling Unit
401 Room 0 264 6 0 Rooftop Unit
401A Room 0 572 13 0 Rooftop Unit
402 Room 0 836 19 0 Rooftop Unit
403 Room 0 1056 24 0 Rooftop Unit
404 Room 0 1188 27 0 Rooftop Unit
406 Room 0 44 1 0 Rooftop Unit
407 Room 0 44 1 0 Rooftop Unit
408 Room 0 44 1 0 Rooftop Unit
409 Room 0 132 3 0 Rooftop Unit
410 Counselor's Office 0 Yes 165 3 3 Rooftop Unit
- Auditorium 0 3740 85 0 Air Handling Unit
- Gym 1 0 2816 64 0 Air Handling Unit
- Gym 2 0 2816 64 0 Air Handling Unit
- Lunchroom 1 0 2640 60 0 Air Handling Unit
- Lunchroom 2 0 2596 59 0 Air Handling Unit
Sheet Last Modified: 03-29-2021    
School:  Wister Elementary School
Vendor: Mastery Charter Property Management
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Classroom 307 20 0 0 Unit Ventilator
101 Classroom 319 21 0 0 Unit Ventilator
103 Classroom 148 9 0 0 Unit Ventilator
106 Lounge 202 13 0 0 Unit Ventilator
107A Main Office 0 0 0 0 Unit Ventilator
108 Classroom 316 21 1134 25 21 Unit Ventilator
109 Classroom 313 20 1094 24 20 Unit Ventilator
110 Storage 215 14 0 0 Unit Ventilator
111 Classroom 339 22 1414 32 22 Unit Ventilator
200 Classroom 309 20 0 0 Unit Ventilator
201 Office 162 10 0 0 Unit Ventilator
202 Classroom 138 9 0 0 Unit Ventilator
203 Classroom 311 20 0 0 Unit Ventilator
204 Classroom 271 18 0 0 Unit Ventilator
205 Classroom 144 9 0 0 Unit Ventilator
206 Classroom 304 20 0 0 Unit Ventilator
207 Classroom 304 20 0 0 Unit Ventilator
208 Classroom 308 20 0 0 Unit Ventilator
209C Classroom 337 22 0 0 Unit Ventilator
210 Classroom 319 21 0 0 Unit Ventilator
211 Classroom 302 20 0 0 Unit Ventilator
212 Classroom 313 20 0 0 Unit Ventilator
213 Classroom 331 22 0 0 Unit Ventilator
214 Classroom 349 23 0 0 Unit Ventilator
300 Classroom 299 19 0 0 Unit Ventilator
301 Office 129 8 0 0 Unit Ventilator
302 Classroom 153 10 0 0 Unit Ventilator
303 Classroom 308 20 0 0 Unit Ventilator
304 Classroom 330 22 0 0 Unit Ventilator
305 Classroom 332 22 0 0 Unit Ventilator
306 Classroom 311 20 0 0 Unit Ventilator
307 Classroom 312 20 0 0 Unit Ventilator
- Auditorium 2036 135 0 0 AHU
- Gym 1544 102 0 0 AHU
Sheet Last Modified: 3/17/21    
School:  Sustainability Workshop School
Vendor: Goldner
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
101 Corridor 7 0 533 12 0 VAV
102 Closet 6 0 45 1 0 VAV
105 Nurses Office / Classroom 0 150 3 0 HU
106 Woodshop 43 2 1003 22 2 HU
110 Classroom 23 1 884 20 1 VAV
111 Auto Service 0 0 1761 40 0 HU and Univent
111 Classroom 0 756 17 0 Univent
112 Training Classroom 0 0 459 10 0 HU and Univent
114 Tool Storage 0 0 450 10 0 HU and Univent
117 Body Shop 0 0 2944 66 0 HU
121 Classroom 0 729 16 0 Univent
200 Corridor 33 2 1868 42 2 VAV
201 Classroom 42 2 740 16 2 VAV
206 Main Office 7 0 234 5 0 VAV
207 Office 6 0 192 4 0 VAV
208 Principle Office 5 0 80 1 0 VAV
209 Copy Room 12 0 132 3 0 VAV
210 Classroom 25 1 748 17 1 VAV
210-C Counselors office in front of classroom 210 2 0 NA 0 0 VAV
212 Mechanical room 0 620 14 0 AHU
212 Classroom 366 24 720 16 16 VAV
213 Classroom 1,829.00 121 691 15 15 VAV
214 Classroom 837 55 761 17 17 VAV
215 Classroom 839 55 961 21 21 VAV
215A Classroom 96 6 NA 0 0 VAV
216 Classroom 655 43 1012 23 23 VAV
219 Corridor Bathroom 40 2 48 1 1 VAV
- Automotive Classroom 0 0 NA 0 0 HU and Univent
- Body Shop Classroom 0 0 NA 0 0 Univent
- Cafeteria Bathroom 41 2 49 1 1 VAV
- Cafeteria 402 26 2550 57 26 RTU
- Computer Lab 60 4 312 7 4 HU
- Kitchen 0 0 504 11 0 MUA
- Mr. Boyd Office 185 12 152 3 3 VAV and RETURN DUCT
- Mr. Tobias Office 185 12 80 1 1 VAV
- Mrs. Walker Office 138 9 80 1 1 VAV
- Ms. Phoebe Office 188 12 91 2 2 VAV
- Nurse Room 0 0 NA 0 0 HU and Univent
- Storage / Office 15 1 120 2 1 RTU
- Woodshop Office 43 2 NA 0 0 HU
- Woodshop Saw 24 1 NA 0 0 HU
Sheet Last Modified: 04-30-2021    
School:  Richard R. Wright Elementary School
Vendor: Goldner Goldner Retest
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
100 Art Room 280 18 Yes 1400 31 31 Unit Ventilator
108-A 1st Floor Gymnasium Office 5 0 100 2 0 Air Handling Unit
112-A 1st Floor Music Practice 10 0 100 2 0 Air Handling Unit
112-B 1st Floor Music Practice 19 1 100 2 1 Air Handling Unit
114 Classroom 334 22 Yes 1360 30 30 Unit Ventilator
115 Classroom 358 23 Yes 1360 30 30 Unit Ventilator
118 Nurse area 0 0 Yes 378 8 8 Unit Ventilator
119 Nurse area 0 0 Yes 216 4 4 Unit Ventilator
120 Classroom 273 18 Yes 1360 30 30 Unit Ventilator
121 Classroom 435 29 1360 30 29 Unit Ventilator
122 Classroom 273 18 Yes 1360 30 30 Unit Ventilator
201 Classroom 342 22 Yes 1610 36 36 Unit Ventilator
202 Classroom 634 42 1702 38 38 Unit Ventilator
203 Classroom 349 23 Yes 1120 25 25 Unit Ventilator
204 Classroom 358 23 0 0 Unit Ventilator
205 Classroom 482 32 870 19 19 Unit Ventilator
206 Classroom 499 33 812 18 18 Unit Ventilator
207 Classroom 460 30 870 19 19 Unit Ventilator
208 Classroom 232 15 Yes 841 19 19 Unit Ventilator
209 Classroom 341 22 0 0 Unit Ventilator
210 Classroom 413 27 899 20 20 Unit Ventilator
211 Classroom 270 18 Yes 1715 38 38 Unit Ventilator
212 Classroom 434 28 Yes 1911 43 43 Unit Ventilator
213 Classroom 310 20 Yes 1715 38 38 Unit Ventilator
214 Classroom 799 53 1786 40 40 Unit Ventilator
215 Classroom 325 21 870 19 19 Unit Ventilator
216 Classroom 296 19 Yes 930 21 21 Unit Ventilator
217 Classroom 568 37 870 19 19 Unit Ventilator
218 Classroom 415 27 870 19 19 Unit Ventilator
219 Classroom 289 19 870 19 19 Unit Ventilator
220 Classroom 278 18 870 19 18 Unit Ventilator
221 Classroom 339 22 899 20 20 Unit Ventilator
222 Classroom 372 24 784 17 17 Unit Ventilator
223 Classroom 369 24 Yes 1739 39 39 Unit Ventilator
224 Classroom 284 18 Yes 1739 39 39 Unit Ventilator
225 Room 211 14 196 4 4 Air Handling Unit
227 Room 119 7 196 4 4 Air Handling Unit
- 1st Floor Conference Room 89.0 5 108 2 Air Handling Unit
- 1st Floor Counselor's Office 17 1 100 2 Air Handling Unit
- 1st Floor Engineer's Office 30 2 36 0 Air Handling Unit
- 1st Floor Entry Hallway 79 5 140 3 Air Handling Unit
- 1st Floor CSC Office 4 0 100 2 Air Handling Unit
- 1st Floor IT Room 10 0 100 2 Air Handling Unit
- 1st Floor Main Office 98.0 6 144 3 Air Handling Unit
- 1st Floor Office Storage 0 0 160 3 Air Handling Unit
- 1st Floor Prinicpal's Office 23 1 140 3 Air Handling Unit
- 1st Floor Psychologist's Office 14 0 140 3 Air Handling Unit
- 1st Floor Small Kitchen 56.0 3 84 1 Air Handling Unit
- 1st Floor Staff Lounge 447 29 1556 35 29 Unit Ventilator
- 2nd Floor Computer Storage 44 2 196 4 2 Air Handling Unit
- 2nd Floor Library 2,489 165 556 12 12 Air Handling Unit
- 2nd Floor Library Lounge 131 8 192 4 4 Air Handling Unit
- 2nd Floor Library Storage 109 7 336 7 7 Air Handling Unit
- 2nd Floor Office space 250 16 216 4 4 Unit Ventilator
- 2nd Floor Storage space 358 23 432 9 9 Unit Ventilator
- Cafetorium 4,622 308 4730 107 107 Air Handling Unit
- Gym 890 59 5644 128 59 Air Handling Unit
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sheet Last Modified: 5-3-2021    
School:  William H. Ziegler Elementary School
Vendor: Chadwick Chadwick Part 2 Chadwick Part 3
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
102 Classroom 147 9 140 3 3 Unit Ventilator
103 Classroom 309 20 836 19 19 Unit Ventilator
104 Classroom 346 23 836 19 19 Unit Ventilator
105 Classroom 296 19 836 19 19 Unit Ventilator
106 Office/Classroom 0 Yes 322 7 7 Unit Ventilator
107 Classroom 161 10 Yes 638 14 14 Unit Ventilator
108 Nurse 0 Yes 171 3 3 Unit Ventilator
109 Classroom 0 Yes 696 15 15 Unit Ventilator
111 Classroom 331 22 682 15 15 Energy Recovery Unit
112 Classroom 300 20 682 15 15 Energy Recovery Unit
113 Classroom 338 22 682 15 15 Energy Recovery Unit
114 Classroom 301 20 682 15 15 Energy Recovery Unit
115 Classroom 312 20 682 15 15 Energy Recovery Unit
116 Classroom 318 21 682 15 15 Energy Recovery Unit
117 Classroom 318 21 682 15 15 Energy Recovery Unit
125 Classroom 294 19 600 13 13 Energy Recovery Unit
201 Classroom 398 26 598 13 13 Unit Ventilator
202 Classroom 511 34 644 14 14 Unit Ventilator
203 Classroom   0 Yes 390 8 8 Unit Ventilator
204 Classroom 417 27 780 17 17 Unit Ventilator
205 Classroom 315 21 962 21 21 Unit Ventilator
206 Classroom 110 7 Yes 644 14 14 Unit Ventilator
207 Classroom   0 Yes 243 5 5 Unit Ventilator
208 Teacher's Lounge   0 Yes 280 6 6 Unit Ventilator
210 Classroom 147 9 Yes 644 14 14 Unit Ventilator
212 Classroom 534 35 667 15 15 Unit Ventilator
213 Classroom 332 22 682 15 15 Energy Recovery Unit
214 Classroom 166 11 Yes 682 15 15 Energy Recovery Unit
215 Classroom 281 18 682 15 15 Energy Recovery Unit
216 Classroom 265 17 682 15 15 Energy Recovery Unit
217 Classroom 261 17 682 15 15 Energy Recovery Unit
218 Classroom 275 18 682 15 15 Energy Recovery Unit
220 Classroom 269 17 748 17 17 Energy Recovery Unit
- Cafeteria  2,750 183 2,736 62 62 Air Handling Unit
- Gymasium 1,073 71 3,498 79 71 Air Handling Unit
- Hallway 105 7 0 0 Air Handling Unit
- Library/IMC 983 65 1,953 44 44 Air Handling Unit
- Main Office  0 Yes 456 10 10 Unit Ventilator
- Principal's Office 0 Yes 198 4 4 Unit Ventilator
- Science Lab 228 15 968 22 15 Energy Recovery Unit